Regal Smartvalve 7001 Instruction Bulletin Download Page 11

11

C)  TO EXIT THE CONFIGURATION MODE 

 

1) Follow the same steps as explained in Section 4C      

          (TO EXIT THE ENGINEERING MODE). 

 

NOTE: The system is now ready for start-up. 

 

After all wiring and plumbing has been completed, and the 
Engineering and Configuration parameters have been                             
confirmed, the system is ready for startup. 

 
Once the system is up and running, the TOP LINE of the 
SMARTVALVE display screen will show the water 

FLOW 

rate 

in the selected units. The ball float in the remote metering tube 
should read the same gas feed rate as shown on the bottom 
line of the SMARTVALVE display screen. ALWAYS READ 
THE CENTER OF THE BALL FLOAT.   

 

IMPORTANT:

 The REGAL 7500 Remote Meter Panel MUST 

be configured for AUTOMATIC control. 
  

A)  LINEARIZING (CALIBRATING) THE  
     SMARTVALVE

 

 

IMPORTANT:

 As previously mentioned, the SMARTVALVE 

has been calibrated (linearized) at the factory, however, it is 
still recommended that the user/installer checks and becomes 
familiar with the linearization process at startup, especially if all 
system components HAVE NOT been supplied by Chlorinators 
Incorporated. To check the linearization, proceed as follows: 

    

1) ENTER THE ENGINEERING MODE as explained in               

Section 5.0. 

 

2) Once in the Engineering Mode, scroll to the 

CAL VALVE

 

parameter. 

   

NOTE:

 Linearization will be based upon the factory set, 

5-point linearization curve. Confirm this setting by                         
checking the previous (

LAST

) parameter, 

VALVE CAL 

PTS 

(Valve Calibration Points). 

  

3) While observing the ball float in the Remote Metering         

Tube, press the 

ADJ

 (adjust) keypad button and the               

SMARTVALVE will start to drive to the ZERO feed rate 
position. The ball should come to rest on the bottom                 
stop of the metering tube at exactly the same time the   
motor stops driving. 

 

4) The Top Line of the SMARTVALVE display screen will  

show a ZERO VOLTAGE reading of 

0.45 V

.  

 

NOTE:

 A voltage reading from 

0.41

 to 

0.49

 is acceptable. 

 

IMPORTANT: If for some reason the voltage reading 
falls outside of the acceptable range, contact                           
Chlorinators Incorporated for assistance.

 

 
 
 
 
 
 
 
 
 
 

5) Once the correct ZERO voltage reading has been             

confirmed, press the 

NEXT

 keypad button and the             

SMARTVALVE will automatically open to the second       
linearization point which represents 

25%

 of the system’s 

Full Scale (capacity). e.g.- For a 50 PPD system, 25%  
would be 

12.5 PPD

 

6) If the reading on the metering tube panel equals the                 

reading on the SMARTVALVE display screen, press               

ENTER

 and proceed to step 8.  

 

7) If the readings 

DO NOT

 match, press 

ADJ

 (adjust). Use 

the 

UP

 and 

DOWN

 keypad buttons to move the ball float 

to the correct (

12.5 PPD

) reading on the metering tube. 

Once the value matches the reading on the display,               
press 

ENTER

 to accept. 

  

8) Press 

NEXT

 and the SMARTVALVE will automatically   

open to the third linearization point representing 50% of 
the valve’s capacity. e.g.- 50% of a 50 PPD system               
equals 25 PPD.  

 

NOTE:

 Follow the same procedure described in steps 6 

and 7 to complete the 50% point. Then continue on to the 
fourth linearization point (75%) and the fifth linearization 
point (100%).   

 

9) Once the five linearization points have been set, press  

the 

LAST

 button four times to return the valve back to   

the first point (0%). 

IMPORTANT:

 If the valve is not               

returned to 0%, it will continue to feed gas at 100% until 
you exit the Engineering Mode and reset the operation  
setting from Manual (

MANL

) to Automatic (

AUTO

).   

 
    10) Once the valve is reset to 0%, the Linearization is complete. 

Simply press escape (

ESC

) to accept the Linearization 

settings. The 

CAL VALVE 

parameter is once again displayed. 

Press escape (

ESC) 

a second time and you will be               

asked to 

SAVE CHANGES?

. Press 

YES

 to confirm and 

you will return to the Main Operating Screen. Press               

MENU

, then 

AUTO

 to return the valve to automatic             

operation. 

 

 

NOTE: THE SMARTVALVE IS NOW READY FOR OPERATION. 
CONTINUE ON TO THE NEXT SECTION.

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

6.0   SYSTEM START-UP

Summary of Contents for Smartvalve 7001

Page 1: ...nt is suitable for use only with the gases specified DO NOT USE THIS EQUIPMENT WITH OTHER GASES Such use can result in failures having hazardous consequences 2 This equipment is designed FOR VACUUM SE...

Page 2: ...against material defects in components and workmanship occurring in the course of manufacture Buyer s sole remedy for breach of said warranty shall be at C I s option either repair or replacement of...

Page 3: ...ct to open or close the valve 8 Do not reuse lead gaskets They may not seal properly thereby permitting the release of gas 9 Use only lead gaskets Other types may contract with temperature variations...

Page 4: ...ing the Analog Output C Setting the Mechanical Zero 8 0 MAINTENANCE 9 0 SPECIFICATIONS A To Enter the Configuration Mode B Configuration Parameters C To Exit the Configuration Mode 5 0 CONFIGURATION M...

Page 5: ...ly Circuit Board Part No 7071 Drawing No 7 Use of External Surge Suppressors Consult manufacturer of surge suppressor for installation and wiring specifics Drawing No 8 Control Valve Assembly for 10 t...

Page 6: ...the middle third of the system s capacity maximum feed rate 2 The water flow meter and transmitter must be sized or scaled so the maximum water flow coincides with the maximum feed rate capacity of t...

Page 7: ...ting to the vacuum fitting on the ejector assembly 5 Finally connect a length of tubing from the bottom connection of the pressure relief valve routing it outside with the end facing down and protecte...

Page 8: ...isplay screen reads ENT ENG PW 0 Enter Engineering Password 2 Press the NEXT keypad button three times until the factory default password 0 0 0 0 appears Then press ENT enter to accept 3 The TOP LINE...

Page 9: ...eatedly until the preferred FIRST digit is displayed Then press NEXT to accept the new value b The number 0 will appear as the second digit Once again use UP or DOWN to scroll to the preferred number...

Page 10: ...red and designate what condition the alarm represents The selections are OFF LOW or HIGH If the SET POINT MODE setting is left in the factory default OFF position no additional parameters will be made...

Page 11: ...ading of 0 45 V NOTE A voltage reading from 0 41 to 0 49 is acceptable IMPORTANT If for some reason the voltage reading falls outside of the acceptable range contact Chlorinators Incorporated for assi...

Page 12: ...t the feed rate simply turn the thumbwheel while using the remote meter ball float as a guide 4 Fully Manual If it is necessary to temporarily bypass the SMARTVALVE entirely use the remote meter rate...

Page 13: ...t Press ESC a second time and SAVE CHANGES to return to the main operating screen C SETTING MECHANICAL ZERO See Drawing No 8 for Model 7001 or No 9 for Model 7006 The mechanical zero valve plug positi...

Page 14: ...AM 16 Bit Display 20 character 2 line Backlit LCD Relays Three 3 each 10A 250 VAC Environmental Limits 32 to 120 F 0 to 50 C Calibration Accuracy 0 25 from zero Speed of Response Variable and field se...

Page 15: ...Union Typ BY OTHERS Gauge for Supply Pressure Ps BY OTHERS Gauge for Back Pressure Pb BY OTHERS REGAL Model CRA 5000 Residual Analyzer REGAL VAC 1000 Vacuum Monitor Static Mixer BY OTHERS Residual Sa...

Page 16: ...Ball Valve 1 PVC Ball Valve 3 PVC Ball Valve Chemical Solution Injection Point Water Flow Meter 4 20 mA Analog Flow Input Signal 4 20 Milliamp Analog Output Signal 1 For Automatic Operation open ball...

Page 17: ...valve tool supplied with your REGAL chlorinator system into the slot and tilt the screwdriver in the direction of the terminal number This will open the clamp and allow the wire to be inserted Remove...

Page 18: ...RIGHT SIDE JUNCTION BOX 1 L See Note 1 2 N See Note 1 3 Ground See Note 1 4 N O Relay K1 5 Com Relay K1 6 N C Relay K1 7 N O Relay K2 8 Com Relay K2 9 N C Relay K2 10 N O Relay K3 11 Com Relay K3 NOT...

Page 19: ...19 DRAWING NO 5 DISPLAY CIRCUIT BOARD Part Number 7070 NOTE All wiring connections to this circuit board are made at the factory prior to shipment See Drawing No 4 for Field Wiring...

Page 20: ...20 DRAWING NO 6 POWER RELAY CIRCUIT BOARD Part Number 7071 NOTE All wiring connections to this circuit board are made at the factory prior to shipment See Drawing No 4 for Field Wiring...

Page 21: ...h Grounding Rod External Surge Protection Device Typ BY OTHERS IMPORTANT Consult the manufacturer of the transient voltage surge suppression device for proper wiring of inputs and outputs Analog and d...

Page 22: ...7121 1 Potentiometer 7124 3 S 405 0 Ring 7127 1 S 414 0 Ring 7128 2 Seal 7129 1 Seal 7131 4 Screw 10 24 X 2 1 2 7132 1 Screw 10 24 X 1 2 7133 4 Screw 10 32 X 1 with O Ring 7135 5 10 Lock Washer 7136...

Page 23: ...r 7121 1 Potentiometer 7122 1 Guide Retainer 7124 1 S 405 O Ring 7125 1 S 415 O Ring 7126 1 S 407 O Ring 7127 1 S 414 O Ring 7128 1 Seal 7129 1 Seal 7130 1 Seal 7131 4 Screw 10 24 X 2 1 2 7132 1 Screw...

Page 24: ...24 DRAWING NO 10 ENGINEERING DATA SHEET Series 7000 SMARTVALVE Dimensions DIMENSIONS INCHES mm 7500 REMOTE METER PANEL SMARTVALVE...

Page 25: ...e Valve Plug O Ring 11 S 406 2 Meter Tube Plug O Ring 12 Z 815 4 Screw 1 4 20 x 1 Long 13 ZZ 278 1 Plug 1 2 NPT 14 See Chart 2 Tube Fitting Elbow Not Shown NOTE If system is using 1000 PPD or 2000 PPD...

Page 26: ...Metering Tube Float Assembly 1000 PPD 20 Kg Hr 2000 PPD 40 Kg Hr Flow Meter Inlet Block Back Panel Mounting Screws For RV 810 RV 814 Base Plate for RV 814 Rate Valve Seat Plug with 2 S 803 Seals NOTES...

Page 27: ...pad 1 At dosage settings greater than 100 proportionality is lost at some water flow rate less than the designed maximum rate If the dosage setting is increased to 200 for example proportional control...

Page 28: ...2019 Chlorinators Incorporated Printed in U S A Pub No 0919 3 1044 SE Dixie Cutoff Road Stuart Florida 34994 USA Phone 772 288 4854 Fax 772 287 3238 www regalchlorinators com Email regal regalchlorin...

Reviews: