Information for the specialist - Configuration
Summer mode
N
Noottee!! The menu
Exch. / Mix. Damper
refers to the
sequence
Exch. / Mix. Damper. The menu
Exchanger
refers to a physical exchanger.
Sequences A to D
Read more about sequences in
.
The sequences available in the controller are Heater, Exchanger/Mixed damper, Cooler or Additional heater.
The sequence/sequences used depends on the predefined configuration chosen for the controller.
Table 4-23 Settings for sequence A to D
Variable
Read/Write
Default
value
Min/Max
Note
Pump stop delay (min)
W
5
0/600
Pump-kick hour (h)
W
15
0/23
Pump running when outdoor
temperature < (°C)
W
10
-40/100
Hysteresis to allow pump stop (°C)
W
1
0/100
Freeze protection
Read more about freeze protection in
.
Table 4-24 Settings for freeze protection
Variable
Read/Write
Default
value
Min/Max
Note
Setpoint (°C)
W
7
-40/150
P-band (°C)
W
5
0/100
Setpoint standby mode (°C)
W
25
-40/150
Exchanger
Read more about exchangers in
.
Table 4-25 Settings for exchanger
Variable
Read/Write
Default
value
Min/Max
Note
Start delay exchanger (s)
W
0
0/3600
Start delay exchanger 100 % (s)
W
2
0/3600
Start alarm delay exchanger (s)
W
60
0/3600
Defrosting setpoint (°C)
W
Defrosting min time (min)
W
5
0/60
Defrosting hysteresis (°C)
W
0,2
0/10
Defrosting stop SAF if temp outdoor
< (°C)
W
-100
-100/150