
Manual Corrigo E Ventilation, revision M
Chapter 16
Configuration
93
Outdoor temp for
control mode change
13.0°C
16.27.8 Split of optional temp. sequence
Any one of the analogue temperature control output sequences Y1, Y2 and Y3 can be split, for
example to control two heating valves in sequence. The split is always even 50/50 which means that
each part of the split will have half the part of the P-band assigned to the output. An analogue output
must be assigned to the output signal “Split”. On increasing output demand, the regular output is
always run first and then the output that has been configured as Split.
Split optional
temperature sequence
Y1 Y2 Y3
No split
16.27.9 Fast stop on overheating
If this function is active, the fans will be immediately stopped when there is an overheating alarm,
regardless of the set cool-down time.
Fast stop on alarm
“Electric heating is
overheated”: No
16.28 System
16.28.1 Change language
Use this menu to change the display language.
Choose language
English
Note, this menu is also directly accessible by holding the OK-button depressed during power-up or
by pressing right arrow three times when the start display is shown.
The different language files are stored in the application memory and are downloaded to the work
memory. If a Corrigo via E tool has been reloaded with a newer program revision than the factory
revision, the controller will not allow language files to be downloaded from the application
memory. This is because there is a risk that the language files are not compatible with the new
revision. Therefore, you are limited to the two languages you have downloaded using E tool.
16.28.2 Choose start display, the text normally shown on the
display
There are 5 different to choose from.
Type 1
The text on the first line can be changed using Corrigo E tool.
The second line shows date and time.
The third line shows the present running status.
The fourth line shows the present temperature setpoint and actual values.