4. Function description of TSV3B valve 

Technical Data

Max. working temperature

95 °C

Max. working pressure

6 bar

Valve opening temperature  

depending on the thermostatic element    

Control range 

t

valve,opening 

 + 5 °C

Valve Kvs (A→AB direction)  

6.2 m³/h.

Valve Kvs (B→AB direction) 

4.4 m³/h

Connections   

3x G 1" F

Nominal inner diameter  

DN 25

Materials

Housing, cone and plug 

brass

Spring  

stainless steel  

Element and plug seals  

EPDM

Cone seal  

NBR

Valve pressure drop graph

The pressure drop value 

moves between the two cur-

ves depending on the mixing 

ratio during mixing.

0,0

0,3

0,6

0,9

1,2

0,0

0,5

1,0

1,5

2,0

Δ

p [

H

2

O]

Q [m

3

/h]

▬▬

AB, Kvs = 6,2 m

3

/h

▬▬

AB, Kvs = 4,4 m

3

/h

B

AB

A

The TSV3B load valve is fitted with an integrated 

thermostatic insert that will close the 

A

 inlet (from a heating 

system), if the return water temperature to the boiler (

AB 

outlet) is lower than the opening one. As soon as the 

opening temperature is reached, the thermostat starts 

opening the 

A

 inlet slowly and mixing the cold return water 

with the hot water from the 

B

 inlet (boiler flow) with the 

aim to reach the opening temperature (

AB

 outlet) in the 

return pipe.

At the same time, the valve closes the 

B

 inlet, limiting so 

the hot water flow coming from the bypass till its complete 

tight closure. Thanks to this, no balancing valve is needed. 

The load valve is made of brass, element and plug seals 

are in EPDM, cone seal is made of NBR.

Summary of Contents for RGMAT E W-iPWM

Page 1: ...www regulus eu RGMAT E W iPWM RGMAT E W iPWM EN Installation and Operation Manual RegulusRGMAT E W iPWM LOAD UNIT with PARA 25 8 for heating systems...

Page 2: ...n Features Function maintaining stable inlet temperature into a boiler fireplace through a load valve Application Load Unit for solid fuel boilers and fireplaces it prevents low temperature corrosion...

Page 3: ...der or even disable its operation Always respect valid rules and boiler manufacturer s data during installation Example of possible connection I Example of possible connection II The diagram shows a t...

Page 4: ...2 0 p m H 2 O Q m3 h A AB Kvs 6 2 m3 h B AB Kvs 4 4 m3 h B AB A The TSV3B load valve is fitted with an integrated thermostatic insert that will close the A inlet from a heating system if the return wa...

Page 5: ...calculation function The high efficiency circulation pumps of the PARA iPWM1 series are used exclusively for the circulation of liquids in hot water heating systems Operating the pump in other systems...

Page 6: ...RED IS LIT 1 rotor is blocked 2 electric motor winding defect FLASHING RED 1 power supply lower higher than 230 V 2 electric short circuit in pump 3 pump overheated FLASHING RED AND GREEN 1 unforced...

Page 7: ...7 5 6 Performace curves for Wilo Para 25 8 iPWM1 pump...

Page 8: ...iping or horizontally to the left of a boiler When being installed horizontally to the left of a boiler the Load Unit needs to be turned by 180 and the TSV3B valve turned as shown in the pics below FL...

Reviews: