Regulus HSK 350 K P-B Installation And Operation Manual Download Page 7

6 - Installation and Commissioning 

Installation must meet valid rules and may be done only by qualified staff.

Defects caused by improper installation, use or handling are not covered by warranty.

After the tank is installed and connected to an existing heating system, it is recommended to clean the entire heating 

system using a suitable cleaning agent, e.g. MR-501/R.

Anti-corrosion protective liquid should be also used, e.g. MR-501/F.

6.1 - Connection to heat sources

Place the tank on the floor and level it. Fit the insulation, see Installing Insulation on the Tank. Connect the heating system 

according to the diagram of recommended connection - see Chap. 5. Install a drain valve at the lowest point of the tank. 

Install an air vent valve at the highest point of the system. Insulate all the connection piping.

6.2 - Connection to water mains

DHW piping shall be done according to valid rules. The connections to the tank including the location of components is 

shown in the recommended connection diagram in chapter 5. Installation of a pressure reducing valve on the tank inlet is 

recommended. For water mains pressure above 6 bar a pressure reducing valve is necessary. To prevent water loss, we 

recommend installing an expansion vessel at the cold water inlet with a minimum volume of 4% of the total volume of water 

in the DHW piping, including heat exchangers, circulation pipes, etc. (usually 8 l). Should the water be too hard, install a 

water softener before the tank. In case the water contains mechanical impurities, install a filter.

6.3 - Commissioning

The tank shall be filled up together with the heating system, respecting valid standards and rules. In order to minimize 

corrosion, special additives for heating systems should be used. The quality of heating water depends on the quality of 

filling water at commissioning, on the top-up water and on the frequency of topping up. This has a strong influence on the 

lifetime of heating systems. Poor quality of heating water may cause problems like corrosion or incrustation, esp. on heat 

transfer surfaces.

Quality of DHW shall meet the conditions shown in the Table of limit values for total dissolved solids in hot water 

on this page.

Fill the heating circuits with the appropriate fluids and air-bleed the entire system. Check all connections for leaks and verify 

the system pressure. Set the heating controller in compliance with the documentation and manufacturer’s recommendations. 

Check regularly the proper function of all control and adjustment elements.

Table of limit values for total dissolved solids in hot water 

Description  

pH

Total dissolved 

solids (TDS)

Ca

Chlorides

Mg

Na

Fe

max. value

6,5 - 9,5

600 mg/l

40 mg/l

100 mg/l

20 mg/l

200 mg/l

0,2 mg/l

7 - Installing Insulation on the Tank 

Product description

Thermal insulation is a part of thermal stores, preventing heat loss. For easier handling, the insulation shall not be fitted 

on the tank until it reaches its definite place of installation. 

Warning

Insulation installation shall be done in two persons. Do not use any tools for installation. Keep away from open fire.

Installing Insulation 

1. Fix the tank following installation instructions.

2. Wrap the insulation around the tank carefully. Check that the insulation adheres to its body perfectly. This can be 

reached by rubbing and patting the insulation by hand from its center evenly in both directions until the insulation 

adheres to the tank’s surface completely and no bubbles are left. 

3. Use the holes for connections as a rest during the insulation installation.

4. At least one person presses the insulation to the tank, pulling both ends together. The other person closes the 

insulation lock from the side.

5. Put on the upper insulation and cover.

6. Push on the covering plastic rosettes depending on the size of connections.

7. Finish the tank installation in compliance with the respective instructions and valid standards and rules.

Warranty on insulation

□ Warranty shall become null and void if:  

○ 

the procedure described in the Installation Manual was not respected

○ 

the product was used for other purposes than intended.

□ Warranty does not cover: 

○ 

usual wear and tear,

○ 

damage caused by fire, water, electricity or a natural disaster,

Summary of Contents for HSK 350 K P-B

Page 1: ...www regulus eu HSK 350 K P B HSK 350 K P B EN Installation and Operation Manual THERMAL STORE with stainless steel DHW heat exchanger HSK 350 K P B ...

Page 2: ... Technical Data and Dimensions of HSK 350 K P B Thermal Store 4 4 Operation 5 5 Connection of HSK 350 K P B to a Heating System 6 6 Installation and Commissioning 7 6 1 Connection to heat sources 7 6 2 Connection to water mains 7 6 3 Commissioning 7 7 Installing Insulation on the Tank 7 8 Maintenance 8 9 Disposal 8 10 Warranty 8 ...

Page 3: ...ion The insulation is made of fleece 100 mm thick with a hard polystyrene surface 1 4 Packaging Thermal stores are delivered standing each screwed to its pallet packed in bubble wrap It is forbidden to transport and or store the thermal stores in a horizontal position 2 General Information This Manual is an integral and important part of the product and must be handed over to the User Read careful...

Page 4: ...anger and a tight separating metal sheet is intended for heat accumulation and DHW heating Thanks to its modified design and the tight separating metal sheet just one zone valve is sufficient for switching between heating the upper and lower tank sections The tank is suitable for installations with heat pumps and RegulusBOX indoor unit The tank insulation is not included in supply and shall be ord...

Page 5: ...door unit Dimensions pos description connection height mm Heat sources B1 Incoming from heat source G 1 F 1390 B2 Return to heat source G 1 F 1630 B3 Incoming from heat source G 1 F 1170 Heating system H1 Flow to heating system G 1 F 1530 H2 Return from heating system G 1 F 1210 DHW heating W1 Cold water G 1 F 1725 W2 Return from heating system G 1 F 1775 Control and safety C1 Temperature sensor G...

Page 6: ...tation for DHW recirculation CSE TVMIX ZV 8 safety kit for HW storage tank 9 DHW expansion vessel 10 RegulusBOX indoor unit SV cold water TV hot water CV hot water recirculation ÚT central heating heating system KK ball valve ZV check valve AOV automatic air vent valve PTR pressure temperature relief valve REDV pressure reducing valve optional VK drain valve SVE expansion vessel service valve PV Ú...

Page 7: ...orrosion or incrustation esp on heat transfer surfaces Quality of DHW shall meet the conditions shown in the Table of limit values for total dissolved solids in hot water on this page Fill the heating circuits with the appropriate fluids and air bleed the entire system Check all connections for leaks and verify the system pressure Set the heating controller in compliance with the documentation and...

Page 8: ...he tank with a soft cloth and a mild detergent Never use abrasive cleaners or solvents Check all connections for leaks 9 Disposal Packaging shall be disposed of in compliance with the valid rules When the product reaches the end of its life it shall not be disposed of as household waste It shall be dropped off at a Local Waste Recycling Center Insulation shall be recycled as plastic and the steel ...

Reviews: