background image

5.

The following is a list of Technical Data Bulletins which de-

scribe the valves and devices which are used in the system:

Device

Reliable Bulletin #

(unless otherwise noted)

Model DDX Deluge Valve 

Reliable Bulletin 519

Type F Double Interlock Preaction Trim

Reliable Bulletin 751

Low Air Pressure Switch

Potter, 5401564

Alarm Pressure switch

Potter, 5400928

Nitrogen Pressure Switch

Potter, 5400930

Mechanical Sprinkler Alarm

Reliable Bulletins 612/613

Solenoid Valve

Reliable Bulletin  718

Releasing Control Panel                                

Potter Manual #5403550

Fire Alarm Devices                                          

  Reliable Bulletin 700

Desiccant Dryer

Wilkerson Catalog 9EM-

TK-190-4

The following table provides a quick reference to the vari-

ous programs (found in this bulletin and the Potter Manual

#5403550) that may be utilized with a Type F PrePaK:

Desired

Applications 

(1)

Description

Program

No.

Double Interlock

Single Hazard, 2 Alarm Zones with 

1 Waterflow Zone and 2 Supervisory 

Zones

Potter

Program #6

Double Interlock, 

Cross-Zoned

Single Hazard, Cross-Zoned, 2 

Alarm Zones with 1 waterflow Zone 

and 2 Supervisory Zones

Potter

Program #7

(2)

(1)

  Refer to Potter Manual # 5403550 included with the PrePak, for 

other programming options available.

(2)

  Factory Program setting

Installation Requirements

The automatic sprinklers, releasing devices, fire detection 

devices, manual pull stations, and signaling devices which 
are utilized with the Reliable Model DDX Type F PrePaK must 
be UL and/or ULC Listed or FM Approved, as applicable.

The steel enclosure and all the interconnecting piping must 

be located indoors in a readily visible and accessible loca-
tion and in an area that can be maintained at a minimum tem-
perature of 40°F (4°C). 

Note:

 Heat tracing is not permitted. 

The solenoid valve is operated and supervised by the Potter 
Model PFC-4410-RC Releasing/Control Panel. Details on the 
electrical connections of this system to the Potter Panel can 
be found in the Potter Manual #5403550, Installation, Opera-
tion and Instruction of PFC-4410-RC Releasing Control Panel 
(this manual is included with other pertinent manuals and 
shipped inside the enclosure). This panel is fully zone and 
output programmable and may be adapted to several ap-
plications.

Hydrostatic Testing of DDX Valves and DDX Systems 

As required by NFPA 13, fire sprinkler systems with working 

pressures up to and including 150 psi are to be hydrostati-
cally tested at a water pressure of 200 psi and maintain that 
pressure without loss for two hours. Fire sprinkler systems with 
working pressures above 150 psi are required to be hydrostati-
cally tested at 50 psi above the system working pressure and 
maintain that pressure without loss for two hours. In addition to 
the hydrostatic tests described above, dry pipe and double 
interlock preaction systems require an additional low pressure 
air test. 

In some cases, hydrostatic testing (in accordance with the 

NFPA 13 requirements noted above) will result in pressures 
that exceed the working pressure of the valve and trim kit for 
the two-hour test period. The valve and applicable trim kit have 
been tested, approved and listed under these conditions and 
as such, hydrostatic testing in accordance with NFPA 13 is ac-
ceptable. In addition, the clapper can remain in the closed po-
sition and the trim kit need not be isolated, as each has been 
designed to withstand hydrostatic testing as required by NFPA 
13. 

Hydrostatically testing the valve and trim to pressures higher 

than their rating is limited to the hydrostatic test as referenced 
by NFPA13. It does not address the occurrence(s) of a “wa-
ter hammer” effect, which can indeed damage the valve. A 
“water hammer” in the water supply piping of the valve can 
create pressures in excess of the rated pressure and should 
be avoided by all necessary means. This condition may be 
created from improper fire pump settings, underground con-
struction work, or an improper venting of trapped air in the wa-
ter supply piping. 

System Air / Nitrogen Pressure Requirements 

The Model DDX Type F PrePaK includes gauges to read the 

pneumatic and water pressures of Model LP Dry Valve Actua-
tor. Table A specifies the air or nitrogen pressure level to be 
applied to the Actuator.  The factory installed Pressure Main-
tenance Device in the unit automatically provides adequate 
makeup air or nitrogen flow to maintain supervisory pressure 
with normal leakage for the system piping, while restricting the 
flow of makeup air or nitrogen to allow for system operation.  
Please note that when the optional Model B1 Accelerator is 
to be utilized to expedite water-delivery time, the pneumatic 
pressure must be not less than 15 psi (1.0 bar). 

Table A

Water Pressure

psi (bar)

Supervisory Air or Nitrogen Pressure in 

Sprinkler System, psi (bar)

Maximum

Not Less Than

Not More Than

  20    (1.4)

10   (0.7)

14   (0.9)

 50    (3.4)

12   (0.8)

16   (1.1)

 75    (5.2)

13   (0.9)

17   (1.2)

100    (6.9)

15   (1.0)

19   (1.3)

125    (8.6)

16   (1.1)

20   (1.4)

150    (10.3)

17   (1.2)

21   (1.4)

175    (12.1)

18   (1.2)

22   (1.5)

200    (13.8)

19   (1.3)

23   (1.6)

225    (15.5)

21   (1.5)

25   (1.7)

250    (17.2)

22   (1.5)

26   (1.8)

Note:

 During system set-up, a higher pneumatic pressure 

may be required in order to properly set the Model LP Dry 
Valve Actuator. The dew point of the air supply must be main-
tained below the lowest ambient temperature to which the 
preaction system will be exposed. Otherwise, accumulation 
of water (condensate) on the air side of the Actuator can low-
er the air pressure at which the Actuator opens, and possibly 
prevent proper system operation. Also, introduction of mois-
ture into the system piping exposed to freezing temperatures 
can create ice blockage, which could prevent proper system 
operation. As a minimum, the supply of air should be taken 
from the area of lowest temperature within the protected area. 
The air supply system must be carefully designed to prevent 

Summary of Contents for DDX PrePaK

Page 1: ...visory Pressure Double Interlock Electric Pneumatic Release Contents Page General Description 2 Listings and Approvals 2 Technical Data 4 Installation Requirements 5 System Operation 7 System Reset Procedure 7 Inspection Testing and Maintenance 8 Diagrams Assembly Dimensions 3 Potter PFC 4410 RC Releasing Control Panel 10 Terminal Box Wiring 11 Factory Installed Electrical Devices 12 14 Detector C...

Page 2: ...urged of its su pervisory air sufficiently enough for the Model LP Dry Valve Actuator to operate This purging is usually caused by the operation of an automatic sprinkler In the event that the system piping is ruptured or a sprin kler head is accidentally opened the Model LP Dry Valve Actuator will open and a low system air pressure alarm will sound The Model DDX Deluge Valve however will not be r...

Page 3: ...3 Fig 1 ...

Page 4: ...ote controlled Releasing Control Panels used with these units are Listed Approved and programmed to handle the required sequence of operation necessary to operate the automatic sprinkler system Any unauthorized modification or addition made on site to a factory built Listed Approved unit will void the Listing Approval Such modifications or additions may void the unit s warranty as well Consult Re ...

Page 5: ...ditional low pressure air test In some cases hydrostatic testing in accordance with the NFPA 13 requirements noted above will result in pressures that exceed the working pressure of the valve and trim kit for the two hour test period The valve and applicable trim kit have been tested approved and listed under these conditions and as such hydrostatic testing in accordance with NFPA 13 is ac ceptabl...

Page 6: ...y fill the sprinkler system with air the steel enclosure s door should remain open to provide maximum intake air flow to the air compressor The air compressor is connected to a storage tank This tank functions as a reser voir providing make up air to compensate for small inter mittent leaks in the sprinkler system It should be noted that significant leaks may overburden this storage tank thereby c...

Page 7: ...ion Systems provides minimum mainte nance requirements Systems should be tested operated cleaned and inspected at least annually and parts replaced as required Periodically open the air condensate drain valve see Figs 10 11 or 12 depending on system size beneath the air tank to drain any condensate accumulation Reliable Technical Bulletin 751 provide information for maintaining the Model DDX Delug...

Page 8: ...l Emergency Station valve D in the OFF position with a nylon tie supplied with the assembly 18 Press the system reset button on the Potter PFC 4410 RC Panel to place the system in the ready condition Note All detection devices must be reset before the panel can be reset Inspection And Testing Refer to Figs 10 11 or 12 depending on system size 1 Water supply Verify that the valve controlling water ...

Page 9: ...ve B If system contains pressur ized air allow air pressure to come back up to specifica tion Open valve A first and then open the main valve controlling the water supply to the deluge valve 9 SOLENOID VALVE INSPECTIONS TESTS AND MAINTENANCE WARNING THE OWNER IS RESPONSIBLE FOR MAIN TAINING THE FIRE PROTECTION SYSTEM IN PROP ER OPERATING CONDITION ANY SYSTEM MAINTE NANCE OR TESTING THAT INVOLVES P...

Page 10: ...POWER TBL SYSTEM TBL SUP TBL GROUND FAULT SUP 1 ABORT SUPERVISORY 2 COMMON ALARM ALARM SILENCE STEADY DISCHARGED FLASHING PRE DISCHARGE RUN PROGRAM SET SELECT FUNCTION SCROLL DOWN BUZZER SILENCE SIGNAL SILENCE SYSTEM RESET SCROLL UP BUZZER SILENCE VIEWING ANGLE RED OUTPUT LED STEADY ABORT LAMP TEST 10 ...

Page 11: ...11 Fig 3 ...

Page 12: ...12 Fig 4 ...

Page 13: ...13 Fig 5 ...

Page 14: ...14 Fig 6 ...

Page 15: ...15 Fig 7 ...

Page 16: ...16 Fig 8 ...

Page 17: ...17 Fig 9 ...

Page 18: ...18 Fig 10 ...

Page 19: ...19 ...

Page 20: ...20 Fig 11 ...

Page 21: ...21 ...

Page 22: ...22 Fig 12 ...

Page 23: ...23 ...

Page 24: ...Release 3 Waterflow 4 Low Air Supervisory 1 ALARM X X 2 ALARM X 3 SUPERVISORY X X 4 RELEASE X X INPUTS 1 conventional zone 1 manual release zone 1 waterflow zone 1 low air zone 1 supervisory zone OUTPUTS 1 general alarm bell 1 waterflow bell 1 supervisory bell 1 solenoid release circuit OPERATION Activation of either the conventional zone or the manual release will operate the solenoid release cir...

Page 25: ...25 Fig 13 ...

Page 26: ... SUPERVISORY X X 4 RELEASE X X INPUTS 2 conventional zones cross zoned 1 waterflow zone 1 low air zone 1 supervisory zone OUTPUTS 1 general alarm bell 1 waterflow bell 1 supervisory bell 1 solenoid release circuit OPERATION Activation of both conventional zones at the same time will operate the solenoid release circuit and thegeneral alarm bell Activation of either conventional zone will operate t...

Page 27: ...27 Fig 14 ...

Page 28: ...28 Fig 15 ...

Page 29: ...29 Fig 16 ...

Page 30: ...nted in U S A 10 16 P N 9999970383 The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association Factory Mutual Research Corporation or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable Products manufactured and distributed by Reliable have been...

Reviews: