background image

INSTRUCTION

 

RCFM-230TD

1

i

Instruction for products with software version 

1.3. Read this instruction before installation and 

wiring of the product.

Consult documentation in all cases where this symbol 

is used, in order to find out the nature of the potential 

hazards and any actions to be taken

RCFM-230TD

Room controller for controlling fan-coil units

RCFM-230TD is a room controller intended for controlling fan-coil 
heaters/coolers and thermal actuators or 3-point actuators. Instal-
lation is directly on the wall or on an electrical connection box. The 
controller does not have a communication connection. The fan can be 
set to one of three speeds.
RCFM-230TD has change-over function and should be used for 
2-pipe systems.

Technical data

Supply voltage 

 

230 V AC ±10 %, 50/60 Hz

Power consumption 

< 3 W

Ambient temperature 

0...50°C

Ambient humidity   

Max 90 % RH

Storage temperature  

-20...+70°C

Built-in temperature sensor  NTC type, range 0...50°C

Inputs   

 

Refer to connection illustrations and    

 

 

 

table below 

Outputs  

 

Relays for fan control, 230 V AC, 3 A 

 

 

 

DO4, DO5 for actuators, Triac, 230 V AC,  

 

 

 

max. 300 mA

Terminal blocks    

Lift type for a maximum cable area 2.1 mm

2

Protection class    

IP20 

Pollution degree   

Overvoltage category 

3

Material casing    

Polycarbonate, PC

Dimensions  

 

102 x 120 x 29 mm

Installation

Place the controller in a location that has a temperature representative for 
the room. A suitable location is approx. 1.6 m above floor level in a place 
with unobstructed air circulation. 
Depress the locking tab in the upper edge of the controller with a 
screwdriver. Carefully turn the screwdriver until the bottom plate and the 
electronics unit are slightly separated (see figure 1). Then use the cutout 
that becomes visible in the edge of the bottom plate to open the upper 
edge completely (see figure 2). Do the same thing in the lower edge of the 
controller. 

Figure 1

Figure 2

Lift the electronics unit up from the bottom plate. The bottom plate with 
terminals has a number of hole combinations. Select suitable holes and 
fasten the bottom plate on the wall or connection box, so that the arrows 
on the bottom plate point upwards. Do not tighten the screws too hard!

 Disconnection

RCFM-230TD should be connected to a switch or circuit breaker in the 
building installation. This switch should be in close proximity to the con-
troller and within easy reach of the operator, and should be marked as the 
disconnecting device for the equipment.
Always use the circuit breaker to disconnect the controller from the mains 
supply during maintenance of the fan-coil and actuators.

Settings

Control modes

RCFM-230TD has, via a button on the controller, seasonal switching 
between heating and cooling (change-over, see below).

Change-over function

RCFM-230TD has a function for change-over via the M button on the 
controller. By pressing the M button, you choose whether output DO4 
should operate with heating or cooling function. When the controller is 
used together with a 3-position actuator, output DO5 is also affected 
by the change-over function in accordance with the above.

Operating mode

There are four different operating modes. Switching between these 
modes is performed locally.

Comfort: 

   is shown in the display. Heating and cooling have a 

smaller neutral zone. Switching between Comfort/Economy and Off is 
done via the fan button. Comfort/Economy is selected via the param-
eter list and can be controlled by input DI.

Economy (Standby):

 “Standby” is shown in the display. The heat-

ing and cooling setpoints are freely adjustable. Factory settings: 
heating=15°C, cooling=30°C.

Off:

 The controller does not heat or cool and the fan stops (unless 

mould protection has been selected, in which case the fan will still 
run).

Window: 

    is shown in the display, the controller is off and the fan 

stops (unless mould protection has been selected, in which case the 
fan will still run). The window contact is connected to the DI and must 
be configured.

Occupancy detection

Parameter 3 determines if the DI is window contact input or 
occupancy detection input. An occupancy detector can be connected 
to the DI in order to switch between Comfort and Economy mode.

Setpoint

The setpoint is set using the INCREASE and DECREASE buttons. 
Parameter 24 determines what is shown in the display. Refer to the 
parameter list for details. 

Setpoint limitation

In parameters 34 and 35, it is possible to set the maximum allowed 
setpoint increase and decrease respectively. 
Example: If P35=5 and P34=3, the setpoint can be changed between 
17°C and 25°C (see the picture below).
The basic setpoint can be changed in parameter 64 (factory 
setting=22°C).

7435N

 

OCT

 14

EN

Summary of Contents for RCFM-230TD

Page 1: ...to a switch or circuit breaker in the building installation This switch should be in close proximity to the con troller and within easy reach of the operator and should be marked as the disconnecting...

Page 2: ...REASE buttons depressed simultaneously for about 5 seconds until the Service symbol is displayed and then press the INCREASE button twice First the display will show parameter 1 Use the INCREASE and D...

Page 3: ...22 C 13 K 35 Highest permitted setpoint offset downwards Set table value 0 17 K Starting point 22 C 17 K 36 NO NC digital input 1 0 NO 1 NC 0 37 NO NC universal input 1 0 NO 1 NC 0 38 NO NC digital ou...

Page 4: ...har change over funktion och ska anv ndas f r 2 r rs system Tekniska data Matningssp nning 230 V AC 10 50 60 Hz Egenf rbrukning 3 W Omgivningstemperatur 0 50 C Omgivande fuktighet Max 90 RH Lagringst...

Page 5: ...et Auto Fr n Fl ktens aktuella hastighet i Autol get beror p v rme eller kylbehovet och inst llningar f r varje hastighet Vid automatisk styrning visas AUTO i displayen Antalet fl ktsteg v ljs via par...

Page 6: ...anv ndning av en elv rmare ska denna parameter endast s ttas till 1 eller 3 annars finns det risk att v rmaren verhettas 3 26 Startsignal i av regulatorns utstyrning v rme eller kyla f r fl kthastighe...

Page 7: ...00 mA Max 2 A under 20 ms 32 CDO45 Gemensam DO4 5 Gemensam anslutning f r digital utg ng 4 och 5 33 DO5 Digital utg ng 5 f r st nga med 3 punktsst lldon Digital utg ng 230 V AC max 300 mA Max 2 A unde...

Page 8: ...in Bei Wartungsarbeiten an Fan Coil und Stellantrieben ist der Regler grund s tzlich mit Hilfe des Schutzschalters von der Versorgungsspannung zu trennen Einstellungen Regelmodi Jahreszeitliches Umsch...

Page 9: ...ara meter erscheint wird die Ventilatortaste zum Ausw hlen gedr ckt Anstatt der Parameternummer erscheint die gegenw rtige Ein stellung Wert Der Wert kann mit den ERH HEN und SENKEN Tasten ge ndert we...

Page 10: ...Ausgangssignal Heizen in Handbetrieb 0 43 Ausgangssignal K hlen in Handbetrieb 0 44 Modell 45 Hauptversion 46 Zwischenversion 47 Release oder Beta Version 48 Revision 49 Hintergrundbeleuchtung schwach...

Page 11: ...linie 2011 65 EU des europ ischen Parlamentes und des Rates Kontakt RICCIUS SOHN GmbH Vertriebsb ro Deutschland Haynauer Str 49 12249 Berlin Tel 49 30 77 99 40 Fax 49 30 77 99 413 info riccius sohn eu...

Page 12: ...sence peut tre branch sur l entr e digitale DI pour permettre de passer du mode Confort au mode co Valeurs de consigne La consigne est r gl e l aide des boutons AUGMENTER DIMINUER Le param tre 24 per...

Page 13: ...tionnelle du r gulateur 10 K 9 Temps d int gration du r gulateur 300 s 10 Sans objet pour ce mod le 11 D lai de mise l arr t du mode Confort 0 min 12 D lai de mise en route du mode Confort 0 min 13 Ty...

Page 14: ...fficheur luminosit lev e 30 51 63 Sans objet pour ce mod le 64 Valeur de consigne de r f rence R glable 5 50 C 22 C N Description RU 65 R glages boutons actifs 0 Aucun bouton actif 1 Seul le bouton ve...

Page 15: ...r commander la fermeture avec un actionneur 3 points Sortie digitale 230 V AC max 300 mA Max 2 A pendant 20 ms 40 DI Entr e digitale Contact libre de potentiel pour un contact de fen tre ou un d tecte...

Reviews: