MO 3.3, MO 3.4, MO 3.5
13
b) 3-wires connection
(without built-in power supply, resp. with built-in power supply)
Electric current signal ................................................................................................ 0 ÷ 20 mA (DC)
Electric current signal................................................................................................. 4 ÷ 20 mA (DC)
Electric current signal................................................................................................... 0 ÷ 5 mA (DC)
Supply voltage (for make without built-in power source ............................................................24 V DC
Load resistance..................................................................................................................... max. 3 k
W
The values of output signal in terminal positions:
“O“ ... 20 mA, resp. 5 mA (terminals 81; 82)
“Z“ ..... 0 mA, resp. 4 mA (terminals 81; 82)
Tolerance of electronic transmitter output signal value
“Z“ ........... +0, 2 mA
“O“ ..........
±
0, 1 mA
Linearity deflection of electronic and capacitive transmitter of the position ............................
±
1, 5[%]
1)
Hysteresis of electronic and capacitive position of the transmitter ................................. max. 1, 5 [%]
1)
1) of transmitter nominal value related to output values
Weight:
38 kg ± 5 % for MO 3.3,
42 kg ± 5 % for MO 3.4,
49 kg ± 5 % for MO 3.5
Lubrication:
·
Gearbox oil for temperatures: –25°C up to +55°C Madit PP-80 (Slovnaft)
-40°C up to +40°C GYROL 75W (Paramo)
·
Lubrication grease for additional gearbox GLEIT-
μ
HF 401/0
2.2.1 Mechanical connection
·
By flange F16 resp. F 14 (ISO 5210, DIN 3338)
·
By flange
f
220 resp.
f
135 (OST 26-07-763)
Main and connecting dimensions are presented in
dimensional drawings
.
2.2.2 Electric connection
a) of electric actuator
to terminal board (X)
(max. 32 terminals – the crosscut of connecting wire max. 2, 5 mm
2
)
:
through 2 cable bushings – M25x1, 5 - cable diameter from 11 up to 17 mm
to connector (XC)
(max. 32 poles - the crosscut of connecting wire 0, 5 mm
2
)
:
through two cable bushings - P 21/18 - cable diameter from 13 up to 18 mm
b) 3~ electric-motor
in a terminal board make:
................................. through bushing M25 to the motor terminal board
in connector make:
........ to common connector
Protective terminal
Outer and inner, they are mutually interconnected and marked by a sign of protective grounding.
Electric connection is performed according to
connection drawings
.