Potter Program #6

Double Interlock Programming Instructions (Single 
Hazard; 2 Alarm Zones, 1 Water

fl

 ow Zone, and 2 

Supervisory Zones)

1.  Apply power to panel.
2.  Slide the program switch down.
3.  Press the FUNCTION button until the display reads 

“PASSWORD=000.”

4.  To enter a password, press the SELECT button until the 

proper number is displayed above the “^” symbol; then 
press the SET button to move to the next digit.  After 
entering the third number the display will change.  (All 
panels are shipped with a “000” password.)

5.  Press the FUNCTION button until the display reads 

“PROGRAM ##.” (the second “#” character refers to the 
current program number between “0” and “24”).

6.  Press the SELECT button until the display reads “PRO-

GRAM #6.”

7.  Press the SET button
8.  The panel is completely programmed except for the 

custom banner and zone messages. Slide the program 
switch back up.

POTTER PROGRAM #6

OUTPUTS

ZONES

*Supervisory 2

#1

Conventional

#2

Manual Release

#3

Water

fl

 ow

#4

Low Air

Supervisory

#1 ALARM

X

X

#2 ALARM

X

#3 SUPERVISORY

X

X

#4 RELEASE

X

X

INPUTS: 

1 conventional zone, 1 manual release zone, 1 waterflow zone, 1 low air zone, 1 supervisory zone.

OUTPUTS:  

1 general alarm bell, 1 waterflow bell, 1 supervisory bell, 1 solenoid release circuit.

OPERATION:  Activation of either the conventional zone or the manual release will operate the solenoid release 

circuitand the general alarm bell.Activation of the waterflow zone will operate the waterflow bell.Acti-
vation of either the low air zone or the supervisory zone will operate the supervisory bell.When either 
Zone #1 or  #2 is in alarm, Output #1 (general alarm) and Output #4 (solenoid release) willoperate.
When Zone #3 is in alarm, Output #2 (waterflow bell) will operate.When either Zone #4 or the supervi-
sory zone is activated, Output #3 (supervisory bell) will operate.

* The Butter

fl

 y valve in the PrePaK assembly is connected to Supervisory 2 input of the Potter PFC-4410RC 

Releasing/Control panel

Refer to the “Installation, Operation and Instruction Manual” for the PFC-4410-RC Releas-
ing Control Panel for Additional Information.

Summary of Contents for DDX PrePaK

Page 1: ...visory Pressure Double Interlock Electric Pneumatic Release Contents Page General Description 2 Listings and Approvals 2 Technical Data 4 Installation Requirements 5 System Operation 7 System Reset Procedure 7 Inspection Testing and Maintenance 8 Diagrams Assembly Dimensions 3 Potter PFC 4410 RC Releasing Control Panel 10 Terminal Box Wiring 11 Factory Installed Electrical Devices 12 14 Detector C...

Page 2: ...urged of its su pervisory air sufficiently enough for the Model LP Dry Valve Actuator to operate This purging is usually caused by the operation of an automatic sprinkler In the event that the system piping is ruptured or a sprin kler head is accidentally opened the Model LP Dry Valve Actuator will open and a low system air pressure alarm will sound The Model DDX Deluge Valve however will not be r...

Page 3: ...3 Fig 1 ...

Page 4: ...ote controlled Releasing Control Panels used with these units are Listed Approved and programmed to handle the required sequence of operation necessary to operate the automatic sprinkler system Any unauthorized modification or addition made on site to a factory built Listed Approved unit will void the Listing Approval Such modifications or additions may void the unit s warranty as well Consult Re ...

Page 5: ...ditional low pressure air test In some cases hydrostatic testing in accordance with the NFPA 13 requirements noted above will result in pressures that exceed the working pressure of the valve and trim kit for the two hour test period The valve and applicable trim kit have been tested approved and listed under these conditions and as such hydrostatic testing in accordance with NFPA 13 is ac ceptabl...

Page 6: ...y fill the sprinkler system with air the steel enclosure s door should remain open to provide maximum intake air flow to the air compressor The air compressor is connected to a storage tank This tank functions as a reser voir providing make up air to compensate for small inter mittent leaks in the sprinkler system It should be noted that significant leaks may overburden this storage tank thereby c...

Page 7: ...ion Systems provides minimum mainte nance requirements Systems should be tested operated cleaned and inspected at least annually and parts replaced as required Periodically open the air condensate drain valve see Figs 10 11 or 12 depending on system size beneath the air tank to drain any condensate accumulation Reliable Technical Bulletin 751 provide information for maintaining the Model DDX Delug...

Page 8: ...l Emergency Station valve D in the OFF position with a nylon tie supplied with the assembly 18 Press the system reset button on the Potter PFC 4410 RC Panel to place the system in the ready condition Note All detection devices must be reset before the panel can be reset Inspection And Testing Refer to Figs 10 11 or 12 depending on system size 1 Water supply Verify that the valve controlling water ...

Page 9: ...ve B If system contains pressur ized air allow air pressure to come back up to specifica tion Open valve A first and then open the main valve controlling the water supply to the deluge valve 9 SOLENOID VALVE INSPECTIONS TESTS AND MAINTENANCE WARNING THE OWNER IS RESPONSIBLE FOR MAIN TAINING THE FIRE PROTECTION SYSTEM IN PROP ER OPERATING CONDITION ANY SYSTEM MAINTE NANCE OR TESTING THAT INVOLVES P...

Page 10: ...POWER TBL SYSTEM TBL SUP TBL GROUND FAULT SUP 1 ABORT SUPERVISORY 2 COMMON ALARM ALARM SILENCE STEADY DISCHARGED FLASHING PRE DISCHARGE RUN PROGRAM SET SELECT FUNCTION SCROLL DOWN BUZZER SILENCE SIGNAL SILENCE SYSTEM RESET SCROLL UP BUZZER SILENCE VIEWING ANGLE RED OUTPUT LED STEADY ABORT LAMP TEST 10 ...

Page 11: ...11 Fig 3 ...

Page 12: ...12 Fig 4 ...

Page 13: ...13 Fig 5 ...

Page 14: ...14 Fig 6 ...

Page 15: ...15 Fig 7 ...

Page 16: ...16 Fig 8 ...

Page 17: ...17 Fig 9 ...

Page 18: ...18 Fig 10 ...

Page 19: ...19 ...

Page 20: ...20 Fig 11 ...

Page 21: ...21 ...

Page 22: ...22 Fig 12 ...

Page 23: ...23 ...

Page 24: ...Release 3 Waterflow 4 Low Air Supervisory 1 ALARM X X 2 ALARM X 3 SUPERVISORY X X 4 RELEASE X X INPUTS 1 conventional zone 1 manual release zone 1 waterflow zone 1 low air zone 1 supervisory zone OUTPUTS 1 general alarm bell 1 waterflow bell 1 supervisory bell 1 solenoid release circuit OPERATION Activation of either the conventional zone or the manual release will operate the solenoid release cir...

Page 25: ...25 Fig 13 ...

Page 26: ... SUPERVISORY X X 4 RELEASE X X INPUTS 2 conventional zones cross zoned 1 waterflow zone 1 low air zone 1 supervisory zone OUTPUTS 1 general alarm bell 1 waterflow bell 1 supervisory bell 1 solenoid release circuit OPERATION Activation of both conventional zones at the same time will operate the solenoid release circuit and thegeneral alarm bell Activation of either conventional zone will operate t...

Page 27: ...27 Fig 14 ...

Page 28: ...28 Fig 15 ...

Page 29: ...29 Fig 16 ...

Page 30: ...nted in U S A 10 16 P N 9999970383 The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association Factory Mutual Research Corporation or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable Products manufactured and distributed by Reliable have been...

Reviews: