U900E-11 Gas Fireplace  |    5

Non-Combustible Facing Installation 

Non-combustible board

Non-combustible board-faces and edges
MUST BE PRIMED.

Non-combustible board

shipped with unit

shipped with unit

Caution:

 

The non-combustible board supplied with this unit can    

    

          

be damaged if dropped or struck.  

Handle with care

.

1.   

Using drywall screws

 - 

secure non combustible material 

      around unit, framing and top nailing strip every 6 inches. 

Important Note: 

To avoid cracking the board - pre-drill holes prior to          

     

securing to unit/ framing.

2.

   Wipe any debris/dust from the non combustible 

       material and drywall.

3

.    Prior to securing it is mandatory to prime the facing and edges using a quality 

primer. This will ensure proper adhesion of both the tape and mud.  The 
supplied board is very porous. 

      Failure to follow this procedure will result in cracked seams.

4.

   Tape the seams using a mesh type tape.

5.

   Mud seams as normal. We recommend using a 

      product called Durabond high strength compound - for the first coat.
      This product can be found at any hardware store. 
      Mud must be cured as per manufacturer’s recommendations.

6.

  Prime wall for a second time for proper adhesion of paint

7.

  Paint walls using a high quality paint which will withstand 

      the high temperatures being emitted from this appliance.

Non-Combustible Requirements

* Installation of the ON/OFF Wall Switch/Battery Holder must be completed before installing non-combustible facing.

All three pieces (top, 2 sides) may be ordered separately to meet the non combustible requirements.  

Calcium silicate board is a high - grade material
with cement, quartz, natural and selected
minerals as the main raw materials. It is widely
used for partitions and ceilings in buildings.
It is fire proof and earthquake proof.

If finishing the wall above the unit with materials
such as tile, brick, marble, etc. non-combustible
board available from the building supply store
can be used.

Note: 

Calcium Silicate is 1/2' thick 

NOTE:

  A  minimum  thickness 

of 1/2" non combustible facing 
is required. 

U900E-11 Gas Fireplace

Summary of Contents for U900E-11

Page 1: ...High 3 5 W C 0 87 kPa 10 W C 2 48 kPa Manifold Pressure Low 1 6 W C 0 41 kPa 6 4 W C 1 59 kPa Orifice Size Altitude 0 4500 ft 35 DMS 52 DMS Minimum Input Altitude 0 4500 ft 0 1372m 23 500 BTU h 6 89 k...

Page 2: ...ght 20 508mm I Gas Connection Opening Height 1 11 16 43mm J Gas Connection Height 2 11 16 67mm K Gas Connection Inset 1 1 8 29mm L Gas Connection Opening Width 4 11 16 119mm Framing depth measurement...

Page 3: ...nce that this fireplace and vent system be installed only in accordance with these instructions Clearance Dimension Measured From A Mantel Height min 20 508mm Top of Fireplace Opening B Sidewall on on...

Page 4: ...is used on the mantel and the facing is high quality or the paint may discolour Mantel Leg Clearances Combustible mantel leg clearances as per diagram Note A non combustible mantel may be installed at...

Page 5: ...using a product called Durabond high strength compound for the first coat This product can be found at any hardware store Mud must be cured as per manufacturer s recommendations 6 Prime wall for a se...

Page 6: ...on Combustible materials can be laid against the side and back standoffs and the stove base 4 Non combustible material ie tile slate etc may be brought up to and overlap the unit top and bottom ensuri...

Page 7: ...ical as the installation itself The temperatures around linear gas fireplaces are typically higher than would be acceptable for combustible materials Your Regency Horizon Fireplace is no exception to...

Page 8: ...p adjust and retighten screws 4 Attach both vertical studs 466 126 to the vertical wood studs and secure using 6 screws 2 at bottom 2 at top and 2 on sides as shown NOTE Ensure the flat side of the st...

Page 9: ...minations The diagram shows all allowable combinations of vertical runs with horizontal terminations using one 90o two 45o elbows equal one 90o elbow Note Must use optional rigid pipe adapter Part 510...

Page 10: ...elbows equal to one 90o elbow Vent must be supported at offsets Minimum distance between elbows is 1 ft 305mm Maintain clearances to combustibles as listed in the Clearances section Horizontal vent m...

Page 11: ...ne 90o elbow Two 45o elbows Option V H H1 With these options maxi mumtotalpipelengthis30 feetwithminimumof6feet totalverticalandmaximum 8 feet total horizontal Please note minimum 1 footbetween90o elb...

Page 12: ...ver keeptheflexible linerasstraightaspossible avoidunnecessarybending The Air Intake pipe must be attached to the inlet air collar of the termination cap Required Parts Part Description 946 529 Co lin...

Page 13: ...diagrams show the allowable vertical terminations Restrictor Position Set 0 3 Factory Setting Venting Arrangements Vertical Termination with Co linear Flex System for both Residential Manufactured Hom...

Reviews: