Regada Rematic STR 1PA Installation, Service And Maintenance Instructions Download Page 53

 STR 1PA, STR 2PA

 

 

51 

Terminals for STR PA for DMS3: 

PE, N, L - terminals (0,05-1,5 mm

2

) of supply (24 V AC resp. 110/120 V AC, resp. 230/240 V AC, 50/60 Hz 

(according to the specification – voltage and frequency are stated on nameplate of EA) 

2, 3, 4 – terminals (max. 1,5 mm

) of supply of supply 3-phase motor 3x400 resp. 3x380 V AC 

5,6 – terminals (max. 1,5 mm

) of supply of supply 3-phase motor 3x400 resp. 3x380 V AC 

OP, CL – – terminals (max. 1,5 mm

2

 ) of output  of control for without reverse unit 

0 V, +24 V– terminals (max. 1,5 mm

2

 ) of output voltage 24 V DC (40 mA) 

COM, CLOSE OPEN, I1, I2 – terminals (0,05 - 1 mm

2

) of control inputs 24 V DC 

+IN, -IN, SH – terminals (0,05 - 1 mm

2

) of unified input current signal or voltage signal  

+L, -L, SH – terminals (0,05 - 1 mm

2

) of output current signal (passive) 4-20 mA 

COM, NO, NC, NO, NO – terminals (0,05 - 1,5 mm

2

) of 

relay

 READY, 

relay

 R1 a R2 (

on control unit

COM5, NO5, NC5 – terminals (0,05 – 1,5 mm

2

) relay RE5 (on the module of the additional relays) 

COM1, RE4, RE3, RE2, RE1 – terminals (0,05 - 1,5 mm

2

) relay RE4, RE3, RE2, RE1 (on the module of the 

additional relays) 

COM, NO, NC – terminals (0,05 – 1,5 mm

2

) of relay READY 

(on the module of the additional relays)

 

 

Terminals for DMS3 Modbus/Profibus: 

- screwless terminals are in separately terminal box. cross-section of connection wire  0,08 - 2,5 mm

2

 

PE,N,U,V,W - terminals of supply voltage 230 V AC and 3x400 V AC 
1,2,3,4,5,6 – terminals of single channel interface Modbus/Profibus 
7,8,9,10,11,12 - terminals of duo channel interface Modbus/Profibus 
21,22 – terminals of output voltage 24 V DC (40 mA) 
13,14,15,16,17 – terminals of control inputs 24 V DC (40mA) 

 

Note 1: On terminal N, L terminal power supply (X) feed supply voltage 230  V AC, or 24 V AC by you - specified 
type of construction EA. For supply voltage 24 V AC no need connect ground wire PE. For a version of EA with 
the supply voltage 3x400 or 3x380V, terminals N, L on terminal board of power supply (X) are fed by power 
supply 220 respectively 

230 V AC.

 

Note  2:  Program  possibilities  for 

R1,  R2,  RE1,  RE2,  RE3,  RE4,  RE5

  relays:  DISABLED,  open  position,  close 

position, torque-open, torque – close, torque open or torque close, torque open or position open, torque close or 
position  close,  open,  close,  movement,  movement  flasher,  to  position,  from  position,  warning,  remote  control, 
local control, control shut off, relay READY 
Program possibilities for 

READY

 relay: errors, errors or warnings, errors or no remote, errors or warnings or no 

remote.  
Program possibilities for output signal (from 

EPV

 passive): 4 to 20 mA, 20 to 4 mA. 

Control  programme  options  (regulating)(not  valid  for  with  Modbus/Profibus  protocol):  2P,  3P,  3P/2P  switched 
over to I2 
Program possibilities 

for input control signal (N)

: 4 to 20 mA (2 to 10 V), 20 to 4 mA (10 to 2 V), 0 to 20 mA (0 

to 10 V), 20 to 0 mA (10 to 0 V). 
Program possibilities -  for Modbus protocol 
 

address  – 1 .... 247 

 

baudrate [bit/s] – 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 

 

parity – even, odd, No 

 

       redundancy – off, Cable,   Component, Repeater 

 

connect  time [s] – 0,1 .... 25,5s 

 
Program possibilities -  for Profibus protocol 
 

Address 1 – 1 ... 126 

 

Address 2 – 1 ....126 

 

Redundancy: - Off, Simple  

Program possibilities for 

inputs I1

: DISABLED, ESD, DBL (local releasing, remote releasing - not valid for EA 

without local control), STOP. 
Program possibilities for 

inputs I2

: DISABLED, ESD, DBL (local releasing, remote releasing), STOP 

2P (when controller is switch on)(for control programme option 3P/2P I2)) allows control using the binary 24V DC 
inputs with I2 input activated. 
Program possibilities of 

FAILURE REACTION

: OPEN, CLOSE, STOP, SAFE POSITION.  

The identical functions cannot be set on I1 &I2 inputs in addition to the disabled state (e.g., if the ESD function is 
set on I1 input, it is not possible to select the (ESD) function on I2 input at the same time.

  

 

Relay READY on the control unit is doubled with  relay READY on the module of the additional relays. 
Relay R1 and relay R2 on the control unit is doubled with  relay RE1 and  relay RE2 on the module of the 
additional relays. 

Summary of Contents for Rematic STR 1PA

Page 1: ...INSTALLATION SERVICE AND MAINTENANCE INSTRUCTIONS 74 1091 02 74 1091 02 Electric linear actuators Rematic with the DMS3 DMS3 M1 DMS3 M2 DMS3 P1 DMS3 P2 electronic control STR 1PA STR 2PA...

Page 2: ...rust N Wiring diagram Operating speed mm min Operating stroke mm Control Input operation signal Warranty period months Output signal Serial number of electric motor Serial number of control unit Tests...

Page 3: ...n the stroke and parameter setting done by the producer suit to your needs 33 3 5 Putting an EA into operation when it is necessary to do a change to the stroke setting new end positions and the other...

Page 4: ...ct Regarding Its Exposure Rate EA of STR PA types are reserved technical devices with higher rate of danger with possibility of installation in areas specially danger regarding casualties caused by el...

Page 5: ...stitute the text messages Some of them are in accordance with EN ISO 7010 ISO 7000 and IEC 60417 within valid edition Dangerous voltage EN ISO 7010 W012 Stroke of the electric linear actuator Switchin...

Page 6: ...assembly and operation of electric actuators in standard make can be on covered places of industrial objects without the regulation of temperature humidity and with protection against direct exposure...

Page 7: ...mean sinusoid vibrations with frequency in range 10 to 150 Hz with amplitude of shift 0 15 mm for f fp and with amplitude of acceleration 19 6 m s2 for f fp contact frequency fp is 57 to 62 Hz applies...

Page 8: ...p to 90 cycles per hour for automatic regulation intermitted operation S4 25 90 up to 1200 cycles per hour Note The operation modes consist of the loading type load factor and connection switching fre...

Page 9: ...rol system for STR PA Control unit 2 main part of system DMS3 it contains microprocessor 6 signal LED and 4 buttons for simple adjustment and control of EA connectors for connection of thrust scanner...

Page 10: ...8 STR 1PA STR 2PA Fig 1 1 5 2 4 3 8 7 6...

Page 11: ...STR 1PA STR 2PA 9 Fig 1A 4 8 2 7 6 1 5...

Page 12: ...N N kg V 10 W 1 min A F V 50Hz 60Hz 8 10 16 19 7000 8700 8000 10000 32 38 5000 6300 6000 7500 63 1 74 1 2560 3200 3000 3700 10 12 7000 8700 8000 10000 20 24 6000 7500 6900 8600 40 52 4000 5000 4600 58...

Page 13: ...0 72 14 000 11 200 12 000 16 000 80 100 14 000 11 200 12 000 16 000 Single phase 120 60 220 50 230 50 240 60 70 60 60 70 3 380 2 770 2 770 3 380 1 20 0 70 0 70 0 54 16 200 7 400 7 400 4 400 21 500 17...

Page 14: ...ion relays are adjusted to the specified stroke with accuracy of 1mm It is possible to set up with buttons situated on the control unit resp with buttons situated on the local control resp program aft...

Page 15: ...dependent Factory setting up of the individual relays is shown in the Adjusting of actuator Chapter Transmitter output signal not valid for Modbus Profibus version Electronic position transmitter EPV...

Page 16: ...rates o 9 6 kbit s o 19 2 kbit s o 93 75 kbit s o 187 5 kbit s o 500 kbit s o 1500 kbit s Control by binary inputs 24 V DC by feeding of 24 V DC to terminals CLOSE and OPEN Programming possibilities...

Page 17: ...ng torque 0 285 N m 2 terminals 0 V 24 V with cross section of cross section wire max 1 5 mm2 Max terminal screw tightening torque 0 285 N m 5 terminals READY R1 R2 with cross section of connection wi...

Page 18: ...6 diameter of cable 6 to 10 5 mm and 1xM16 diameter of cable 9 to 13 mm extended Cable glands for EA with the DMS 3 electronic control with Modbus Profibus protocol 2 cable glands M20x1 5 cable diamet...

Page 19: ...XXXX YY 24 VAC 60 15 39 18 48 2 8 xx 431 1 JXXXX YY 3x380 V AC 50 15 40 0 25 STR 1PA 431 431 1 JXXXX YY 3x400 V AC 50 15 40 0 25 F 2 5 A 250 V 432 1 0XXXX YY 230 VAC 50 432 1 VXXXX YY 240 VAC 60 0 45...

Page 20: ...18 STR 1PA STR 2PA EXTERNAL PROTECTION TERMINAL Fig 2a INTERNAL PROTECTION TERMINAL FOR THREE PHASE VERSION WITH SSR Fig 2b INTERNAL PROTECTION TERMINAL FOR THREE PHASE VERSION WITH CONTACTORS Fig 2c...

Page 21: ...STR 1PA STR 2PA 19 INTERNAL PROTECTION TERMINAL WITH MODBUS PROTOCOL Fig 2d Fig 2e FUSE F4 1 FUSE F4 2...

Page 22: ...EA examine if during transportation resp storing did not come to its damage At the same time verify if the data on the labels corresponds to accompanying documentation and purchase sale contract order...

Page 23: ...responding dimensional drawing and put it to a mid position Before installation put the hand wheel on Mechanical connection with connection dimensions according to DIN Fig 3 Properly defat contact sur...

Page 24: ...w thread coupling Put the clamping parts of the thread coupling 8 on and tighten the both coupling screws 5 to have the coupling nut able to rotate Tighten the screws 4a or central nut 4 with the cros...

Page 25: ...to use shielded wires 2 Together with EA are delivered sealing cable glands which make possible enclosure protection IP68 in case of tight mounting onto supply lead For required enclosure it is neces...

Page 26: ...ode it lights with a control action for the closing direction eventually blinks besides the chosen parameter in the menu and lights up at writing the parameter into the memory LED I1 SEL yellow perman...

Page 27: ...f the EA 2P resp E2P for control programme option 3P 2P I2 or in case of active communication through Modbus Profibus protocol allows control using the binary 24V DC inputs with I2 input activated FAI...

Page 28: ...ON MENU SETTING BUTTON P SETTING BUTTON C SETTING BUTTON O LED ERROR LED OPEN LED MENU LED CLOSE LED PAR LED I1 LED SEL LED I2 LED POWER COMMUNICATION CONNECTOR COMMUNICATION MODBUS DUO CHANNEL COMMUN...

Page 29: ...10V input control signal supplied on terminals IN IN The EA stops once the required position is reached corresponding with the input control signal supplied or the set end position is reached The EA...

Page 30: ...the local control block is set to remote control The local control block has higher priority than the ESD or E2P ESD Emergency Shutdown is activated when the function parameter is set as I1 ESD and t...

Page 31: ...sition for single seat valves C Torque O Torque switching in both end positions by thrust for double seat valves 3 TORQUE BLOCKING 2 sec blocking time 5 blocking position for OPEN CLOSE direction 4 RE...

Page 32: ...is type of electric actuators is inoperative CYCLE MODE DISABLED CYCLE RUNNING TIME 10 s CYCLE PAUSE 50 s CYCLE POSITION O1 0 CYCLE POSITION O2 100 CYCLE POSITION C1 0 CYCLE POSITION C2 100 O AND C TO...

Page 33: ...shown on nameplate 8 BLOCK TIME 2 s 9 BLOCK POS O 5 10 BLOCK POS C 5 11 CPT output signal 4 to 20 mA 12 REGULATION according to specification 2P 3P 13 ANALOG INPUT 4 to 20 mA 2 to 10 V 14 16 14 DEAD...

Page 34: ...djusting button P on the control to activate the calibration process or start it from MENU 4 in the version with local control use the buttons on local control or from the programme once the EA is con...

Page 35: ...up see also the procedure in the separate attachment No 74 1053 02 release the P setting button after releasing the P button the calibration procedure starts after the calibration procedure is finish...

Page 36: ...OP 3 6 Setting other parameters If changes to some parameters would be necessary proceed please according to the instructions given in the separate attachment No 74 1053 02 3 7 Error messages from the...

Page 37: ...hand wheel While rotating the hand wheel clockwisely the output part moves in the direction Z closed Electric local control additional equipment Fig 7 If necessary in the case of accession function c...

Page 38: ...ease HF 401 0 GLEIT resp GLEITMO 585 K in versions for climate with temperatures 50 C till 40 C grease ISOFLEX TOPAS AK 50 linear adapter grease GLEIT HP 520M to 25 C resp HP 520S to 40 C Lubrication...

Page 39: ...of power the EA is prepared for operation In case of failure of any element of the EA it can be changed by a new one Entrust the change to a service centre In case of an EA failure which cannot be eli...

Page 40: ...Supply Relay module X Power Supply Relay module type X E2P X Profibus Channel 1 only for version with Profibus X Profibus Channel 2 only for version with Profibus X Notes X the error or warning flag...

Page 41: ...V AC 60 Hz 63 592 058 1 1A Electric motor 60W 120 VA 230 220 V AC 50 Hz 63 592 322 1 1A Electric motor 70W 125 VA 240 V AC 60 Hz 63 592 055 1 1A Electric motor 70W 125 VA 120 V AC 60 Hz 63 592 056 1...

Page 42: ...40 STR 1PA STR 2PA 6 Enclosures 6 1 Wiring diagrams ES STR 1PA and STR 2PA for single phase supply...

Page 43: ...STR 1PA STR 2PA 41 6 2 Wiring diagrams ES STR 1PA for three phase supply...

Page 44: ...42 STR 1PA STR 2PA 6 3 Wiring diagrams ES STR 2PA for three phase supply...

Page 45: ...STR 1PA STR 2PA 43 6 4 Wiring diagrams ES STR PA for three phase supply without reverse unit...

Page 46: ...44 STR 1PA STR 2PA 6 5 Wiring diagrams ES STR 2PA for three phase supply with contactless switching...

Page 47: ...STR 1PA STR 2PA 45...

Page 48: ...46 STR 1PA STR 2PA 6 6 Wiring diagrams EA STR PA with interface Modbus Profibus for single phase supply...

Page 49: ...STR 1PA STR 2PA 47 6 7 Wiring diagrams EA STR 1PA with interface Modbus Profibus for three phase supply...

Page 50: ...48 STR 1PA STR 2PA 6 8 Wiring diagrams EA STR 1PA with interface Modbus Profibus for three phase supply...

Page 51: ...STR 1PA STR 2PA 49 6 9 Wiring diagrams EA STR 2PA with interface Modbus Profibus for three phase supply with contactless switching...

Page 52: ...m of EA STR 2PA with 3 phase electric motor with contactors for the ON OFF control Z537c wiring diagram of EA STR PA with 3 phase electric motor without reverse unit for the ON OFF control Z574 wiring...

Page 53: ...board of power supply X are fed by power supply 220 respectively 230 V AC Note 2 Program possibilities for R1 R2 RE1 RE2 RE3 RE4 RE5 relays DISABLED open position close position torque open torque cl...

Page 54: ...52 STR 1PA STR 2PA 6 10 Dimensional drawings STR 1PA P 1169 Flange DIN 3358...

Page 55: ...STR 1PA STR 2PA 53 P 1170 Pillars...

Page 56: ...54 STR 1PA STR 2PA...

Page 57: ...STR 1PA STR 2PA 55 P 2046 EA with local control...

Page 58: ...56 STR 1PA STR 2PA 6 11 Dimensional drawings STR 2PA...

Page 59: ...STR 1PA STR 2PA 57...

Page 60: ...58 STR 1PA STR 2PA P 1246a C Vyhotovenie Version D1 Z D3 L L L1 H W W D2 P C 1246a i 8 6 7 8 UN9 125 80 621 M 32...

Page 61: ...STR 1PA STR 2PA 59...

Page 62: ...60 STR 1PA STR 2PA...

Page 63: ...STR 1PA STR 2PA 61...

Page 64: ...62 STR 1PA STR 2PA P 2047 Version with local electric control...

Page 65: ...STR 1PA STR 2PA 63 6 12 Commercial representation Slovak Republic Regada s r o Strojn cka 7 080 01 Pre ov Tel 421 0 51 7480 460 Fax 421 0 51 7732 096 E mail regada regada sk...

Reviews: