Reflex Reflexomat Basic RS 90 / 1 Operating Manual Download Page 8

Installation 

 

 

 

8 —  English  

Reflexomat Basic — 20.09.2020 - Rev. A 

 

 

 

6.3.5

 

Fitting the level sensor 

ATTENTION 

 

Damage to the pressure load cell due to unprofessional installation 
Incorrect installation may result in damage to the "LIS" level sensor, 
malfunctioning and incorrect measurements from the pressure load cell. 
• 

Comply with the instructions regarding the installation of the pressure 
load cell. 

 
The "LIS" level sensor uses a pressure load cell. This pressure pick-up is to be 
installed after the primary vessel has been placed at its final position, see 
chapter 6.3.2 "Tank installation" on page 6 . Comply with the following 
instructions: 
• 

Remove the transport securing device (squared timber) at the vessel base 
of the primary vessel. 

• 

Replace this transport securing device with the pressure load cell. 

• 

Avoid shock-type loading of the pressure load cell by, for example, 
subsequent alignment of the vessel. 

• 

Use flexible hoses to connect the primary vessel and the first secondary 
vessel. 
–  

Use only the supplied connection sets, see chapter 6.3.2 "Tank 
installation"
 on page 6 . 

• 

Perform a null balancing of the filling level when the primary vessel is 
aligned and fully emptied, see chapter 9.2 "Configuring settings in the 
controller"
 on page 12 . 

 
Standard values for level measurements: 

 

Primary vessel 

Measuring range 

200 l 

0 – 4 bar 

300 – 500 l 

0 – 10 bar 

600 l 

0 – 25 bar 

 

6.4

 

Make-up and degassing variants 

6.4.1

 

Function 

The filling level is recorded in the primary tank by the "LIS" level sensor and 
evaluated in the controller. When the water level falls below the value specified 
in the controller's customer menu, the external make-up is activated. 
 
6.4.1.1

 

Make-up without pump 

Reflexomat Basic with solenoid valve and ball valve. 

 

 

 

Reflexomat Basic 

  WC 

Make-up pipe 

Solenoid valve "Fillvalve" with ball 
valve 

  LIS 

Level sensor 

Reflex Fillset 

  EC 

Expansion pipe 

ST  Dirt trap 

   

 

 

Preferably, you should use the Reflex Fillset with integrated system separator 
when using drinking water for make-up. If you don't use a Reflex Fillset, you 

must use an "ST" dirt trap with a mesh size ≥

 0.25 mm for the make-up. 

 

6.4.1.2

 

Make-up with pump 

Reflexomat Basic with Reflex Fillcontrol Auto 

 

 

 

Reflexomat Basic 

 

ST  Dirt trap 

Fillcontrol Auto 

 

EC  Expansion pipe 

WC  Make-up pipe 

 

LI

Level sensor 

 

Water make-up with Fillcontrol Auto is suitable for make-up at high system 
pressures of up to 8.5 bar. The "ST" dirt trap is part of the deliverables. 
 
6.4.1.3

 

Make-up with softening and degassing 

Reflexomat Basic and Reflex Servitec. 

 

 

 

Reflexomat Basic 

 

ST 

Dirt trap 

Reflex Servitec 

 

WC  Make-up pipe 

Reflex Fillsoft 

 

LIS  Level sensor 

Reflex Fillset Impulse 

 

EC  Expansion pipe 

 

The Reflex Servitec degassing and make-up station degasses the water from the 
system circuit and the make-up water. The automatic water make-up for the 
system circuit is controlled by the pressurisation system. Reflex Fillsoft 
additionally softens the make-up water. 
• 

Reflex Servitec degassing and make-up station, see chapter 4.6 "Optional 
equipment and accessories"
 on page 5 . 

• 

Reflex Fillsoft softening systems and Reflex Fillset Impulse, see chapter 4.6 
"Optional equipment and accessories"
 on page 5 . 

 

 

Note! 
When using Reflex Fillsoft softening systems, always install the Reflex 
Fillset Impulse. 
–  

The controller evaluates the make-up quantities and signals a 
required replacement of the softening cartridges. 

 

Summary of Contents for Reflexomat Basic RS 90 / 1

Page 1: ...20 09 2020 Rev A Reflexomat Basic GB Operating manual Original operating manual Reflexomat RS 90 1 mounted Reflexomat external air...

Page 2: ...5 Fitting the level sensor 8 6 4 Make up and degassing variants 8 6 4 1 Function 8 6 5 Electrical connection 9 6 5 1 Terminal diagram 9 6 5 2 RS 485 interface 9 6 6 Installation and commissioning cert...

Page 3: ...observe the safety information can result in death or severe irreversible injuries CAUTION Damage to health The sign in combination with the signal word Caution indicates danger failure to observe th...

Page 4: ...or SV Safety valve PV Solenoid valve LIS Pressure load cell EC Expansion pipe Expansion vessels One primary vessel and multiple optional secondary vessels may be connected A membrane separates the ves...

Page 5: ...otection IP 54 Noise level 72 dB Electric output 750 W Power supply 230 V 50 Hz Fusing 3 A Electrical voltage control unit 230 V 2 A Number of RS 485 interfaces 1 Weight 21 kg Permissible operating te...

Page 6: ...eing stressed or strained If necessary provide support structures for the pipes or equipment For installation proceed as follows Position the device Complete the primary tank and the optional secondar...

Page 7: ...cables are factory installed on the primary vessel The cables between the primary vessel and the control unit are pre installed Subsequently install the level sensor at the primary vessel see chapter...

Page 8: ...ontroller s customer menu the external make up is activated 6 4 1 1 Make up without pump Reflexomat Basic with solenoid valve and ball valve 1 Reflexomat Basic WC Make up pipe 2 Solenoid valve Fillval...

Page 9: ...ke up request Not used with the Reflexomat 17 Make up 230 V 18 Make up 230 V 19 PE shield Level analogue input Display at the controller Activation of the make up Factory prepared sensor plug must be...

Page 10: ...n in extreme cases Note Avoid dropping below the P0 minimum operating pressure Vacuum vaporisation and cavitation are thus excluded 7 3 Modifying the controller s start routine Note During commissioni...

Page 11: ...e up pressure at least 1 3 bar above the set minimum pressure P0 Without automatic make up Use the discharge ports or the facility system to manually fill the individual tank to approximately 30 of th...

Page 12: ...ey marked menu items must be reviewed during commissioning Press Manual to switch to manual operation Press Menu to display the first main menu option Customer menu Indication on the display Meaning C...

Page 13: ...oftening used and the specified hardness reduction Fillsoft I soft water capacity 6000 hardness red l Fillsoft II soft water capacity 12000 hardness red l Enter the value in the controller Consult the...

Page 14: ...ed Note Floating contacts setting in the Customer menu see chapter 9 2 Configuring settings in the controller on page 12 ER Code Alarm Floating contact Causes Remedy Alarm reset 01 Minimum pressure YE...

Page 15: ...een option card and controller faulty Option card defective Inform Reflex Customer Service 31 EEPROM defective YES EEPROM defective Internal calculation error Inform Reflex Customer Service Quit 32 Un...

Page 16: ...ended closing Checking Insufficient water Off 14 Check the displayed value for the Insufficient water OFF filling level message Insufficient water Off is displayed at the controller at a minimum filli...

Page 17: ...ified by the operating company based on a safety evaluation taking into consideration the actual operating conditions experience with the mode of operation and charging material and the applicable nat...

Page 18: ...Installation and commissioning certificate This device has been installed and commissioned in accordance with the instructions provided in the operating manual The settings in the controller match th...

Page 19: ...SI2041enA 11 20 Reflex Winkelmann GmbH Gersteinstra e 19 59227 Ahlen Germany 49 0 2382 7069 0 49 0 2382 7069 9546 www reflex winkelmann com...

Reviews: