Manual Corrigo E Ventilation, revision M
Chapter 15
Settings
70
Flow control EAF
Flow control EAF
P-band: 1000 m3/h
I-time: 60 sec
Min Output: 0 %
15.4 Humidity control
Control humidity
P-band: 100.0 %RH
I-time: 300.0 sec
15.5 Control Extra unit
Control extra
unit
P-band: 33.0 °C
I-time: 100.0 sec
15.6 Alarm settings
Alarm settings
Alarm limits
Alarm delays
Restore alarm
15.6.1 Alarm limits
Alarm limits, supply air
Al. lim. supply air
Control dev: 10.0 °C
High temp: 30.0 °C
Low temp: 10.0
Alarm limits, extract air
Al. lim. extract air
High temp: 30.0 °C
Low temp: 10.0 °C
Alarm limits, room
Al. lim. room air
High temp: 30.0 °C
Low temp: 10.0 °C
Alarm limit, frost protection
Alarm limit frost
protection
7.0 °C