40
REGULUS SRS6 EP Controller - www.regulus.eu
Special functions
menu 6
6.4.8 - Heat transfer
menu 6.4.8
This is used to transfer energy from one storage to another with a pump.
Settings range: S1-S8, VFS1-2, Active storage / Default setting: none
6.4.8.1 -
Δ
T Heat transfer
menu 6.4.8.1
Temperature difference for heat transfer function.
When the temperature difference between HT Source
and HT Drain reaches
Δ
T Heat Transfer On, the relay is switched on. As soon as the difference drops to
Δ
T
Heat Transfer Off, the relay is switched off again.
ON: Settings range: 5-20 K/ Default setting: 8 K
OFF: Settings range: 2 K to
Δ
T Zap / Default setting: 4 K
6.4.8.2.
-
Setpoint
menu 6.4.8.2
Setpoint temperature of the target storage
When this temperature is detected in the target storage, heat transfer is switched off.
Settings range: 0 to 90 °C / Default setting:60 °C
6.4.8.3 - HT Tmin
menu 6.4.8.3
Minimum temperature in source storage tank to enable the heat transfer
Settings range: 0 to 90°C / Default setting:30°C
6.4.8.4 HT Source (sensor)
menu 6.4.8.4
This menu determines the sensor placed in the source storage
Settings range: S1-S8, VFS1-2, Active storage/ Default setting: none
6.4.8.5 – HT Drain (Target sensor)
menu 6.4.8.5
This determines the sensor placed in the storage that is receiving energy from the source storage.
Settings range: S1-S8, VFS1-2, Active storage/ Default setting: none