22
SPR 0.1PA
3.5 Putting an EA into operation when it is necessary to do a change to the angle
(setting new end positions), and the other parameter setting done by the producer
suits to your needs
When an EA is delivered from the producer without armature, and the setting of other parameters done by the
producer suit to your needs, and it is necessary to do a change to the EA stroke, proceed as follows:
-
connect the EA with the armature to be controlled (
according to chapter 2
) and fit this assembly into the
specified technology complex
-
connect the EA electrically according to the wiring diagram and chapter Electrical connection...,
switch on the supply voltage and switch off control signals fed to the EA (input control signal
(EA reports error No.2), eventually binary inputs)
-
move the EA in the „Closed“ end position and write the „Closed“ end position into the memory by
pressing the
C
button
for 2s as minimum (
until the LED ERROR (red), LED MENU (green) and LED
PAR (red) lights up) – see also the procedure presented in the separate attachment No.74 1053 02
-
release the
C
setting button
-
move the EA in the „Opened“ end position and write the „Opened“ end position into the memory by
pressing the
Q
button
for 2s as minimum
(until the LED ERROR (red), LED MENU (green) and LED
PAR (red) lights up) – see also the procedure presented in the separate attachment No.74 1053 02
-
release the
O
setting button
-
introduce the EA into an intermediate position (see
Note 2
presented above)
-
start the EA auto-calibration by pressing the
P
button on the control unit
for 2 seconds as minimum
until
LED ERROR (red), LED MENU (green) and LED PAR (red) light up – see also the procedure in the
separate attachment No.74 1053 02
-
release the
P
setting button
-
after releasing the
P
button the auto-calibration procedure starts
-
switch on control signals, the EA is prepared for its operation and starts to response to control inputs
-
if changes to some parameters would be necessary, proceed please according to the instructions given in
the separate attachment No.74 1053 02
* This applies to setting of EA to be controlled by 2P and 3P or 3P/2P switched by I2, at the same time with
standard setting of menu 9 FAILURE REACTION: STOP!
3.6 Setting other parameters
If changes to some parameters would be necessary, proceed please according to the instructions given in the
separate attachment No 74 1053 02.
3.7 Error messages from the control unit
The EA electronics makes possible to identify some failures of EA. The failure is signalled by flickering LED
ERROR (red) on the control unit (Fig.6). For identifying the reason of the error, the EA can be connected to a PC
and the program helps you find the type of the error.
The list of errors and warnings and the way for identifying a given error as well are presented in the separate
attachment No. 74 1053 02.
The list of errors and warnings compiled by the producer is presented in table 3 (chapter 4.3).
A field serviceman is only entitled to change the errors and warnings set using the programme once the EA is
connected to the PC.
Summary of Contents for SPR 0.1PA
Page 9: ...SPR 0 1PA 7 1 7 2 Fig 1 5 4 3 8...
Page 29: ...SPR 0 1PA 27 6 Accessories 6 1 Wiring diagrams...
Page 32: ...30 SPR 0 1PA 6 2 Dimensional drawings...
Page 33: ...SPR 0 1PA 31...
Page 34: ...32 SPR 0 1PA...
Page 35: ...SPR 0 1PA 33...
Page 36: ...34 SPR 0 1PA...
Page 37: ...SPR 0 1PA 35...
Page 38: ...36 SPR 0 1PA...