Revision E and newer versions of the SMART-Space Controller allow a user to Override a
point using the LCD and buttons. 

The Hand/Off/Auto feature is only applicable to physical outputs of the SSC.  Binary and
analog points are both supported.

T

O

 U

SE

 

THE

 H

AND

/O

FF

/A

UTO

 F

EATURE

1          

Press and hold the left and right buttons down for 5 seconds, release for 3
seconds, then press the left button to enter Hand/Off/Auto mode, or 

HOA

mode

. The controller should remain in HOA mode with the backlight on, the

display flashing, and the first output displayed, for 30 seconds following the last
button press, after which the home screen will be displayed.

2      

In HOA mode, press the center button repeatedly to cycle through the
configured output points.

3      

With any output point displayed, pressing the left or right hand buttons cycles
the overridden state of the point through AUTO, OFF, ON, AUTO,OFF…etc.

4      

For binary outputs:

Auto = control by operators and Control-BASIC commands at the default

priority of 10

OFF = overrides Control-BASIC, and commands the output off at a priority

of 8

ON  = overrides Controls-BASIC, and commands the output on at a priority

of 8

Summary of Contents for SMART-Space Controller

Page 1: ...SMART Space Controller better by design User Guide...

Page 2: ......

Page 3: ...SMART Space Controller User Guide better by design 2012 2015 Reliable Controls Corporation All rights reserved...

Page 4: ......

Page 5: ...Click the Save button Italics in lowercase for field values file types directories and file paths e g The value of the Panel Program field is pan The pan files are stored in the pan subdirectory of t...

Page 6: ...r by any means without the express written permission of Reliable Controls Corporation www reliablecontrols com Reliable Controls RC Studio and the Reliable Controls logo are registered trademarks of...

Page 7: ...ME CLOCK 09 INSTALLATION 11 TOOLS 11 INSTALLATION PROCEDURE 12 DISASSEMBLY 13 MOUNTING THE BACKPLATE 15 SETTING INPUT OUTPUT JUMPERS 16 EIA 485 NETWORK WIRING PROCEDURES 18 TERMINATING THE CONTROLLER...

Page 8: ...UNCTION 68 SHARE NET FUNCTION 68 SHARE AND SHARE NET EXAMPLE 70 OPERATOR INTERFACE 71 DEFAULT LCD SCREEN 71 SECONDARY POINT 71 QUICK ADJUST POINT 72 POINT SCROLLING 73 DEFAULT SCREEN ICONS 73 BUTTON P...

Page 9: ...SPECIFICATIONS 94 GENERAL 94 POWER 94 DISPLAY 94 NETWORK 94 COMMISSIONING PROGRAMMING 94 AMBIENT LIMITS 95 PHYSICAL 95 ONBOARD TEMPERATURE SENSOR 95 INPUTS 95 HUMIDITY OPTIONAL 96 OCCUPANCY OPTIONAL...

Page 10: ...OLLER Standalone operation or part of any BACnet MS TP network Programmable BACnet schedule with onboard real time clock and optional capacitor backup Three base models with different input output con...

Page 11: ...or was made available A thicker back plate was added to provide more venting and more room for models with the CO2 option Earlier hardware revisions all used TRIACs for their two position outputs The...

Page 12: ...ACKAGE CONTENTS USER GUIDE GETTING STARTED SMART SPACE CONTROLLER GETTING STARTED PACKAGE CONTENTS SMART SPACE CONTROLLER PACKAGE CONTENTS One SMART Space Controller with 0 9 cm 3 8 deep backplate Two...

Page 13: ...n PHYSICAL LAYOUT FIGURE 2 PHYSICAL LAYOUT Backplate LCD screen Optional occupancy sensor Three button keypad Two 1 6 mm 1 16 Allen screws secure sensor head to backplate Cooling vents Sensor head X P...

Page 14: ...2015 Reliable Controls Corporation PHYSICAL DIMENSIONS USER GUIDE GETTING STARTED SMART SPACE CONTROLLER PHYSICAL DIMENSIONS FIGURE 3 PHYSICAL DIMENSIONS 3 2 cm 1 1 4 7 0 cm 2 3 4 12 0 cm 4 3 4 0 9 c...

Page 15: ...SICAL DIMENSIONS 6 2012 2015 Reliable Controls Corporation FIGURE 4 PHYSICAL DIMENSIONS BACKPLATE 0 43 cm 3 16 4 0 cm 1 9 16 7 1 cm 2 13 16 12 1 cm 4 3 4 0 9 cm 3 8 1 9 cm 3 4 8 3 cm 3 1 4 3 6 cm 1 7...

Page 16: ...rmistor 3 universal inputs jumper selectable as thermistor dry contact 0 10 VDC or 4 20 mA Output 1 is jumper selectable as universal or relay Outputs 2 3 and 4 are fixed relay relay outputs on this m...

Page 17: ...mally open dry contacts that can switch sustained AC or DC loads up to 0 5 Amps Note that for SSCP models the relay outputs can only switch the power supplied to the controller For example if the cont...

Page 18: ...shown in Figure 5 This jumper also labelled Clear memory connects the 72 hour backup capacitor to the SMART Space Controller circuitry By unplugging J10 and with no external power applied volatile me...

Page 19: ...MODELS 10 2012 2015 Reliable Controls Corporation J10 Clear memory FIGURE 5 SSC C J10 LOCATION...

Page 20: ...s are required Flat blade instrument screwdriver with 2 mm 0 08 wide blade for wire terminal screws and 1 16 Allen key for the Allen screws that lock the SMART Space Controller head to the backplate T...

Page 21: ...o the backplate Loosen the Allen screws counter clockwise until the controller head is locked firmly in place 8 Apply 24 VAC power to the controller see procedure later in this section 9 If the contro...

Page 22: ...o main pieces the controller head and the backplate Prior to installation remove the controller head using the steps below TO REMOVE THE CONTROLLER HEAD 1 Use a 1 16 Allen key to tighten clockwise the...

Page 23: ...INSTALLATION PROCEDURE 14 2012 2015 Reliable Controls Corporation 3 Separate the backplate from the controller head FIGURE 8 BACKPLATE SEPARATION...

Page 24: ...electrical box or mud ring Method 2 The backplate is screwed directly to the wall with no electrical box or mud ring Use suitable anchors and screws to attach the backplate to the wall This method is...

Page 25: ...ating any wiring FIGURE 10 INPUT OUTPUT JUMPER LOCATION Each of the three SMART Space Controller base models has a different number of input output jumpers as detailed on the protector director mounte...

Page 26: ...ER GUIDE INSTALLATION SMART SPACE CONTROLLER FIGURE 12 SSC OUTPUT JUMPERS The metal strips in the square output jumper must be vertically aligned Installing the jumper with the metal strips horizontal...

Page 27: ...d 3 It is not necessary to terminate the REF pins as the EIA 485 A and B voltages are referenced to ground via the grounded return wire to the 24 VAC power transformer 4 When two EIA 485 cables are co...

Page 28: ...VAC transformer or 24 VDC power supply The SSCP consumes up to 65 VA with all 4 relay outputs powering external loads Beginning with Revision C SSC hardware shipped after Jan 1 2012 the SSC EIA 485 tr...

Page 29: ...r setting the MAC address on a SMART Space Controller METHOD 1 RC TOOLKIT BACNET MSET TOOL When installing more then one SMART Space Controller on a single network it may be convenient to enter multip...

Page 30: ...aud being displayed alternately for approximately 10 seconds If the network is disconnected or is not functioning correctly the words No Net will be displayed 1 Hold the and buttons down for 5 seconds...

Page 31: ...INSTALLATION PROCEDURE 22 2012 2015 Reliable Controls Corporation FIGURE 17 CONFIGURED SSC WITH NETWORK BAUD IDENTIFIED FIGURE 18 CONFIGURED SSC WITH DISCONNECTED NETWORK...

Page 32: ...al time clock and 72 hour capacitor back up can be installed as a standalone device In this application RC Toolkit and RC Studio can be used in conjunction with an X Port 2 to configure the SSC The X...

Page 33: ...r to be accessed by other BACnet devices including RC Studio a proxy device must be present on the same physical network Possible proxy devices are the MACH ProCom MACH ProSys firmware version 7 20 or...

Page 34: ...5000 and SSC 6000 however the X Port 2 cannot act as proxy because it is not physically connected to the MS TP main network 2 Although the X Port 2 shown connected to the SMART Net port of Device 7004...

Page 35: ...an input e g temperature pressure Off On is configured using RC Studio Each universal input can be connected to a two wire input device temperature sensor pressure transducer dry contact etc Connect t...

Page 36: ...2015 Reliable Controls Corporation BACNET NETWORK APPLICATIONS USER GUIDE INPUT OUTPUT CONFIGURATION SMART SPACE CONTROLLER FIGURE 21 INPUT JUMPER LOCATIONS The maximum voltage measured by an input is...

Page 37: ...H For H models a humidity element is factory installed on the bottom right corner of the SMART Space Controller The humidity element is connected internally to input number five FIGURE 22 HUMIDITY SEN...

Page 38: ...tatus variable is determined by Control BASIC similar to the following code 10 IF BI6 THEN START OCC VARIABLE 20 IF TIME OFF BI6 0 15 00 THEN STOP OCC VARIABLE With the above code installed a single s...

Page 39: ...on is typical Twenty four hours after initial installation and power application the automatic calibration algorithm will run as described below If this does not provide enough immediate accuracy then...

Page 40: ...automatic calibration algorithm For applications such as continuously occupied rooms or in densely populated cities this sensor is not recommended MANUAL Manual calibration is only required for immed...

Page 41: ...rties dialog box exposed enter the following values Option Description Device ID The BACnet Device ID of the SSC to be manually calibrated Object The object type to be calibrated Enter a zero in the l...

Page 42: ...m of the dialog box to read the present value sensed by the SSC CO2 sensor In the example above the value displayed in the central frame is 750 000000 4 Type over the present value displayed with a mo...

Page 43: ...Read Property button at the bottom of the dialog box to check that the new value was written correctly The present value displayed will be slightly different than the calibration value due to constan...

Page 44: ...lways have two terminals per output positive e g Out1 and negative e g OUT1 The negative terminal is connected internally to the COM terminal Figure 28 shows the recommended method for wiring an SSC u...

Page 45: ...ller power Figure 29 shows the typical Relay output wiring for an SSC or SSCE The output terminals are completely isolated between outputs and from the power connections For this reason SSC and SSCE m...

Page 46: ...relay wiring schematic for an SSCP If Output 1 is configured as a relay the OUT1 terminal is connected internally through a relay to the 24 VAC terminal and the OUT1 terminal is an open circuit Termin...

Page 47: ...nd Tool can only discover and display configured SMART Space Controllers if a slave proxy device is connected directly to the same EIA 485 network as the SMART Space Controllers If a slave proxy devic...

Page 48: ...DIRECT CONNECTION WITH RC STUDIO OR RC TOOLKIT When running RC Studio on a PC with an X Port 2 connected directly to an SSC an RCP direct connection will not work Instead select Access BACnet Direct C...

Page 49: ...ning RC Studio or RC Toolkit can communicate to SMART Space Controllers over a BACnet network using any of the standard connection methods detailed in Figure 32 FIGURE 32 BACNET NETWORK CONNECTION PTP...

Page 50: ...d button pad see the Installation section of this manual however the RC Toolkit BACnet MSet Tool is a more efficient method to simultaneously configure multiple SMART Space Controllers The BACnet MSet...

Page 51: ...CATIONS PORT 4 If using TCP IP to connect enter values for the IP Address field and the BACnet Port field of any IP connected device on the BACnet internetwork FIGURE 34 TCP IP CONNECTION 5 Double cli...

Page 52: ...running total of the devices discovered on the network FIGURE 36 DEVICE DISCOVERY DIALOG BOX 8 After the Status field displays Done click the Close button to populate the BACnet MSet Tool application...

Page 53: ...ges cannot be made to other Reliable Controls devices or third party devices that have been discovered and displayed FIGURE 38 RC TOOLKIT BACNET MSET DIALOG BOX 10 Multiple device configuration change...

Page 54: ...cessible B IP B Ethernet and MS TP networks The BACnet devices connected to any one network can be discovered by selecting a network number and then clicking the Discover button located beneath the Ne...

Page 55: ...e If configuring multiple SMART Space Controllers using the Automatic Addressing procedure described later the fields in this frame determine the starting MAC and Device ID values Starting Device ID T...

Page 56: ...d above FIGURE 41 RC TOOLKIT BACNET MSET DIALOG BOX 2 Unconfigured SMART Space Controllers are always displayed with a blue background at the top of the list of devices discovered on the network The o...

Page 57: ...tarting Device ID according to the Reliable Controls standard for device numbering In this example the SSC Setup application determined that the host device number was 124 resulting in the Starting De...

Page 58: ...be unique and are limited to 32 alphanumeric characters or less The BACnet MSet Tool will not allow a blank Device Name field FIGURE 43 RC TOOLKIT BACNET MSET DIALOG BOX 7 When all SMART Space Control...

Page 59: ...d up using RC Studio prior to beginning the OS Send procedure 1 Connect a PC to the BACnet internetwork using one of the physical connection methods described above 2 Launch RC Toolkit 3 If using a di...

Page 60: ...tion on the PC or network where the desired SMART Space Controller firmware is located After selecting the file the BACnet OS Send Tool populates the Networks list with accessible BACnet network numbe...

Page 61: ...ntrollers When using the Send To feature it is important to highlight the correct network number in the Networks frame to ensure the firmware is sent to the desired controller 10 When one or more targ...

Page 62: ...2 and MACH Pro1 controllers firmware version 7 20 or later and the X Port 2 converter firmware version 6 70 or later all of which have the slave proxy service enabled by default To review and modify t...

Page 63: ...e Manage Slave Proxy dialog box along with the current status of proxy management for that network Figure 53 shows the default configuration of a Slave Proxy Device with all fields enabled for all con...

Page 64: ...Cnet System Tree and then right click and select BACnet Advanced Manage Slave Devices from the right click menu Slave devices that have been auto discovered or previously created will appear in the Ma...

Page 65: ...Setup Set Time Date from the RC Studio main menu This operation broadcasts the current time and date of the PC to the network CLEARING THE PAN FILE TO CLEAR THE PAN FILE IN A SMART SPACE CONTROLLER 1...

Page 66: ...SMART Space Controller is described later in this manual Database Object Amount Details Mneumonic System Group 1 each allowing up to 30 object annotations DISP Display Configuration 1 DISP Binary or A...

Page 67: ...ple in a Variables worksheet row three is used to create a variable object with instance number three which could be an analog binary or multistate variable depending on the unit range selected In Fig...

Page 68: ...more than two states The following multistate ranges are supported Off Low High Low High Auto Off On Auto Cool Heat Auto Cool Heat Auto Off Off Low High Auto Off Low Medium High When evaluating a mul...

Page 69: ...objects internal to the SMART Space Controller The object name or mnemonic may also be typed directly into a cell Enable The Trend Log is automatically enabled when a minimum of one point is entered a...

Page 70: ...for the Multipoint Trend Log FIGURE 58 ADVANCED PROPERTIES DIALOG BOX Shaded fields in the Advanced Properties dialog box cannot be adjusted by the operator The onboard buffer for each Multipoint Tre...

Page 71: ...logs of binary points Programmers cannot create additional Single point Trend Logs Whenever a programmer creates a new binary input binary output or binary variable object in a SMART Space Controller...

Page 72: ...re start the Runtime Log use the Clear Data procedure described below Length The number of complete cycles half the number of changes of state that an SSC Runtime Log can store is fixed at 50 When 50...

Page 73: ...the Duration On and Duration Off Selecting the Export button at the bottom of the Runtime Log opens the Export by Time Range dialog box allowing operators to quickly transfer data to an Excel or ASCII...

Page 74: ...SMART Space Controller objects A priority array exists for each output in a SMART Space Controller If two BACnet devices write to the same output in a SMART Space Controller the write command with th...

Page 75: ...cts that have been previously created A program that references an object that does not yet exist will compile without the point being created When programming with mnemonics rather than object names...

Page 76: ...r a SMART Space Controller to receive network objects or Net Ins one of the following three Control BASIC statements or functions must be used 1 standard command statements 2 SHARE function and 3 SHAR...

Page 77: ...the object is shared to the network object is the name or mnemonic of a valid BACnet object located in the device where the SHARE function is utilized arg is an optional Change of Value COV increment...

Page 78: ...ed analog values The COV increment is the minimum change in the value of the object required before the object will be re broadcast to the network If arg is omitted an increment of 1 0 is used The COV...

Page 79: ...ill receive the shared object updates because the SHARE function does not broadcast over B IP or B Ethernet networks 2 The following line of Control BASIC is written in a program in device number 1203...

Page 80: ...oller The default screen displays the point in row number one defined in the Display Configuration dialog box along with the secondary point if enabled and any icons defined to display the current mod...

Page 81: ...bed later in this section pressing either the or buttons will instantly cause the quick adjust point to be displayed and adjusted Holding the adjustment buttons down will cause the adjustment incremen...

Page 82: ...om programming of each SMART Space Controller the standard meaning of the icons is described in Table 10 TABLE 10 ICON DESCRIPTIONS Field Icon Description Off Auto On AUTO ON OFF Typically used to ind...

Page 83: ...net Schedule must be entered into the Display Configuration worksheet see procedure described later in this section TO ADJUST A SCHEDULE USING THE BUTTON PAD 1 Open a schedule 1 1 Use the button to na...

Page 84: ...Press the button to step through all eight operations The button steps backwards through the operations 3 2 To adjust the start time of operation number one press the button The starting hour flashes...

Page 85: ...ally revert to the default screen after 10 seconds 5 3 At any time during the schedule programming process if no buttons are pressed for over 20 seconds the current adjustment will be cancelled and th...

Page 86: ...and Off Auto mode or HOA mode The controller should remain in HOA mode with the backlight on the display flashing and the first output displayed for 30 seconds following the last button press after wh...

Page 87: ...es Control BASIC and commands the output to the lowest value of its defined range eg for a 0 100 range the output would be commanded to 0 ON overrides Controls BASIC and commands the output to the hig...

Page 88: ...T TO ACCESS THE DISPLAY CONFIGURATION WORKSHEET 1 In the RC Studio BACnet System Tree select the appropriate SMART Space Controller and click the node to display the list of objects available 2 Click...

Page 89: ...OMMAND BAR The command bar along the bottom of the Display Configuration worksheet has five buttons as described in Table 11 TABLE 11 DISPLAY CONFIGURATION COMMAND BAR Button Description Mode Used to...

Page 90: ...10 The row number containing the point that will be displayed at the top of the default LCD screen The secondary point option is often used to display a setpoint or outdoor air temperature If the sec...

Page 91: ...oller TABLE 13 COLUMNS OF THE DISPLAY CONFIGURATION WORKSHEET Column Description Display Name Six character display name that will be displayed on the LCD screen along with the current value of the ob...

Page 92: ...e for the display of objects with State selected in the Type column These icon ranges are displayed at the bottom of the default LCD screen and also when the point is displayed individually by scrolli...

Page 93: ...76 DISPLAY CONFIGURATION IN RC STUDIO 3 Enter a name in the Display Name column such as Time 4 In the Point column enter 0 0 5 The Type column must be set to Analog and the Range column must be set t...

Page 94: ...TO EDIT THE TIME VIA THE SSC INTERFACE 1 On the SMART Space Controller press the button until the Time point is displayed FIGURE 77 SSC TIME DISPLAY SCREEN 2 Use the and buttons to decrement or increm...

Page 95: ...s of how to wire each of the three base SMART Space Controller models using typical HVAC applications Actual wiring requirements will vary with each installation The following examples are provided Ex...

Page 96: ...Air HWR HWS OUT2 FC1 HCV IN2 FC1 SAT OUT1 FC1 SF IN1 FC1 SF S EIA 485 Trunk BACnet MS TP Supply Fan Current switch dry contact SSC Terminals PLF 2 power filter 120 24 VAC Class II transformer 120 VAC...

Page 97: ...ground in HP 1 Fan Compressor Rev Valve Alarm Dry Contact Alarm Dry Contact EIA 485 Trunk BACnet MS TP Supply Fan Current Switch Dry Contact Supply Air Temperature Sensor 10k thermistor SSCP Input Ou...

Page 98: ...T SSCE Terminals EIA 485 Trunk BACnet MS TP PLF 2 power filter 120 24 VAC transformer 120 VAC SIG 24 VAC COM 0 10 VDC Modulating Heating Coil Valve 0 10 VDC Modulating Cooling Coil Valve SIG 24 VAC CO...

Page 99: ...a wiring diagram for an SSCE controlling a standard heat cool fan coil unit with fresh air damper FC2 The following worksheets encompass the complete database for that example FIGURE 81 INPUTS WORKSH...

Page 100: ...ls Corporation SAMPLE SSCE DATABASE USER GUIDE SAMPLE WIRING DOCUMENT SMART SPACE CONTROLLER FIGURE 86 BACNET SCHEDULE FIGURE 87 BACNET MULTIPOINT TREND LOGS WORKSHEET FIGURE 88 CONTROL BASIC WORKSHEE...

Page 101: ...SAMPLE SSCE DATABASE 92 2012 2015 Reliable Controls Corporation FIGURE 90 CONTROL BASIC PROGRAM 1 FIGURE 91 CONTROL BASIC PROGRAM 2 FIGURE 92 CONTROL BASIC PROGRAM 3...

Page 102: ...93 2012 2015 Reliable Controls Corporation SAMPLE SSCE DATABASE USER GUIDE SAMPLE WIRING DOCUMENT SMART SPACE CONTROLLER FIGURE 93 CONTROL BASIC PROGRAM 4...

Page 103: ...kup Optional 72 hour capacitor for RAM and real time clock Supply Voltage 24 VAC VDC Class 2 Consumption 10 VA maximum SSC SSCE 65 VA maximum SSCP including Relay outputs Backlight Switchable Viewable...

Page 104: ...ondensing Dimensions 12 0 cm H x 7 0 cm W x 3 2 cm D 4 3 4 H x 2 3 4 W x 11 4 D Weight 0 12 kg 0 254 lb Range 0 C to 40 C 32 F to 104 F Resolution 0 1 C 0 18 F Accuracy 1 C 1 8 F over range Quantity S...

Page 105: ...90 RH Resolution 0 1 resolution Accuracy 1 8 over range Type Passive Infrared Radiation PIR Detection Distance 5m 16 4 ft maximum Detection Angle 100 horizontal 82 vertical Detection Zones 64 Type No...

Page 106: ...urs Quantity SSC 2 universal or Relay SSCP 1 universal or Relay 3 fixed Relay SSCE 2 universal or Relay 2 fixed Relay Type Selection Jumper configurable Relay Rating 0 500 mA current loads at 24 VAC V...

Page 107: ...CERTIFICATIONS 98 2012 2015 Reliable Controls Corporation...

Reviews: