36
REGULUS SRS6 EP Controller - www.regulus.eu
Special functions
menu 6
6.4.4 - Cooling
menu 6.4.4
This is used to cool down e.g. storages to a setpoint temperature by radiating heat, time- and temperature
controlled.
Settings range: S1-S8, VFS1-2, active storage / Default setting: none
6.4.4.1 - Co T set
menu 6.4.4.1
Target temperature at thermostat sensor 1. Cooling is on above this temperature till Co T set + hysteresis is
reached.
Settings range: 0-100 °C / Default setting: 50 °C
6.4.4.2. - Co hysteresis
menu 6.4.4.2
If the temperature drops below Co T set + hysteresis, the relay is switched off.
Settings range: 0-100 / Default setting: 40
6.4.4.3 - Cooling (sensor)
menu 6.4.4.3
Reference sensor of the cooling function.
Settings range: (Storage sensor) / Default setting: storage 1
6.4.4.4
Periods
menu 6.4.4.4
Cooling activity times
Set the desired periods of time when the cooling should be active. 3 periods can be set per day, settings can
also be copied to other days. Outside the set times the cooling function is switched off.
Settings range: from 00:00 to 23:59 /Default setting: 06:00 to 22:00