Manual Corrigo E Ventilation, revision M
Chapter 16
Configuration
90
Expansion unit
In order to connect more I/Os to the Corrigo, port two is set as expansion unit (only Corrigo E
controllers can be connected). It is possible to connect two units which gives a maximum of 28*3 =
84 inputs/outputs. The expansion controllers must have the addresses 241:1 and 241:2 respectively
(ELA:PLA).
Expansion unit 1
None
Expansion unit 2
None
To initiate the expanded controllers, select ”Expansion unit” at start-up (see below). If the controller
is not loaded with program version 3.0 or later, the initiation must be made via E tool (see the E tool
manual). However, this requires that the controller hardware is of Corrigo generation 2 (-S). After
initiating the expansion units and configuring the master controller, all inputs and outputs are
available for configuration in the master controller under Configuration / Inputs/Outputs (the
expansion controllers’ inputs/outputs are called Exp1/Exp2).
Ventilation
Heating
Boiler
Expansion Unit 1
Expansion Unit 2
16.26.3 Dial-up modem
With the help of a dial-up modem, Corrigo E can be connected to a supervisor EXO-system. We
recommend the modem Modem56kINT485kit. The default password is exo.
DialUpModem: No
Number:
Password:
exo
16.26.4 Alarm forwarding via SMS
Via a connected GSM modem, Corrigo can send an alarm message to up to 3 different recipients.
You do not need an activation code to use this function. When there is an alarm, Corrigo sends an
alarm message to the first number on the list. The message consists of an alarm text, the unit name
(the same text that is shown in the first row of the start display) and the time when the alarm
occurred. If the recipient does not send an SMS within 5 minutes to confirm that the message has
been received, Corrigo will send the message to the next number on the list.
SMS: Not Active
Nbr1:
Nbr2:
Nbr3:
16.27 Other parameters
A collection of different parameters that did not fit into any of the other menus.
16.27.1 Start and stop delays for the fans
Use start delay if you wish one of the fans to start before the other and for example if you wish to
give the close-off dampers time to open before starting the fans. Use stop delay for example to
create a cool-down period when using electric heating.
Delay SAF
Start: 60 sec
Stop: 30 sec