38
STR 1PA, STR 2PA
Table 4
setting error flags and warning flags as at the delivery
PARAMETER
ERROR
WARNING
ESD
X
Analog Input – not valid for Modbus/Profibus protocol
X
Modbus/Profibus activity – only for Modbus/Profibus protocol
X
Wrong command
X
Torque
X
Torque check
X
Torque calibration
X
Regulator calibration
X
Stroke (turns sum)
X
Wrong position
X
Spin
X
Spin direction
X
RAM
X
ROM
X
EEPROM
X
Bus
X
I2C
X
Reset
X
V5V
X
Parameters
X
Set mode
X
Relay
X
Temperature <
X
Temperature >
X
Phase
X
Power frequency
X
Thermal fuse
X
Manual control
X
Position module
X
Position module type
X
Position sensor 1
X
Position sensor 2
X
Position sensor 3
X
Position sensor 4
X
Torque module
X
Torque module type
X
Torque sensor
X
LED module
X
LED module type
X
LCD module
X
LCD module type
X
Power Supply/Relay module
X
Power Supply/Relay module type
X
E2P
X
Profibus Channel 1- only for version with Profibus
X
Profibus Channel 2- only for version with Profibus
X
Notes:
X
– the error or warning flag is activated.
With the
error flag
, the EA takes the positron defined for the FAILURE REACTION function eventually
stops (depending on the kind of the error), and it will not operate until the error is removed.
With the
warning flag
, the EA continues in operation.
The user is advised on error or warning through the READY relay (according to the relay setting), by
LED ERROR blinking on Control unit, by ERROR message on LED or LCD display, eventually through
the program after connecting the EA with a PC
Note 1
: In some cases having the error removed the electric actuator must be restarted by switching-
off the voltage supply to the electric actuator for about 3 sec.
If some EA element would fail it can be replaced with a new one. The
producer’s service centre
only
is allowed for such replacement.
Summary of Contents for Rematic STR 1PA
Page 10: ...8 STR 1PA STR 2PA Fig 1 1 5 2 4 3 8 7 6...
Page 11: ...STR 1PA STR 2PA 9 Fig 1A 4 8 2 7 6 1 5...
Page 43: ...STR 1PA STR 2PA 41 6 2 Wiring diagrams ES STR 1PA for three phase supply...
Page 44: ...42 STR 1PA STR 2PA 6 3 Wiring diagrams ES STR 2PA for three phase supply...
Page 45: ...STR 1PA STR 2PA 43 6 4 Wiring diagrams ES STR PA for three phase supply without reverse unit...
Page 47: ...STR 1PA STR 2PA 45...
Page 54: ...52 STR 1PA STR 2PA 6 10 Dimensional drawings STR 1PA P 1169 Flange DIN 3358...
Page 55: ...STR 1PA STR 2PA 53 P 1170 Pillars...
Page 56: ...54 STR 1PA STR 2PA...
Page 57: ...STR 1PA STR 2PA 55 P 2046 EA with local control...
Page 58: ...56 STR 1PA STR 2PA 6 11 Dimensional drawings STR 2PA...
Page 59: ...STR 1PA STR 2PA 57...
Page 61: ...STR 1PA STR 2PA 59...
Page 62: ...60 STR 1PA STR 2PA...
Page 63: ...STR 1PA STR 2PA 61...
Page 64: ...62 STR 1PA STR 2PA P 2047 Version with local electric control...