INSTRUCTION

 

i

Read this instruction before installation 

and wiring of the product

RVAN10-24A

Valve actuator for 0(2)...10 V control

RVAN10-24A is a valve actuator designed for control of Regin valves. 
The actuator has automatic self stroke adjustment and can be oper-
ated manually.

Technical data

Supply voltage 

 

24 V AC ±15 %, 50/60 Hz 

  

or 24 V DC ±15 % 

Control signal 

 

0(2)...10 V DC 

Max. power consumption  6.2 W / 17.4 VA 
Stroke 

 

10...30 mm 

Stroke time 

 

1.5 s/mm 

Force 

 

1000 N 

Ambient temperature 

0...50°C 

Storage temperature 

-40...80°C 

Ambient humidity   

10...90 % RH 

Dimensions (WxHxD) 

198 x 266 x 133 mm 

Protection class   

IP54

Installation

If the valve stem adaptor and valve throat adaptor are not already mount-
ed on the valve, mount them. Pull the valve stem out as far as possible. 
Remove the locking bolt (U-bolt) from the actuator yoke. Insert the valve 
stem into the yoke and make sure that the stem adaptor engages the hole 
in the angled iron of the actuator drive spindle.
The groove in the valve throat adaptor must be made to line up with the 
U-bolt mounting holes on the actuator. If the spindle needs moving in or 
out for this to happen, depress the central part of the manual button and 
turn it clockwise for the actuator spindle to extend, and anti-clockwise for 
it to retract (see Manual override). When the valve is in the correct posi-

tion, insert the U-bolt. Tighten the bolt nuts until the valve is firmly gripped. 

Disassembly in reverse order.

Mounting positions

90º

90º

Wiring

24 V AC/DC 

1

2

3

4

5

1

2

3

4

5

6

Ov

er

ride 

in

pu

t

Y    0(2)...10 V DC

Control signal from 

controller 

U    0...10 V DC

Measuring voltage 

for position indication 

Signal neutral

Y

U

B

M

G0

G

Stroke and end position calibration

Stroke and end position calibration is not necessary due to a construction 
utilizing end position stops. When the valve reaches the end position, a 
force is generated.

 Once the force of the actuator reaches a predefined 

level, the limit switch automatically halts the drive motor.

Override

Activation of the override input will force the valve to the maximum 
open position.

Manual override

To manually set the valve position, first depress the central part of the 
knob, until it clicks and remains depressed (1 in the figure). Then the 

valve position can be changed manually by turning the knob (2 in the 

figure). When the knob is turned clockwise, the drive rod is pushed 

outwards and when the knob is turned anti-clockwise, the drive rod is 
pulled inwards. 
To return to normal operation, set the knob so that it is in line with the 
text ”Auto” on the cover. Then depress the outer parts of the knob (3 

in the figure). The central depressed part will pop out, and the actua

-

tor will return to normal operation.
Note: After any manual operation the actuator will always run through 
a zero point calibration.

DIP switches

There are six DIP switches for setting different functions. Follow the 

table below for setting the DIP switches. 
Adjusted settings will be valid only after the next power-on.

1 (On)

0 (Off)

SW1

Spindle down when the 
valve is closed

Spindle up when the valve is 
closed (FS=factory setting)

SW2

LOG

LIN (FS)

SW3

Y = 2...10 V DC

Y = 0...10 V DC (FS)

SW4

Reverse operation

Direct operation (FS)

SW5

Y signal split in accordance 
with the setting of SW6

No split function (FS)

SW6

5(6)...10 V = 0...100 %

0(2)...5(6) V = 0...100 % (FS)

RVAN10-24A

10474E

 

MA

Y 18

EN

1

Summary of Contents for RVAN10-24A

Page 1: ...roller U 0 10 V DC Measuring voltage for position indication Signal neutral Y U B M G0 G Stroke and end position calibration Stroke and end position calibration is not necessary due to a construction...

Page 2: ...blue plastic end position marker on the actuator linkage The markers can easily be moved in order to show when the actuator is closed open for heating cooling For heating valves the red marker should...

Page 3: ...rekt verkan FI SW5 Y signalsplit enligt inst llning av SW6 Ingen splitfunktion FI SW6 5 6 10 V 0 100 0 2 5 6 V 0 100 FI SW1 Ventilens arbetsriktning On Ventilen r st ngd n r spindeln r i sitt nedre l...

Page 4: ...n um die Stange auszufahren und gegen den Uhrzeigersinn um die Stange einzufahren siehe Handbedienung B gelschraube anbringen wenn sich das Ventil in der korrekten Position befindet Muttern anziehen b...

Page 5: ...einem 4 20 mA Stellsignal ange steuert werden In diesem Falle ist ein 500 Widerstand zwischen Stellsignale ingang Kl 3 und Neutralleiter Kl 2 anzubringen und SW3 muss auf On 2 10 V DC stehen Dann wird...

Page 6: ...DC U 0 10 V DC Signal neutre Signal de commande du r gulateur Tension de mesure pour l indicateur de position Entr e for age Y U B M G0 G talonnage de la course et des limites L talonnage de la course...

Page 7: ...ff 0 5 V 0 100 2 6 V quand SW3 On Indications Le moteur est quip de deux LEDs dont la signification est d crite dans le tableau ci dessous Indication Voyant vert fixe L actionneur fonctionne correctem...

Reviews: