30
Regency Horizon HZ54E Gas Fireplace
INSTALLATION
GAS PIPE PRESSURE
TESTING
The appliance must be isolated from the gas sup-
ply piping system by closing its individual manual
shut-off valve during any pressure testing of the
gas supply piping system at test pressures equal
to or less than 1/2 psig. (3.45 kPa). Disconnect
piping from valve at pressures over 1/2 psig.
The manifold pressure is controlled by a regulator
built into the gas control, and should be checked
at the pressure test point.
Note: To properly check gas pressure, both
inlet and manifold pressures should be
checked using the valve pressure ports
on the valve.
1)
Make sure the valve is in the "OFF" position.
2)
Loosen the "IN" and/or "OUT" pressure tap(s),
turning counterclockwise with a
1/8"
wide
fl at screwdriver.
3)
Attach manometer to "IN" and/or "OUT" pressure
tap(s) using a 5/16" ID hose.
4)
Light the pilot and turn the valve to "ON" position.
5)
The pressure check should be carried out with
the unit burning and the setting should be within
the limits specifi ed on the safety label.
6)
When
fi nished reading manometer, turn off the
gas valve, disconnect the hose and tighten the
screw (clockwise) with a 1/8" fl at screwdriver.
Note: Screw should be snug, but do not over
tighten.
HIGH ELEVATION
This unit is approved for altitude 0 to 4500 ft.
(CAN1 2.17-M91).
GAS LINE
INSTALLATION
Since some municipalities have additional
local codes it is always best to consult with
your local authorities and the CAN/CGA B149
installation code.
For USA installations follow local codes and/
or the current National Fuel Gas Code, ANSI
Z223.1.
When using copper or fl ex connectors use only
approved fi ttings. Always provide a union so
that gas lines can be easily disconnected for
servicing. Flare nuts for copper lines and fl ex
connectors are usually considered to meet this
requirement.
NOTE: A shutoff / dante valve should be
supplied in or near the unit (or as per local
codes) for ease of servicing this appliance.
IMPORTANT: Always check for gas leaks with
a soap and water solution or gas leak detec-
tor. Do not use open fl ame for leak testing.
HZ54E-NG SYSTEM DATA
Min. Supply Pressure
5" WC (1.25 kpa)
Low Setting Man.
Pressure
1.6" WC (0.40kpa)
Max. Manifold
Pressure
3.5" WC (0.87 kpa)
Orifi ce Size
#30 DMS
Minimum Input
29,000 Btu/h
(8.50 kW)
Maximum Input
41,500 Btu/h
(12.16 kW)
HZ54E-LP SYSTEM DATA
Min. Supply Pressure
12" WC (2.98 kpa)
Low Setting Man.
Pressure
6.4" WC (1.59kpa)
Max. Manifold
Pressure
10" WC (2.49 kpa)
Orifi ce Size
#49 DMS
Minimum Input
30,000 Btu/h
(8.79 kW)
Maximum Input
37,000 Btu/h
(10.84 kW)
Note: If you have an incorrect fl ame pattern,
contact your Regency
®
dealer for further
instructions.
Incorrect fl ame pattern will have small, probably
yellow fl ames, not coming into proper contact
with the rear burner or fl ame sensor.
Burner
Flame Sensor
Pilot
Ignitor
PILOT ADJUSTMENT
Periodically check the pilot fl ames. Correct fl ame
pattern has two strong blue fl ames: 1 fl owing
around the fl ame sensor and 1 fl owing across
the burner (it does not have to be touching the
burner).
886 S.I.T. VALVE
DESCRIPTION
1)
Manual high/low adjustment
2)
Pilot
adjustment
3)
Outlet
Pressure
Tap
4)
Inlet
Pressure
Tap
5)
Pilot Outlet
6)
Main Gas Outlet
7)
Main Gas Inlet
1
3
2
4
5
6
7