Regada MP 52 200 Installation, Service And Maintenance Instructions Download Page 16

14  

 

MP 52 200

 

· 

Turn  the  adjusting  trimmer  ZERO  (Fig.  7)  to  adjust 
the  output  current  signal  rate  measured  on  the 
terminals 81-82 to  0 mA or 4mA. 

· 

Set the actuator to the position „open“. 

· 

Turn  the  adjusting  trimmer  GAIN  (Fig.  7)  to  adjust 
the  output  current  signal  rate  measured  on  the 
terminals 81-82 to  20mA or 5 mA.. 

· 

Check the output signal of the converter in the both 
limit positions, and repeat the procedure if needed.  

 

   

 

 

 

 

 

 

 

 

Fig.7 

Note: 
The output signal of (0-20mA, 4-20mA or 0-5mA - according to the specification) can be adjusted at the range 
from 85 up to 100% of the rated stroke stated on the actuator

¢

s nameplate. At values less than 85% the value  of 

the output signal is reduced proportionally.

 

 

Electric  local  control:

  -  additional 

equipment 

 In  case  of  need  (during  adjusting, 

function  checking  etc.),  but  power  supply 
must  be  provided,  is  possible  to  readjust 
actuator  by  electric  local  control.  After 
switching  the  mode  switch  to  the  mode 
“LOCAL”  it  is  possible  by  the  direction 
switch to control motion of the output part to 
setting  direction.  Signal  lights  indicate 
achievement  of  limit  position  at  relevant 
direction. 

From terminal 83 of terminal board 

parent  control  system  must  be  power-
supplied.  In  opposite  case  it  is  not 
guaranteed disconnection of remote control 
after switching the mode switch to the mode 
“LOCAL”. 

 
 
 

   

 

 

 

 

 

 

 

Fig. 10 

 

4.  Service, maintenance and troubleshooting 

4.1  Service 

1. In general it is provided that service of the EA is performed by a qualified worker in accordance with 
requirement given in Chapter 1! 
2. After putting the EA into operation it is needed to verify whether during manipulation any scratch on 
surface occurred, it is to be removed to prevent actuator against corrosion! 

 

 

The EA SP/SPR requires just negligible service. Proper putting into operation is a recondition of 

reliable operation. 
 

The  service  of  the  EA  leads  from  the  operation  conditions  and  usually  resides  in  information 

processing for further arranging of required functions. 
 

The  stuff  has  to  perform  prescribed  maintenance  to  prevent  the  EA  during  operation  against 

impacts of environment,  which exceed the frame of allowed influences. 
 

4.2  Maintenance - extent and periodicity 

 

During inspections and maintenance it is needed to tighten all screws and nuts which influence 

tightness and protection enclosure. 
 

Another  maintenance  resides  in  greasing.  Changing  or  filling  grease  up  during  first  years 

operation  is  not  required.  To  refill  or  to  replenish  the  grease  is  needed  during  revisions.  Intervals 
between two prevention inspections are four years. 

!

Summary of Contents for MP 52 200

Page 1: ...74 0767 02 Electric part turn actuators MP 52 200 INSTALLATION SERVICE AND MAINTENANCE INSTRUCTIONS...

Page 2: ...ng diagram Operation time s 90 Operation angle Transmitter potentiometer Serial number of electric motor Serial number of transmitter Serial number of position controller Tests made in accordance with...

Page 3: ...7 Specifications 8 1 8 Packaging Transport Storing and Unpacking 10 1 9 Liquidation of the Product and the Package 11 2 Installation and Dismantling of the Actuator 11 2 2 Dismantling 12 3 Adjusting...

Page 4: ...Operation Conditions and regarding its exposure rate is designated as a device with high exposure rate group A when it is an electric device of the group A see Regulation of MPSvR Ministry of Work and...

Page 5: ...y service is provided by the service department of the producer on the basis of a written claim While claiming it is advised to present the following basic data from the nameplate type and serial numb...

Page 6: ...llution AF 2 with a possibility of influences of mechanical stress medium sinusoid vibrations with frequency in range 10 up to 150 Hz with shift amplitude of 0 15 mm for f fp and acceleration amplitud...

Page 7: ...ule M3 a gearbox with a manual control mechanism The gear train is located in the case 1 The gears are placed on the output shaft 3 and they make up an independent assembly set The rim 44 with interna...

Page 8: ...o the control board place into the control box a transmission unit of the control board a position an indication unit a torque unit a transmitter block space heater local position indicator electric c...

Page 9: ...ig 5 Position unit 11 After loosen a nut of the position unit 51 is possible to rotate 53 54 56 57 The construction of position unit is designed so that transforming one of the cams it does not distur...

Page 10: ...ends 29 The flange 27 is screwed onto the actuator box 1 penetrated With a shaft and on its free end the lever is mounted Fig 8 1 7 Specifications Basic Specifications are given in the table 1 1 7 1...

Page 11: ...lue Adjustment of the capacitive transmitter the position open 20 mA the position close 0 4 mA Weight 27 up to 29 kg Lubrication grease HF 401 0 GLEITM m Gearbox oil PP 80 1 7 2 Mechanical Connection...

Page 12: ...or message LED SYS mode error message LED Adjusters communication connector 2x calibrating and adjusting button Local position indication with position indicator visible through aperture in upper cove...

Page 13: ...gle parts of the package and the product should not be thrown away after its lifetime but sorted according to the related regulations and rules about environment protection and delivered for next trea...

Page 14: ...rection open Press the lever 42 in the direction to the output shaft what switches contacts 20 MO S1 and the actuator should stop Press the button SB1 closed on the control board The output shaft shou...

Page 15: ...Y Fig 6 The used transmitter resistance is 100 W Switch the converter s power supply on Turn the adjusting trimmer ZERO Fig 6 to adjust the output current signal rate measured on the terminals 81 82 t...

Page 16: ...ust be power supplied In opposite case it is not guaranteed disconnection of remote control after switching the mode switch to the mode LOCAL Fig 10 4 Service maintenance and troubleshooting 4 1 Servi...

Page 17: ...upply the EA stops in the position where it was before the failure If needed the EA can be set only with the manual control the handwheel After restoration of power the EA is prepared for operation In...

Page 18: ...16 MP 52 200 4 4 Wiring diagrams...

Page 19: ...er 2 wire with power supply Z295 connection of 1 phase electric motor Z298 connection of torque and position switches and space heater Z299 connection of torque and position switches and space heater...

Page 20: ...18 MP 52 200 4 5 Dimensional drawings...

Page 21: ...MP 52 200 19...

Page 22: ...20 MP 52 200...

Reviews: