Regada SPR 0.1PA Installation, Service And Maintenance Instructions Download Page 26

24

 

 

SPR 0.1PA

 

 

Manual control: 

 

If  needed  (during  adjusting,  function  checking,  failure  etc.)  the  stuff  can  change  setting  of  the 

controlled body using the handwheel.  

Instructions for manual control:

 

  Switch the power supply off. 

  Turn  the  button for gear  disengagement  to the right  by  90°  (Fig.  9), the button  arrow  shows  the 

symbol of hand) what disengages the gear in the actuator. In case of lever actuator it is needed to 
hold the lever to prevent the device with load against stroke to the end position. 

  Set the valve to the chosen position: 

a)

 For actuators with manual control:

 push and turn the hand wheel located on 

the actuator upper cover. While turning counter-clockwisely  the valve is turning 
in  the  direction  "closing".  Having  the  valve  in  the  required  position  turn  the 
button  for  gear  disengagement  to  the  position  "motored  operation"  what 
engages the gears. Put the hand wheel back to its original position. 
b)

 For actuators without manual control 

of the version with a stand and lever - 

using the lever. After resetting of the valve put the gear disengagement button 
to the original position. 

Note: 
After  putting  the  button  for  disengaging  of  gearing  again  to  the  position  of  motor 
operation if the gearing is not connected it is needed to turn the handwheel or the lever 
to put the gears into mesh.   

 

In case of manual control the set end positions are not mistuned. 

 

Actuators without gear disengagement cannot be manually controlled.  

 

4.2  Maintenance - extent and periodicity 

 

During inspections and maintenance is needed to tighten all screws and nuts that affect the tightness and 

coverage.  Similarly, once a year should be checked and if necessary tighten mounting screws of the terminal 
wires and assuring of the slip-on joints with wires. 
 

The interval between two preventive inspections is four years. 

The replacement of cover gaskets and gasket of an oil filling is needed in case of damage or after 6 years of the 
operation. 

 

The grease in the supplied actuators is designed for the lifetime of the product. 
It is not necessary to change the grease during the operation of the actuator. 

Lubrication: 

  - gear part - igrease HF 401/0 (GLEIT-

µ

) resp. GLEITMO 585 K 

 

      

Lubrication of the valve stem is independent on maintenance of the EA! 

 

 

 

After  every  potential  flooding  of  the  product  check,  whether  there  is  no  water  inside.  After  eventual  water 

penetration,  dry  the  product  before  repeated  putting  into  operation  and  replace  damaged  sealings,  resp. 
other parts of EA. identically check also tightness of cable bushings and replace them, if they are damaged. 

 

 

Every  six  months  it  is  recommended  to  perform  one  check  move  in  frame  of  adjusted  operation  stroke  to 

verify reliability of functioning with setting back to the original position. 

 

 If the audit rules do not determine else the inspection of EA is performed ones a year and tightening of all 

connecting and grounded screws have to be checked to avoid overheating. 

 

  After 6 months from putting of EA into operation and once a year it is recommended to check tightening of 

fixing screws between the EA and the valve. (Tighten the screws with the cross system.) 

 

While  connecting  and  disconnecting  of  the  EA  check  the  tightness  of  cable  glands  –  those  with 

damaged sealings should be replaced by new ones of the approved type!  

 

Keep  the  EA  clean  and  take  care  about  removing  impurities  and  dust.  The  cleaning  has  to  be 

performed regularly according to the operation possibilities and requirements

Fig. 9

Fig.10 

Summary of Contents for SPR 0.1PA

Page 1: ...Electric part turn actuators Rematic with the DMS 3 electronic control SPR 0 1PA INSTALLATION SERVICE AND MAINTENANCE INSTRUCTIONS 74 1076 02 74 1076 02...

Page 2: ...r Operating time s 90 Wiring diagram Operating angle Input operation signal Warranty period months Output signal Serial number of electric motor Serial number of control unit Tests made by Packed by D...

Page 3: ...19 3 2 Procedure for setting individual parameters and the register of errors and warnings is given in the separate attachment 74 1053 02 of these operating instructions 20 3 3 Putting an EA into oper...

Page 4: ...ith possibility of installation in areas specially danger regarding casualties caused by electric current Electric actuators are according to directive LVD 2014 35 EU and standard IEC 61010 1 assigned...

Page 5: ...Switching off torque Manual control 0096 ISO 7000 Protection terminal 5019 IEC 60417 1 5 Warranty conditions The supplier is responsible for completeness of the delivery and guarantees these specific...

Page 6: ...position setting by manual adjusting of the actuator Use the stop ends in motor operated operation of actuator is inadmissible Warning Actuator installed on the open place must be protected against a...

Page 7: ...serious danger of plants and moulds growing AK 2 with serious danger of animals occurrence insects birds small animals AL 2 with detrimental influence of radiation of stray current with intensity of...

Page 8: ...led manually according to instructions stated in chapter 4 Service maintenance and troubleshooting Standard equipment of electronic module DMS3 for SPR 0 1PA Control unit 2 main part of system DMS3 it...

Page 9: ...SPR 0 1PA 7 1 7 2 Fig 1 5 4 3 8...

Page 10: ...0 2 75 375 0 04 0 4 25 63 0 27 500 SPR 0 1PA type number 238 160 90 version with stop ends 1 50 40 3 2 5 2 Single phase 230 220 AC resp 24 AC 1 300 0 025 0 25 0 165 400 1 At EA version without stop en...

Page 11: ...on disabled Position O position open Position C position close Torque O torque open Torque C torque close Torque O or Torque C Torque O or Position O Torque C or Position C opens closes movement movem...

Page 12: ...nected to the EA control unit communication connector and the EA cover removed Space heater E1 Space heater supply voltage corresponding with motor supply voltage Space heater power output SPR 0 1PA c...

Page 13: ...circuit breaker must be installed on the power supply line as close as possible to the device easily accessible to operators and identified as the actuator isolation switch External and internal are...

Page 14: ...12 SPR 0 1PA INTERNAL PROTECTION TERMINAL Fig 2 FUSE SUPPLY F3 Fig 2a EXTERNAL PROTECTION TERMINAL...

Page 15: ...be reported without any delay to supplier Electric actuators and their accessories must be stored in dry well ventilated covered spaces protected against impurities dust soil humidity by placement to...

Page 16: ...accordance with ISO 5211 Standard b With a stand and a lever a lever and a pull rod or without any lever with output shaft of square section 11x11 mm or circular section 22 mm The flange actuators ar...

Page 17: ...he button from the position motor drive to the position manual Adjust the levers of the EA and the damper identically to one of the limit positions opened or closed Connect the control levers of the E...

Page 18: ...ead them separately with thrust wires or it is necessary to use shielded wires 2 Together with EA are delivered sealing cable glands which make possible enclosure protection IP68 in case of tight moun...

Page 19: ...active input I1 or flash in the mode of parameters set up LED I2 yellow permanent lights with active input I2 LED POWER green it light on at leading the power supply Electronics programme selections o...

Page 20: ...18 SPR 0 1PA Fig 6 BUTTON MENU SETTING BUTTON P SETTING BUTTON C SETTING BUTTON O LED ERROR LED OPEN LED MENU LED CLOSE LED PAR LED I1 LED SEL LED I2 LED POWER COMMUNICATION CONNECTOR...

Page 21: ...supplied on clamps IN IN The EA stops once the required position is reached corresponding with the input control signal supplied or the set end position is reached The EA stops to respond to 0 4 12 to...

Page 22: ...of the EA 4 READY RELAY errors READY COM NO relay contacts closed in error free conditions 5 RELAY R1 R2 position O for relay R1 position C for relay R2 from position 95 for relay RE 3 from position...

Page 23: ...the EA auto calibration by pressing the P button on the control unit for 2 seconds as minimum until LED ERROR red and LED MENU green light up see also the procedure in the separate attachment No 74 1...

Page 24: ...diate position see Note 2 presented above start the EA auto calibration by pressing the P button on the control unit for 2 seconds as minimum until LED ERROR red LED MENU green and LED PAR red light u...

Page 25: ...e 4 Service maintenance and troubleshooting 4 1 Service 1 In general it is provided that service of the EA is performed by a qualified worker in accordance with requirement given in Chapter 1 2 After...

Page 26: ...hecked and if necessary tighten mounting screws of the terminal wires and assuring of the slip on joints with wires The interval between two preventive inspections is four years The replacement of cov...

Page 27: ...qualified persons trained in the production plant or by a contracted service centre The EA electronics makes possible to identify some failures of the electric actuator The control unit blicking LED E...

Page 28: ...eturn disengagement button after the manual control to the position mechanical control In such case the EA will remain standing 5 Accessories and spare parts 5 1 Accessories The EA is delivered with t...

Page 29: ...SPR 0 1PA 27 6 Accessories 6 1 Wiring diagrams...

Page 30: ...2 up to 10V and output signal 4 to 20 mA C capacitor COM RS232 possibility for connecting the control unit to a PC EPV passive electronic position transmitter is passive E1 space heater F3 fuse of vol...

Page 31: ...type of the EA torque open or torque close not valid for this type of the EA torque open or position open not valid for this type of the EA torque close or position close not valid for this type of t...

Page 32: ...30 SPR 0 1PA 6 2 Dimensional drawings...

Page 33: ...SPR 0 1PA 31...

Page 34: ...32 SPR 0 1PA...

Page 35: ...SPR 0 1PA 33...

Page 36: ...34 SPR 0 1PA...

Page 37: ...SPR 0 1PA 35...

Page 38: ...36 SPR 0 1PA...

Page 39: ...ck report Service center D Date of repair Guarantee repair no User of actuator Claim applied by Actuator type number Actuator production number Product claim fault Detected product fault Used spare pa...

Page 40: ...uarantee service check report Service center Date of repair User of actuator Actuator operating place Actuator type number Actuator production number Detected product fault Used spare parts Remarks Is...

Page 41: ...80 01 Pre ov Tel 421 0 51 7480 460 Fax 421 0 51 7732 096 E mail regada regada sk Czech republic REGADA esk s r o Ltd exclusive representation REGADA s r o Ltd for sale of electric actuators Regada esk...

Reviews: