HZ42 Regency Horizon
TM
Gas Fireplace
9
INST
ALLA
TION
INSTALLATION
Caution Requirements
The top, back and sides of the fi replace are defi ned by
standoffs. The metal ends of the standoff may
NOT
be
recessed into combustible construction.
WARNING
Fire hazard is an extreme risk
if these clearances (air space) to combustible materials are not
adhered to. It is of greatest importance that this fi replace and vent
system be installed only in accordance with these instructions.
CLEARANCES
The clearances listed below are Minimum distances unless otherwise stated:
A major cause of chimney related fi res is failure to maintain required clearances (air space) to combustible materials. It is of the greatest
importance that this fi replace and vent system be installed only in accordance with these instructions.
Clearance:
Dimension
Measured From:
A: Mantel Height (min.)
13" (330mm)
Top of Fireplace Opening
B: Sidewall (on one side)
8" (203mm)
Side of Fireplace Opening
C: Ceiling
(room and/or alcove)
22" (559mm)
Top of Fireplace Opening
D: Mantel Depth (max.)
13" (330mm)
22" Above Fireplace Opening
E: Alcove Width
84" (2134mm)
Sidewall to Sidewall (Minimum)
F: Alcove Depth
36" (914mm)
Front to Back Wall (Maximum)
G: From Floor
25-3/4"
Top of Fireplace Opening
Note:
0"
No hearth required
Flue Clearances to Combustibles
Horizontal - Top
3"
Horiztonal - Side
2"
Horiztonal - Bottom
2"
Vertical
2"
Passing through wall/
f l o o r / c e i l i n g - w h e n
fi restop is used.
1-1/2"
Alcove
E
F
IMPORTANT NOTE
Combustible material can only be installed to
the bottom lip of the fi replace as shown below.
The fi nished fl oor must not come in contact with
the front face of the fi replace. Non-combustible
material (see "Framing and Finishing" section)
must act as a barrier between the front face and
fi nished fl oor.