8
MP 52 200
Torque switch unit
consists of the following parts:
Switch element (9) (Fig 3) is formed by two micro-
switches S1(20) and S2(21). It is put into operation after
loosening of the nut (18)(Fig.3).
Cam unit (26)(Fig.3) is formed by two adjustable cams
(19) and (22)(Fig.7) placed on the shaft of the torque control
element (45)(Fig.2). The cams are turned according to the
set switch-off force.
The space heater
The actuator is equipped with two parallel space heaters(16)(Fig.3,5) With total power output
20W. Connection of the space heater is conditional by operation environment.
Electric connection
can be made through the terminal board (82)(Fig.1) or through the connector.
Module M6 – lever mechanism
The lever mechanism is made up with the flange with a groove (27), where a slider with a screw
(28) carries the stop ends (29). The flange (27) is screwed onto the actuator box (1) penetrated With
a shaft and on its free end the lever is mounted.
Fig.8
1.7 Specifications
Basic Specifications are given in the table 1.
1.7.1 Basic Specifications
Table 1:
Electric motor
Type/
type
number
Operating time
±
10[%]
O
pe
ra
ting
angle
±
1°
Switching-off
torque
5)6)
±
15 [%]
W
eihgt
Supply voltage.
Power output
Speed
Current
[s/90°]
[
°]
[Nm]
[kg]
[V]
±
10%
[W]
[1/min]
[A]
1
2
3
6
7
8
9
10
11
12
60
20
1350
0,4
32
16
MP
T
ype
N
o.
52
200
8
60
÷
160
63
¸
125
cc
a
25a
ž
27
S
ing
le
-pha
se
230
60
2750
0,7
5)
State the switching-off torque in your order by words. If not stated it is adjusted to the maximum rate of the corresponding
range. The switching-off torque is not adjusted by customer. The load torque equals minimally the max. switching-off torque
of the choosing range multiplied by 1,3.
6)
The maximum load torque equals the max.switching-off torque multiplied by:
·
0,8 for duty cycle S2-10min, or S4-25%, 6-90 cycles per hour
·
0,6 for duty cycle S4-25%, 90-1200 cycles per hour
Fig. 7
Summary of Contents for MP 52 200
Page 18: ...16 MP 52 200 4 4 Wiring diagrams...
Page 20: ...18 MP 52 200 4 5 Dimensional drawings...
Page 21: ...MP 52 200 19...
Page 22: ...20 MP 52 200...