12
Regency
®
P36D-1 Zero Clearance Direct Vent Gas Fireplace
INSTALLATION
The
HeatWave
Duct Kit and the Heat
Release Kit have different clearance
and framing requirements, check the
HeatWave
and Heat Release manual
for details.
Heat Release Kit
The clearances listed below are Minimum distances unless otherwise stated:
A major cause of chimney related fi res is failure to maintain required clearances (air space) to combustible materials. It is of the greatest
importance that this fi replace and vent system be installed only in accordance with these instructions.
Clearance to Combustibles from:
Back
0"
(0mm)
Side
0"
(0mm)
Floor
0"
(0mm)
NOTE: The minimum fl oor clearance must be maintained from the top surface of the carpeting, tile, etc.
Minimum Clearance from Top of Unit to:
Ceiling
from top of unit.
32"
(1016mm)
Side Wall Clearances:
Flush Front
6"*
(152mm)
Full Screen Doors
6"*
(152mm)
* Measured from Surround or Front. See Regency
®
Clearances section for dimensions.
Horizontal Vent Clearances:
Top
2"
(51mm)
Side
1-1/2"
(38mm)
Bottom
1-1/2"
(38mm)
Vertical Vent Clearances
1-1/4"
(32mm)
Alcove Clearances**:
Max.
Depth
36"
(914mm)
Min.
Width
48"
(1219mm)
Min.
Height
72"
(1829mm)
WARNING: Fire hazard is an extreme risk if these clearances are not adhered to.
CLEARANCES