Regency Horizon HZ54E Gas Fireplace
INSTALLATION
AERATION ADJUSTMENT
The burner aeration is factory set but may need
adjusting due to either the local gas supply or
altitude. Open the air shutter for a blue fl ame or
close for a more yellow fl ame.
For instructions to remove the burner for access to
the ventury cap, see pages 46-47 in this manual.
Minimum Air Shutter Opening:
NG
1/2"
LP 1/2"
LP w/Logs = Full Open
CAUTION: Carbon will be produced if air shutter
is tightly closed.
Note: Any damage due to carboning
resulting from improperly setting
the aeration controls is NOT covered
under warranty.
Venturi Cap
WIRING DIAGRAM
This heater does not require a 120V A.C. supply for operation. In case of a power failure, the burner switch and the optional remote control/thermostat will
continue to operate. However, a 120V A.C. power supply is needed for the fan/blower operation.
(Do not cut the ground terminal off under any circumstances.)
NOTE: Even if the fan is not purchased with the unit, it is still a good idea to bring power to the receptacle box (provided with the unit) in case the
fan is installed at a later date.
0.886.001
Proflame Valve
Standard Main On/Off Switch
or Optional Wall Switch
SureFire™ Switch
Note:
4 AA batteries must be installed to operate
the burner switch.
Do not use a 9 volt battery.
IMPORTANT:
If the optional remote control is used, the AA batteries normally installed into the battery holder must be removed. The AA batteries in the
receiver now operate the unit. Having AA batteries in both the battery holder and receiver will damage the gas valve.