Regulus RGMAT E W-iPWM Installation And Operation Manual Download Page 6

 

6

5.4. Technical Data

Wilo PARA 25/8 iPWM1

Electric Data

Power supply

230 V, 50 Hz

Power input (min./max.)

2 / 75 W

Current (min./max.)

0.03 / 0.66 A

Max. speed

4800 rpm

Speed control

frequency converter

Energy Efficiency Index

≤ 0,21 by EN 16 297/3

IP rating

IPX4D

Motor protection

integrated

Operating Parameters

Fluid working temperature

0 - 95 °C  

Max. static pressure

10 bar

Max. head

8.4 m

5.5. FAULTS AND THEIR REASONS

 

The LED light signals a defect. The pump will switch off (depending on the defect type) and 

try to restart.

 

LED signals

State description and possible fault reasons

GREEN IS LIT

1 - pump is running in trouble-free operation

RED IS LIT

1 - rotor is blocked
2 - electric motor winding defect

FLASHING RED

1 - power supply lower/higher than 230 V
2 - electric short circuit in pump
3 - pump overheated

FLASHING RED AND GREEN

1 - unforced fluid circulation through the pump

2 - pump speed lower than desired
3 - air in pump

FAULTS

REASONS

TROUBLESHOOTING

The pump is not running despite 

the power supply turned on

Faulty electrical fuse

Check the fuses

The pump is not energized

Remove the power interruption

The pump makes noises

Cavitation due to insufficient 

inlet pressure

Increase the pressure within the 

permitted range
Check the head adjustment, or 

set a lower head

The building is not warming up

Heat output of heating 

surfaces too low

Increase the desired value

Set the control method to Δp-c

If the fault cannot be rectified, contact a qualified technician.

Summary of Contents for RGMAT E W-iPWM

Page 1: ...www regulus eu RGMAT E W iPWM RGMAT E W iPWM EN Installation and Operation Manual RegulusRGMAT E W iPWM LOAD UNIT with PARA 25 8 for heating systems...

Page 2: ...n Features Function maintaining stable inlet temperature into a boiler fireplace through a load valve Application Load Unit for solid fuel boilers and fireplaces it prevents low temperature corrosion...

Page 3: ...der or even disable its operation Always respect valid rules and boiler manufacturer s data during installation Example of possible connection I Example of possible connection II The diagram shows a t...

Page 4: ...2 0 p m H 2 O Q m3 h A AB Kvs 6 2 m3 h B AB Kvs 4 4 m3 h B AB A The TSV3B load valve is fitted with an integrated thermostatic insert that will close the A inlet from a heating system if the return wa...

Page 5: ...calculation function The high efficiency circulation pumps of the PARA iPWM1 series are used exclusively for the circulation of liquids in hot water heating systems Operating the pump in other systems...

Page 6: ...RED IS LIT 1 rotor is blocked 2 electric motor winding defect FLASHING RED 1 power supply lower higher than 230 V 2 electric short circuit in pump 3 pump overheated FLASHING RED AND GREEN 1 unforced...

Page 7: ...7 5 6 Performace curves for Wilo Para 25 8 iPWM1 pump...

Page 8: ...iping or horizontally to the left of a boiler When being installed horizontally to the left of a boiler the Load Unit needs to be turned by 180 and the TSV3B valve turned as shown in the pics below FL...

Reviews: