10
Regency Plateau™ Series Outdoor Gas Fireplace
INSTALLATION
Caution Requirements
The top, back and sides of the decorative gas appliance
are defi ned by standoffs. The metal ends of the
standoff may
NOT
be recessed into combustible
construction.
WARNING
Fire hazard is an extreme risk
if these clearances (air space) to combustible materials are not
adhered to. It is of greatest importance that this decorative gas
appliance be installed only in accordance with these instructions.
MINIMUM CLEARANCES TO COMBUSTIBLES
The clearances listed below are Minimum distances unless otherwise stated:
A major cause of fi res is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance that this
decorative gas appliance be installed only in accordance with these instructions.
Plateau
®
Series Clearance Requirements
Clearance:
Dimension
Measured From:
A: Back wall
17" (432mm)
Burner to back wall
B: Sidewall
17" (432mm)
Burner to sidewall
C: Ceiling
45" (1143mm)
Burner to Ceiling
D
1
: Floor
D
2
: Floor
0" When using supplied leveling legs or optional casters.
1"(25mm)
Unit Base to Floor
E: Alcove Width
84"(2134mm)
Wall to Wall (Minimum)
F: Alcove Depth
60" (1524mm)
Front to Back Wall (Maximum)
Notes:
0"
No Hearth Required
E
F
Alcove
A
C
D
B