Regency U1500E-LP11 Manual Download Page 3

 

U1500E-11 Gas Fireplace  |    3

U1500E-11 Gas Fireplace

Caution Requirements

The top, back and sides of the fireplace are defined by 

standoffs. The metal ends of the standoff may 

NOT be 

recessed into combustible construction.

WARNING

Fire hazard is an extreme risk 

if these clearances (air space) to combustible materials are not 

adhered to. It is of greatest importance that this fireplace and vent 

system be installed only in accordance with these instructions.

Clearances

The clearances listed below are minimum distances unless otherwise stated.

A major cause of chimney related fires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest impor-
tance that this fireplace and vent system be installed only in accordance with these instructions.

Installed close
to ceiling.

Flue Pipe Clearances to Combustibles

Horizontal - Top

3"

Horizontal - Side 

2"

Horizontal - Bottom

2"

Vertical

2"

Passing  through  wall/
floor/ceiling  -  when 
firestop is used.

1-1/2"

Alcove

E

F

F

E

D

A

B

Installed Close

to Floor

G

The 

HeatWave

 Duct Kit has 

different clearance and fram-
ing requirements, check the 

HeatWave

 manual for details.

Clearance:

Dimension

Measured From:

A: Mantel Height (min.)

25" (635mm)

Top of Fireplace Opening

B: Sidewall (on one side)

6" (152mm)

Side of Fireplace Opening

C: Ceiling
     (room and/or alcove)

46-1/4" (1175mm)

Top of Fireplace Opening

D: Mantel Depth (max.)

12" (305mm)

34" (864mm) Above Fireplace 
Opening

E: Alcove Width

60" (1524mm)

Sidewall to Sidewall (Minimum)

F: Alcove Depth

36" (914mm)

Front to Back Wall (Maximum)

G: From Floor

24-1/4" (616mm)

Top of Fireplace Opening

Note:

0"

No hearth required

Summary of Contents for U1500E-LP11

Page 1: ...er 5 Inner 8 Outer CSA P 4 1 67 46 69 64 Approved Venting Systems Flex Vent Systems FPI AstroCap Flex Vent Rigid Pipe Vent Systems Simpson Direct Vent Pro Selkirk Direct Temp American Metal Products Metal Fab Sure Seal Security Secure vent ICC Excel 45 1 4 49 11 16 13 1 2 29 1 16 24 1 4 6 3 16 32 5 8 12 1 4 23 15 16 22 1 16 54 5 16 1381mm 49 11 16 1263mm 312mm 512mm 609mm 1263mm 1150mm 674mm 737mm...

Page 2: ... 16 43mm J Gas Connection Height 2 11 16 67mm K Gas Connection Inset 1 1 8 29mm L Gas Connection Opening Width 4 11 16 119mm Framing depth measurement is noted with the nailing strips set as far forward on the firebox as possible The nailing strips can be adjusted back up to 1 1 2 38mm to allow for varying thicknesses in non combustible material wall finishes See non combustible section in the ins...

Page 3: ...t this fireplace and vent system be installed only in accordance with these instructions Installed close to ceiling Flue Pipe Clearances to Combustibles Horizontal Top 3 Horizontal Side 2 Horizontal Bottom 2 Vertical 2 Passing through wall floor ceiling when firestop is used 1 1 2 Alcove E F F E D A B Installed Close to Floor G The HeatWave Duct Kit has different clearance and fram ing requirement...

Page 4: ...nd the facing is high quality or the paint may discolour Mantel Leg Clearances Combustible mantel leg clearances as per diagram Wood Studs 0 Non combustible Facing 34 864mm 24 1 4 616mm 10 254mm 30 762mm Top of Fireplace Opening 20 508mm 6 152mm 12 305mm 29 1 2 749mm Steel Stud On Edge 1 25mm 23 7 8 606mm 6 152mm 12 305mm Drywall From base of unit 25 635mm 4 Allowable mantel leg projection 7 1 8 1...

Page 5: ... cracked seams 4 Tape the seams using a mesh type tape 5 Mud seams as normal We recommend using a product called Durabond high strength compound for the first coat This product can be found most hardware stores Mud must be cured as per manufacturer s recommendations 6 Prime wall for a second time for proper adhesion of paint 7 Paint walls using a high quality paint which will withstand the high te...

Page 6: ...ustible materials See Clearances section Combustible materials can be laid against the side and back standoffs and the stove base 4 Non combustible material ie tile slate etc may be brought up to and overlap the unit top and bottom ensuring that the maximum thickness does not go beyond the 1 1 2 as shown in the diagram below The faceplate will not be able to be mounted if finished material is beyo...

Page 7: ...o exception to this rule Therefore the units are specified with non combustible required materials to specific dimensions above and around the units This is due to these areas reaching higher temperature levels than required acceptable for a combustible material To obtain the best most durable finish around your fireplace this calls for a high level of care and attention to the preparation and fin...

Page 8: ... 2 screws on each nailing strip adjust and retighten screws 4 Attach both vertical studs 676 036 A to the vertical timber studs and secure using 6 screws 2 at bottom 2 at top and 2 on sides as shown NOTE Ensure the flat side of the steel stud is facing the wood framing 676 036 A Flat side out 5 Secure horizontal steel header stud 606 067 with 2 screws per side as per diagram 6 Slide the unit into ...

Page 9: ...ing one 90o two 45o elbows equal one 90o elbow Note Must use optional rigid pipe adapter Part 770 994 when using Rigid Pipe Venting Systems Maintain clearances to combustibles as listed in Clearances section Horizontal vent must be supported every 3 feet Firestops are required at each floor level and whenever passing through a wall A vent guard should be used whenever the termination is lower than...

Page 10: ...o elbows equal to one 90o elbow Vent must be supported at offsets Minimum distance between elbows is 1 ft 305mm Maintain clearances to combustibles as listed in the Clearances section Horizontal vent must be supported every 3 feet Firestops are required at each floor level and whenever passing through a wall Must use optional rigid pipe adaptor Part 510 994 when using rigid pipe vent systems Refer...

Page 11: ... with Two 2 90o Elbows One 90o elbow Two 45o elbows Option V H H1 With these options maxi mumtotalpipelengthis30 feetwith minimum of 6feet totalverticalandmaximum 8 feet total horizontal Please note minimum 1 foot between 90o elbows is required A 1 Min 3 Max B 2 Min 4 Max C 3 Min 5 Max D 4 Min 6 Max E 5 Min 7 Max F 6 Min 8 Max Restrictor Set 0 5 Factory Setting Option V H V V1 H H1 With these opti...

Reviews: