Information for the specialist - Configuration
Show headline, date/time, vent. mode, supply temp / setp.
Optigo Ardo 1.0
2019-08-01 11:28
System: Normal speed
Sp: 32.8°C Act:33.1°C
Second line: Date and time
Third line: Status of the unit
Fourth line: Supply temperature and setpoint
Show headline, vent. mode, supply temp / setp, sequence A to C
Optigo Ardo 1.0
System: Normal speed
Sp: 32.8°C Act:33.1°C
A 100 B 100 C 100
Second line: Status of the unit
Third line: Supply temperature and setpoint
Fourth line: Output signal of the sequences A to C
Show headline, date/time, vent. mode
Optigo Ardo 1.0
2019-08-01 11:28
System: Normal speed
Second line: Date and time
Third line: Status of the unit
Show headline, date/time
Optigo Ardo 1.0
2019-08-01 11:28
Second line: Date and time
Automatic switch between summer and winter time adjustment
The internal clock is normally configured for automatic summer / winter time adjustment. When enabled,
the clock will be set forward one hour at 02:00 am on the last Sunday of March and adjusted back one hour
at 03:00 am on the last Sunday of October.
The function can be disabled in:
Configuration
►
System
►
General
Automatic logoff
If the access level is set to
Operator
or
Admin
, the user will automatically be logged off after a set time of
inactivity. The time is settable in units of 5 seconds. The default is 60 units = 5 minutes
The automatic log off can be disabled in:
Configuration
►
System
►
General
►
Time before automatic logoff in
display (unit 5s) (min)