48

Regency

®

 P36D-1 Zero Clearance Direct Vent Gas Fireplace

INSTALLATION

OPTIONAL FAN 

INSTALLATION

120 Volt AC power is needed for the fan switch 
and blower. The fan can be hard wired if desired. 
The  receptacle box should be installed  on  the left 
hand side of the unit by a qualifi ed electrician. The 
neutral (wider) slot of the polarized receptacle 
should be at the top.

Unit must be grounded at all times. Do 
not cut the ground terminal off under any 
circumstances.

1)

 

Shut the power off.

2)

  Remove the standard fl ush door and the 

optional bay door, if installed. Open the 
bottom louver door. 

3)

  Loosen the 2 screws holding the Burner 

ON/OFF switch and bracket to the bottom 
louver and lift the assembly out.

4)

  Turn the fan base on its side (with the base 

facing towards you) and then slide the fan 
in towards the rear of the unit. Turn the fan 
upright and slip it over the two mounting 
studs. Take care not to damage the insulation 
on the fan base. 

Ensure that the fan blades 

do not rub against the valve tubing. 

Diagram 1.

6)

   Slide the  thermodisc/cover assembly  into 

the bracket clip on the underside of the 
fi rebox. Check that no wire will touch the 
hot surfaces. Diagram 2.

12)

 Secure the fan wires and power cord by 

attaching one of the adhesive backed wire 
holder clips (Part #910-199) onto the stove 
base. Use the second clip to bundle up the 
wires approximately 4" from the control box. 
Ensure that there is no interference with the 
wires when the louver is closed and that 
no wire will touch the hot metal surfaces or 
sharp edges.

13)

 Plug the fan power cord into the rear end of 

the receptacle box to provide the maximum 
clearance from the louvers.

OPTIONAL FAN REMOVAL

    

1)

 

Shut the power off.

2)

  Reverse the above instructions.

Note:  The bearings are lubricated for life. Do 
not lubricate them. Make sure you vacuum 
the fan area on a regular basis.

IMPORTANT:

These fans collect a lot of dust from within 
your home. Ensure you maintain these fan 
motors on a regular basis by vacuuming 
out the fan blades and housing using a soft 
brush nozzle.

7)

  Attach the Fan control box to the  Burner 

ON/OFF control box.

Diagram 2

Use the clip & hook on the side of the control 

boxes to join them together.

Secure the 2 boxes together 

with one screw.

Hold control box assembly in place and mark 

the position of the right side slot

8) 

Secure the two boxes together with one 
screw. 

9)

  Position the control box assembly on the 

bottom louver and mark the position of the slot 
on the right side bracket.

Secure left 
side with 2 

screws.

Secure right side with one screw.

11)

 Attach the two control boxes to the bottom 

louver and tighten the 2 screws on the left 
side and 1 screw on the right side.

5)

  Connect fan ground cable to ground lug. 

Refer to wiring diagram.

           Diagram 1

10)

 Remove the control box assembly and push 

the hold-down clip onto the louver. Bend the 
tab until it is at 90

o

 to the louver.

Summary of Contents for P36D-LP1

Page 1: ...tly a fire or explosion may result causing property damage personal injury or loss of life FOR YOUR SAFETY Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or...

Page 2: ...esigned to provide you with all the warmth and charm of a wood fireplace at the flick of a switch The model P36D 1 has been approved by Warnock Hersey for both safety and efficiency As it also bears o...

Page 3: ...must comply with the manufacturer s installation instructions and local codes if any In the absence of local codes follow the current National Fuel Gas Code ANSI Z223 1 and the current National Elect...

Page 4: ...Wiring Diagrams 46 Optional Fan Installation 48 Optional Fan Removal 48 SAFETY LABEL Copy of Safety Decal for P36D 1 6 REQUIREMENTS MA Code CO Detector 7 INSTALLATION Unit Dimensions 8 Before You Sta...

Page 5: ...Copy of the Lighting Plate Instructions 50 MAINTENANCE Maintenance Instructions 50 General Vent Maintenance 51 Log Replacement 51 Thermopile Thermocouple 51 Glass Gasket 51 Door Glass 51 Flush Glass R...

Page 6: ...l Bay Window Part 510 930 Option HeatWave Kit 946 556 Cet appareil doit tre utilize uniquement avec le type de gaz indiqu sur la plaque signal tique Cet appareil peut tre install dans une maison pr fa...

Page 7: ...ade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS V...

Page 8: ...8 Regency P36D 1 Zero Clearance Direct Vent Gas Fireplace INSTALLATION 36 914mm 33 838mm 36 914mm 30 1 2 775mm 37 940mm 17 1 8 435mm 32 1 2 826mm 37 940mm UNIT DIMENSIONS...

Page 9: ...APPLIANCE BE KEPT CLEAN DUE TO HIGH TEMPERATURES THE APPLIANCE SHOULD BE LOCATED OUT OF TRAFFIC AND AWAY FROM FURNITURE AND DRAPERIES WARNING FAILURE TO INSTALL THIS APPLIANCE CORRECTLY WILL VOID YOUR...

Page 10: ...and ceilings when cutting holes for termination 11 Under no circumstances should this appliance be modified Parts that have to be removed for servicing should be replaced prior to operating this appl...

Page 11: ...stallationswhenusedwithaListedMillivolt Thermostat Some areas may have further requirements check local codes before installation 6 The P36D 1 Direct Vent Gas Fireplace is approvedforalcoveinstallatio...

Page 12: ...talled only in accordance with these instructions Clearance to Combustibles from Back 0 0mm Side 0 0mm Floor 0 0mm NOTE The minimum floor clearance must be maintained from the top surface of the carpe...

Page 13: ...Regency P36D 1 Zero Clearance Direct Vent Gas Fireplace 13 INSTALLATION Clearances for Flush Front Full Screen Doors REGENCY CLEARANCES TRIPOLI ARCH DOOR CLEARANCES Note No Hearth Required...

Page 14: ...clearances are critical Combustible mantel clearances from top of unit are shown in Diagram 1 Note A non combustible mantel may be installed at a lower height if the framing is made of metal studs cov...

Page 15: ...from top of unit are shown in the diagram below Note A non combustible mantel may be installed at a lower height if the framing is made of metal studs covered with a non combustible board These drawi...

Page 16: ...16 Regency P36D 1 Zero Clearance Direct Vent Gas Fireplace INSTALLATION REGENCY MANTEL LEG CLEARANCES Combustible mantel leg clearances as per diagram Maximum 1 1 2 projection at 2 minimum clearance...

Page 17: ...to the ceiling 2 Frame in the enclosure for the unit with framing material The framed opening is 37 1 4 high x 36 1 4 wide x 17 3 8 deep 946mmhighx921mmwidex441mmdeep FRAMING AND FINISHING Note 40 1 2...

Page 18: ...lete framing dimensions see instructions in this manual The Tripoli Arch Door also requires steel stud framing above and on each side of the unit see diagram 2 TRIPOLI ARCH DOOR FRAMING NOTE Steel Stu...

Page 19: ...ecombustionchambertherebyeliminatingthe need to use heated room air for combustion and losing warm room air up the chimney Note These flue pipes must not be connected to any other appliance The gas ap...

Page 20: ...ne extended above meter regulator assembly 36 90cm a J Clearance to service regulator vent outlet 36 90cm K Clearance to non mechanical air supply inlet to building or the combustion air inlet to any...

Page 21: ...ap termination cap 1 6 screws 12 7 tube of Mill Pac 1 8 plated screws 8 9 screws 8 x 1 1 2 Drill Point Stainless Steel 4 1 6 7 8 dia flexible liner 10 ft length 2 4 dia flexible liner 10 ft length 3 s...

Page 22: ...N A N A N A Adjustable Length 3 10 Galvanized N A N A N A 4DAL N A TC 4DLT Adjustable Length 3 10 Black N A N A N A 4DALB N A TC 4DLTB Adjustable Length 7 Galvanized N A N A 4D7A N A N A N A Adjustabl...

Page 23: ...izontal Termination Kit A Disc 4DT HKA 4DHTK2 4DHTKA SV SHK N A Horizontal Termination Kit B 46DVA KHA Changed Components 4DT HKB 4DHTK1 4DHTKB SV HK N A Vertical Termination Kit Disc 4DT VKC 4DHTK 4D...

Page 24: ...es The FPI AstroCapTM and FPI Riser Vent terminal are certified for installations using FPI venting systems as well as Simpson Dura Vent Direct Vent American Metal Products Security Secure Vent AmeriV...

Page 25: ...6 7 8 inner diameter Maintain clearances to combustibles Horizontal vent must be supported every 3 feet Firestops are required at each floor level and whenever passing through a wall NOTE If you are i...

Page 26: ...n clearances to combustibles Note Must use optional rigid pipe adaptor when using rigid vent systems Part 510 994 VENTING ARRANGEMENTS VERTICAL TERMINATION RIGID PIPE SYSTEM Propane Natural Gas The sh...

Page 27: ...he diagram 1 The shaded area in the diagram 1 shows all allowable combinations of straight vertical and offset to vertical terminations with rigid pipe vent systems for Propane and Natural Gas Maximum...

Page 28: ...al Please note minimum 1 foot between 90o elbows is required One 90o elbow Two 45o elbows Lengths do not include elbow indicated Option V H V V1 H H1 A 0 Min 1 Max 1 Min 2 Max B 1 Min 2 Max 3 Min 3 Ma...

Page 29: ...ertical and max 8 feet total horizontal Please note min 1 foot between 90o elbows is required One 90o elbow Two 45o elbows Lengths do not include elbow indicated Option V H H1 V V1 A 0 Min 2 Max 2 Min...

Page 30: ...bending The Air Intake pipe must be attached to the inlet air collar of the termination cap Required Parts Part Description 946 529 Co linear DV Vertical Termination Cap 948 305 3 Flex 35 ft 946 563 C...

Page 31: ...NTING ARRANGEMENT VERTICAL TERMINATIONS CO LINEAR FLEX SYSTEM INTO MASONRY FIREPLACES FOR BOTH RESIDENTIAL MANUFACTURED HOMES The shaded area in the diagrams show the allowable vertical terminations 8...

Page 32: ...nt is only for use in above grade terminations NOTE For best results and optimum performance with each approved venting system it is highly recommended to apply Mill Pac sealant supplied to every in n...

Page 33: ...xit and mark the location wheretheventwillpenetratetheceiling Drill a small hole at his point Next drop a plumb bob from the roof to the hole previously drilledintheceiling andmarkthespotwhere the ven...

Page 34: ...ECT VENT SYSTEM FLEX INSTALLATION PROCEDURES 1 Locate the unit in the framing rough in the gas preferably on the right side of the unit and the electrical Junction block is on the left side on the lef...

Page 35: ...ll probably yellow flames not coming into proper contact with the rear burner or thermopile or thermocouple alwaysbesttoconsultwithyourlocalauthorities and the CAN CGA B149 installation code For USA i...

Page 36: ...s holding the Burner Assembly to the firebox base Push the Burner Assembly to the left and lift out DC Sparker Kit Contains Qty Part Description 1 820 475 Bracket DC Sparker 1 820 476 Bracket DC Spark...

Page 37: ...or and connect it to the DC Sparker Piezo Ignitor Ignitor Wire Piezo Ignitor Ignitor Wire DC Sparker 18 Reverse steps 6 1 Fig 1 11 Remove the black protection cap by hand from the hi low knob Fig 1 Fi...

Page 38: ...et and outlet pressures 37 Check operation of flame control 38 Check for proper flame appearance and glow on logs NOTE The battery in the DC Sparker Box will need to be replaced an nually 25 Locate th...

Page 39: ...by carefully slipping it between the back wall of the firebox and the rear log bracket 3 Put the side panels in next Slide them in from the front and push them flat up against the wall Be very careful...

Page 40: ...log kit Part 780 930 contains the following pieces a 02 75 Rear Log b 02 55 Middle Left Log c 02 50 Front Left Log d 02 53 Center Left Log e 02 51 Front Bottom Log f 02 54 Center Right Log g 02 52 Mid...

Page 41: ...rest the log on the cutout on Log 02 53 Cutouts 5th Grate Tab 02 54 0 2 5 3 02 51 6 Position Log 02 54 across the cutouts in Logs 02 51 and 02 53 The notch in the bottom right end fitting against the...

Page 42: ...52 02 51 02 54 02 52 02 54 8 Place Log 02 52 between Logs 02 51 and 02 75 and on the indentation on Log 02 54 The bottom right end sits behind the rear grate tab Front Brackets Notch 02 50 02 53 02 50...

Page 43: ...nd around the embers Avoid stacking platinum embers Platinum embers may be placed over burner ports 11 Test fire to ensure proper light off make sure flame flows smoothly from one end of burner to the...

Page 44: ...2 The standard flush door comes with a black frame To install the frame simply hook the top door flange onto the top of the unit and swing the door towards the unit see diagram 1 Be careful that the...

Page 45: ...warranty The remote control kit comes with a hand held transmitter areceiverandawallmountingplate 1 Choose a convenient location on the wall to install the receiver and the receptacle box protection f...

Page 46: ...ill continue to operate However a 120V A C power supply is needed for the fan blower operation Do not cut the ground terminal off under any circumstances NOTE Even if the fan is not purchased with the...

Page 47: ...6D 1 Zero Clearance Direct Vent Gas Fireplace 47 INSTALLATION For PROPANE Units and Units Equipped with DC Spark Boxes For installation of the DC Spark Box refer to the LP Conversion instructions in t...

Page 48: ...pproximately4 fromthecontrolbox Ensure that there is no interference with the wires when the louver is closed and that no wire will touch the hot metal surfaces or sharp edges 13 Plug the fan power co...

Page 49: ...s part of the curing process The glass should be cleaned or the film will bake on and become very difficult to remove Use a non abrasive cleaner and NEVER clean the glass while it is hot AERATION ADJU...

Page 50: ...y is positioned directly under the burnertube s andlogsandismadeofadifferent gauge material from the rest of the firebox and body Therefore thevaryingthicknessesofsteel will expand and contract at sli...

Page 51: ...shown in the diagrams under Log Installation Note Improper positioning of logs may create carbon build up and will severely alter the unit s performance which is not covered under warranty THERMOPILE...

Page 52: ...asket may severely affect the appliance performance 9 Reinstall the 10 hold down screws 10 Hook up the 2 TP and 2 TH wires to the appropriate connections on the valve 11 Reinstall the bottom brick pan...

Page 53: ...at is attached 2 screws per hinge to the lip on bottom of the unit 3 Open the bottom louver Pull the Burner ON OFF control box from inside the bottom of the fireplace and position the slots in the bra...

Page 54: ...the inner cut outs to secure the base of the Frame using the 2 x Hex Head Drill Point Screws provided Backside of Full Screen Door Frame Shown Inside Top of Outer Frame Hinge Bracket Inner Hinge Brack...

Page 55: ...inge Location 6 Slide the Top Grill into the louver brackets located on the inside top of the firebox Push in place Top Grill 8 Close screen doors 7 Install the Left and Right Side Screen Doors in the...

Page 56: ...agram 1 Min 14 1 4 362mm P36 Min 361 4 921mm Steel Stud Steel Stud Min 18 5 8 473mm P36D Option 1 Fireplace with 1 2 13mm Facing Material INSTALLATION NOTE The hearth material must be brought past the...

Page 57: ...bracket as indicated refer to Diagram 2 3 Install On Off switch refer to Diagram 3 4 Place bracket under the Flange Secure with 2 screws as indicated in Diagram 4 Diagram 2 Diagram 3 5 Loosen the 3 x...

Page 58: ...th the correspond hole on the Top Support Frame then secure with 1 screw b Repeat step on the other side 10 Change in Logo Replace existing logo with Regency logo a Mount Side Support Frame to unit as...

Page 59: ...ght 34 Brick Panel Bottom 35 Thermodisc Bracket 432 967 Burner ON OFF Switch Assy 38 910 241 Switch Burner ON OFF 3 way 910 899 Wire Harness Valve to Burner 432 917 Fan Speed Control Assy 120 Volts Op...

Page 60: ...pane 56 Valve Tray NG LP 57 910 478 Valve S I T Natural Gas Propane 58 Valve Bracket 65 Pilot Bracket 66 910 038 Pilot Assy S I T 3 Flame NG 910 039 Pilot Assy S I T 3 Flame LP 67 Pilot Holder 68 W840...

Page 61: ...ole 904 691 U Clip 510 920 Flush Louvers Set Gold Blk 510 921 Flush Louvers Set Brass Blk 510 922 Flush Louvers Set Black 510 923 Flush Louvers Set Steel Black 138 Flush Louver Assy Top 139 Flush Louv...

Page 62: ...62 Regency P36D 1 Zero Clearance Direct Vent Gas Fireplace NOTES...

Page 63: ...agent Transportation Prepaid if requested Porcelain Enamel Absolute perfectionisneither guaranteednor commercially possible Any chips must be reported and inspected by an authorized dealer within thr...

Page 64: ...register your product online today View and modify a list of all your registered products Request automatic email notification of new product updates Stay informed about the current promotions events...

Reviews: