Controller
Servimat M/L — 28.01.2021
English
—
19
PM code Description
029
•
Maximum make-up quantity ... l
030
•
Softening "Yes/'No"
–
If "Yes", continue with 031
–
If "No", continue with 007
007
Maintenance interval…
months
008
Floating contact
•
Message selection >
•
Message selection: only messages marked with "√“ are
output.
•
All messages: All messages are output.
015
Change remote data "Yes/No”
Fault memory > History of all messages
Parameter memory > History of parameter input
Display settings > Brightness, screen saver
009
•
Brightness …
%
010
•
Screen saver brightness …
%
011
•
Screen saver delay …min
018
•
Secure access "Yes/No"
Information >
•
Tank
•
Volume
•
Weight
•
Diameter
Position motorized ball valve 1
•
Software version
9.3.1.2
Setting the customer menu - "Time" example
The setting of system-specific values is explained below using the setting of the
time as example.
To adjust the system-specific values, proceed as follows:
1.
Press "Settings“.
–
The controller switches to the setting area.
2.
Press "Customer >".
–
The controller opens the Customer menu.
3.
Press the required area.
–
The controller switches to the selected area.
–
Use the scroll bar to navigate through the list.
4.
Set the system-specific values for the individual areas.
–
Use the "Left" and "Right" buttons to select the display value.
–
Use the "Up" and "Down" buttons to change the display value.
–
Confirm your entries with "OK".
Press "i“ to display a help text for the selected area.
Press "X“ to cancel your input w
ithout saving the new settings. The
controller automatically opens again the list.
9.3.2
Service menu
This menu is protected with a password. It can be accessed only by the Reflex
Customer Service. A partial summary of the settings stored in the Service menu is
proved in the Chapter Default settings, see chapter 9.3.3 "Default settings" on
page 19 .
9.3.3
Default settings
The device controller is shipped with the following default settings. Use the
Customer menu to adjust these values to local conditions. In specific cases, it is
possible to further adjust the values in the Service menu.
Customer menu
Parameter
Setting
Remarks
Language
EN
Display language
Minimum operating
pressure P
0
1.5 bar
Only Magcontrol
Safety valve, pressure
3.0 bar
Pressure value for the safety
valve of the heat generator in the
system to trip
Next maintenance
12 months
Time left to the next due
maintenance
Volt-free contact
YES
All messages from the Messages
list are displayed
Make-up
Maximum make-up
quantity
0 Litres
Only if controller with "With
water meter yes"
Maximum make-up time 20 minutes
Magcontrol
Maximum make-up
cycles
3 cycles within 2
hours
Magcontrol
Degassing
Degassing programme
Continuous
degassing
Continuous degassing
time
24 hours
Softening (Only if "With
softening yes")
Lock make-up
No
In the case of soft water residual
capacity = 0
Hardness reduction
8°dH
= Target
–
Actual
Maximum make-up
quantity
0 Litres
Attainable make-up quantity
Soft water capacity
0 Litres
Attainable water capacity
Cartridge replacement
18 months
Replace cartridge