Special functions
menu 6
6.4.12 - Pressure monitor
menu 6.4.12
The relay is switched on when the pressure drops below set minimum or exceeds the set maximum pressure.
Settings range: On, Off / Default setting: Off
6.4.12.1. - Pressure monitor
menu 6.4.12.1
This menu is used to con
fi
gure the system pressure monitoring via direct sensor. As soon as the set limits are
exceeded, the relay is switched on.
6.4.12.2. - RPS1 / RPS2
menu 6.4.12.2
Type of pressure sensor
This menu is used to determine the type of pressure sensor used.
Please note: If e.g. VFS1 is connected, RPS1 option is not shown.
Settings range: Off; 0-0.6 bar; 0-1 bar; 0-1.6 bar; 0-2.5 bar; 0-4 bar; 0-6 bar; 0-10 bar
Default setting: Off
6.4.12.3.
-
Pmin
menu 6.4.12.3
Minimum pressure. If this value is undershot, an error message is displayed and the relay is switched on.
Settings range: Off; 0,0 to 1.6 bar
Default setting: Off
6.4.12.4.
-
Pmax
menu 6.4.12.4
Maximum pressure. If this value is exceeded, an error message is displayed and the relay is switched on.
Settings range: Off; 0,0 až 10 bar
Default setting: Off
6.4.13. - Booster pump
menu 6.4.13
Additional pump that
fi
lls the system at the start of every solar charge.
Settings range: S1-S8, VF S1-2,
Active storage
Default setting: Off
6.4.13.1. – Filling time
menu 6.4.13.1
This setting determines the length of time the pump is switched on at the start of a solar charge.
Settings range: 0-120 s / Default setting: 30 s