5. Wilo-Para iPWM1 Pump

5.1. General Info

The Wilo Para 25/8 iPWM1 is a wet running circulation 

pump. The pump speed is controlled by the PWM signal. 

When the PWM signal is disconnected, the pump runs at its 

maximum speed. The operating status and possible faults of 

the pump are indicated by LEDs directly on the pump. The 

pump is able to send the current flowrate electronically to an 

external controller. The controller must be equipped with an 

iPWM read input and a flow calculation function.
The high efficiency circulation pumps of the PARA iPWM1 

series are used exclusively for the circulation of liquids in 

hot water heating systems. Operating the pump in other 

systems or in systems containing too little water, air bubbles 

or not pressurized can lead to its rapid destruction.

5.2. Permitted and Prohibited Pump Positions

 

Permitted Pump Station positions 

 

Prohibited Pump Station positions

5.3. Pump Wiring

The pump must be wired / disconnected by a qualified person in compliance with EN 50110-1! 

Wilo PARA 25/8 iPWM1 pump wiring

L (brown)

N (blue)

PE (yellow-green)

PWM in (brown)

PWM GND (blue)

iPWM out (black)

1.POWER SUPPLY (230 V, 50 Hz 

2.CONTROL (PWM)

Summary of Contents for RGMAT E W-iPWM

Page 1: ...www regulus eu RGMAT E W iPWM RGMAT E W iPWM EN Installation and Operation Manual RegulusRGMAT E W iPWM LOAD UNIT with PARA 25 8 for heating systems...

Page 2: ...n Features Function maintaining stable inlet temperature into a boiler fireplace through a load valve Application Load Unit for solid fuel boilers and fireplaces it prevents low temperature corrosion...

Page 3: ...der or even disable its operation Always respect valid rules and boiler manufacturer s data during installation Example of possible connection I Example of possible connection II The diagram shows a t...

Page 4: ...2 0 p m H 2 O Q m3 h A AB Kvs 6 2 m3 h B AB Kvs 4 4 m3 h B AB A The TSV3B load valve is fitted with an integrated thermostatic insert that will close the A inlet from a heating system if the return wa...

Page 5: ...calculation function The high efficiency circulation pumps of the PARA iPWM1 series are used exclusively for the circulation of liquids in hot water heating systems Operating the pump in other systems...

Page 6: ...RED IS LIT 1 rotor is blocked 2 electric motor winding defect FLASHING RED 1 power supply lower higher than 230 V 2 electric short circuit in pump 3 pump overheated FLASHING RED AND GREEN 1 unforced...

Page 7: ...7 5 6 Performace curves for Wilo Para 25 8 iPWM1 pump...

Page 8: ...iping or horizontally to the left of a boiler When being installed horizontally to the left of a boiler the Load Unit needs to be turned by 180 and the TSV3B valve turned as shown in the pics below FL...