background image

4.

5. Grooved-End 

Connections

• 

ANSI/AWWA C606 grooved Inlet, Outlet & Drain.

Groove Dimensions (Inlet & Outlet)

System 

Size

Outlet

Diameter

Groove

Diameter

Groove

Width

Outlet Face

to Groove

2”

(50 mm) 

2.375” 

(60mm)

2.250” 

(57mm)

5/16”

(8mm)

5/8”

(16mm)

 2½”

(65 mm)

2.875” 

(73mm)

2.720” 

(69mm)

3”

(80 mm)

3.500” 

(89mm)

3.344” 

(85mm)

4”

(100mm)

4.500”

(114mm)

4.334”

(110mm)

3/8”

(10mm)

6”

(150mm)

6.625”

(168mm)

6.455”

(164mm)

8”

(200 mm)

8.625” 

(219mm)         

8.441” 

(214mm)  

7/16” 

(11mm) 

3/4” (19mm)

Groove Dimensions (Drain)

System 

Size

Outlet

Diameter

Outer 

Diameter

Groove

Diameter

Groove

Width

Outlet 

Face

to Groove

2”

(50mm)

1¼”

(32mm)

1.660” 

(42mm)

1.535”

(39mm)

5/16”

(8mm) 

5/8”

(16mm)

2½”

(65mm)

3”

(80mm)

4”

(100mm)

2”

(50mm)

2.375”

(60mm)

2.250”

(57mm)

3/8”

(10mm)

6”

(150mm)

8” 

(200mm)

6. Flanged-End 

Connections

Flange Dimensions (Inlet & Outlet)

System 

size:

Flange 

Type

Bolt 

Circle 

Diameter

Bolt Hole 
Diameter

Flange 

Outside 

Diameter

Flange 

thickness

Number 

of Bolts

8”

(200mm)

ASME 

B16.5

Class 

150

11¾” 

(298mm)

7/8” 

(22mm)

13½” 

(343mm)

1” 

(25.4mm)

8

Flange Dimensions ( Drain)

System 

size:

Flange 

Type

Bolt 

Circle 

Diameter

Bolt Hole 
Diameter

Flange 

Outside 

Diameter

Flange 

thickness

Number 

of Holes

8”

(200mm)

ASME 

B16.5

Class 

150

4¾” 

(120mm)

3/4”

(19mm)

6”

 (150mm)

3/4”

” (19mm)

4

PrePak units are also available without their door-mounted 

Potter PFC-4410-RC Releasing/Control Panel and Air Com-
pressor. These units will still retain their Listings/Approvals, 
however the installing contractor should make sure that any 
remote controlled Releasing/Control Panels used with these 
units are Listed/Approved and programmed to handle the 
required sequence of operation necessary to operate the 
automatic sprinkler system. Any unauthorized modification 
or addition made on-site to a factory-built Listed/Approved 
unit will void the Listing/Approval. Such modifications or 
additions may void the unit’s warranty as well. Consult Re-
liable’s Technical Services Department before proceeding 
with any such modifications or additions.

Technical Data

1.  The Reliable Type F Model DDX PrePaK is rated for 

a minimum water supply pressure of 20 psi (1.4 bar) 
and a maximum water supply pressure of 250 psi 
(17.2 bar). Note: 1 bar = 100 kPa.

2.  Friction loss, expressed in equivalent length of 

Schedule 40 pipe and based on Hazen-Williams For-
mula is:

System Size:

Equivalent Length

2” (50mm) 

19.4 ft (1.3 m)  

2½” (65mm) 

24.5 ft (1.8 m)  

3” (80mm) 

28.9 ft (3.8 m)  

4” (100 mm)

 32.8 ft (17.7 m)  

6” (150 mm) 

54.7 ft (21.8 m)  

 8" (200mm)

79.3ft (24.2m)

These values account for the Model DDX Deluge Valve, 
supply manifold tee, butterfly control valve, and small 
pipe/manifold located directly above Model DDX Deluge 
Valve.
3. Shipping 

Weight:

System Size

Weight

2” (50 mm), 2½” (65 mm)

& 3” (80 mm)

554 lb. (252 kg)

4” (100 mm)

 710 lbs (322 kg)

6” (150 mm)

800 lbs (363 kg)

8" (200mm)

1350lbs (531kg)

4. Dimensions: 

System Size

Equivalent Dimensions

2” (50 mm), 2½” (65 mm) & 3” 

(80 mm)

24” W x 27” D x 68” H

(0.61 m W x 0.69 m D x 1.73 m H)

4” (100 mm) & 6” (150 mm)

 25.7” W x 28.9” D x 68” H

(0.65 m W x 0.73 m D x 1.73 m H)

8” (200mm) 

30.3” W X 36.6” D X 74” H
(0.77 M X 0.93M X 1.87M)

(Refer to Fig. 1 for additional dimensions)

Summary of Contents for DDX PrePaK

Page 1: ...visory Pressure Double Interlock Electric Pneumatic Release Contents Page General Description 2 Listings and Approvals 2 Technical Data 4 Installation Requirements 5 System Operation 7 System Reset Procedure 7 Inspection Testing and Maintenance 8 Diagrams Assembly Dimensions 3 Potter PFC 4410 RC Releasing Control Panel 10 Terminal Box Wiring 11 Factory Installed Electrical Devices 12 14 Detector C...

Page 2: ...urged of its su pervisory air sufficiently enough for the Model LP Dry Valve Actuator to operate This purging is usually caused by the operation of an automatic sprinkler In the event that the system piping is ruptured or a sprin kler head is accidentally opened the Model LP Dry Valve Actuator will open and a low system air pressure alarm will sound The Model DDX Deluge Valve however will not be r...

Page 3: ...3 Fig 1 ...

Page 4: ...ote controlled Releasing Control Panels used with these units are Listed Approved and programmed to handle the required sequence of operation necessary to operate the automatic sprinkler system Any unauthorized modification or addition made on site to a factory built Listed Approved unit will void the Listing Approval Such modifications or additions may void the unit s warranty as well Consult Re ...

Page 5: ...ditional low pressure air test In some cases hydrostatic testing in accordance with the NFPA 13 requirements noted above will result in pressures that exceed the working pressure of the valve and trim kit for the two hour test period The valve and applicable trim kit have been tested approved and listed under these conditions and as such hydrostatic testing in accordance with NFPA 13 is ac ceptabl...

Page 6: ...y fill the sprinkler system with air the steel enclosure s door should remain open to provide maximum intake air flow to the air compressor The air compressor is connected to a storage tank This tank functions as a reser voir providing make up air to compensate for small inter mittent leaks in the sprinkler system It should be noted that significant leaks may overburden this storage tank thereby c...

Page 7: ...ion Systems provides minimum mainte nance requirements Systems should be tested operated cleaned and inspected at least annually and parts replaced as required Periodically open the air condensate drain valve see Figs 10 11 or 12 depending on system size beneath the air tank to drain any condensate accumulation Reliable Technical Bulletin 751 provide information for maintaining the Model DDX Delug...

Page 8: ...l Emergency Station valve D in the OFF position with a nylon tie supplied with the assembly 18 Press the system reset button on the Potter PFC 4410 RC Panel to place the system in the ready condition Note All detection devices must be reset before the panel can be reset Inspection And Testing Refer to Figs 10 11 or 12 depending on system size 1 Water supply Verify that the valve controlling water ...

Page 9: ...ve B If system contains pressur ized air allow air pressure to come back up to specifica tion Open valve A first and then open the main valve controlling the water supply to the deluge valve 9 SOLENOID VALVE INSPECTIONS TESTS AND MAINTENANCE WARNING THE OWNER IS RESPONSIBLE FOR MAIN TAINING THE FIRE PROTECTION SYSTEM IN PROP ER OPERATING CONDITION ANY SYSTEM MAINTE NANCE OR TESTING THAT INVOLVES P...

Page 10: ...POWER TBL SYSTEM TBL SUP TBL GROUND FAULT SUP 1 ABORT SUPERVISORY 2 COMMON ALARM ALARM SILENCE STEADY DISCHARGED FLASHING PRE DISCHARGE RUN PROGRAM SET SELECT FUNCTION SCROLL DOWN BUZZER SILENCE SIGNAL SILENCE SYSTEM RESET SCROLL UP BUZZER SILENCE VIEWING ANGLE RED OUTPUT LED STEADY ABORT LAMP TEST 10 ...

Page 11: ...11 Fig 3 ...

Page 12: ...12 Fig 4 ...

Page 13: ...13 Fig 5 ...

Page 14: ...14 Fig 6 ...

Page 15: ...15 Fig 7 ...

Page 16: ...16 Fig 8 ...

Page 17: ...17 Fig 9 ...

Page 18: ...18 Fig 10 ...

Page 19: ...19 ...

Page 20: ...20 Fig 11 ...

Page 21: ...21 ...

Page 22: ...22 Fig 12 ...

Page 23: ...23 ...

Page 24: ...Release 3 Waterflow 4 Low Air Supervisory 1 ALARM X X 2 ALARM X 3 SUPERVISORY X X 4 RELEASE X X INPUTS 1 conventional zone 1 manual release zone 1 waterflow zone 1 low air zone 1 supervisory zone OUTPUTS 1 general alarm bell 1 waterflow bell 1 supervisory bell 1 solenoid release circuit OPERATION Activation of either the conventional zone or the manual release will operate the solenoid release cir...

Page 25: ...25 Fig 13 ...

Page 26: ... SUPERVISORY X X 4 RELEASE X X INPUTS 2 conventional zones cross zoned 1 waterflow zone 1 low air zone 1 supervisory zone OUTPUTS 1 general alarm bell 1 waterflow bell 1 supervisory bell 1 solenoid release circuit OPERATION Activation of both conventional zones at the same time will operate the solenoid release circuit and thegeneral alarm bell Activation of either conventional zone will operate t...

Page 27: ...27 Fig 14 ...

Page 28: ...28 Fig 15 ...

Page 29: ...29 Fig 16 ...

Page 30: ...nted in U S A 10 16 P N 9999970383 The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association Factory Mutual Research Corporation or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable Products manufactured and distributed by Reliable have been...