Reflex Reflexomat Basic RS 90 / 1 Operating Manual Download Page 13

 

Controller 

 

 

 

Reflexomat Basic — 20.09.2020 - Rev. A 

 

English  — 13 

 

Indication on the 
display 

Meaning 

Make-up: OFF 
at: 12 % 

Terminate the water make-up when the specified vessel 
size is exceeded. 
• 

If an automatic make-up device is installed, make-
up will be shut off automatically; otherwise the 
make-up must be manually deactivated. 

• 

If you have selected "No" for automatic make-up, 
the system will not return any further queries 
about the make-up. 

Max. make-up time 
010 min. 

Pre-selected time for a make-up cycle. Upon expiry of 
this set time, the system interrupts the make-up and 
returns the "Make-up time" fault message. 

Max. make-up 
cycles 
003 / 2 h 

If the set number of make-up cycles is exceeded within 
two hours, the system interrupts the make-up and 
returns the "Make-up cycles" fault message. 

With water meter. 
YES 

• 

YES: FQIRA+ contact water meter is installed, see 
chapter 4.6 "Optional equipment and accessories" 
on page 5 .  
This is the prerequisite for the make-up volume 
monitoring and the operation of a softening 
system. 

• 

NO: A contact water meter is not installed 
(standard model). 

Make-up volume 
000020 l 

Only displayed if "YES" has been set in the "With water 
meter" menu option. 
• 

Use "OK" to delete the counter. 
–  

Press "YES" to reset the value displayed to 
"0". 

–  

Press "NO" to retain the displayed value. 

Max. make-up 
volume 
000100 l 

This value is only displayed if "YES" has been set in the 
"With water meter" menu option. 
• 

When the set volume is exceeded, the system 
interrupts the make-up process and returns the 
error message "Max. make-up volume exceeded". 

With softening 
YES 

This value is only displayed if "YES" has been set in the 
"With water meter" menu option. 
• 

YES: Further queries follow about softening. 

• 

NO: The system does not offer more queries 
regarding the softening process. 

Disable make-up? 
YES 

This value is only displayed if "YES" has been set in the 
"With softening" menu option. 
• 

YES: The system stops the make-up process when 
the set soft water capacity is exceeded. 

• 

NO: The system does not stop the make-up 
process. The system displays the "Softening" 
message. 

Hardness reduction 
10 °dH 

This value is only displayed if "YES" has been set in the 
"With softening" menu option. 
• 

 Hardness reduction is calculated from the 
difference of the overall water hardness GH

actual

 

and the target water hardness GH

target

Hardness reduction = GH

actual

-GH

target

l °dH 

Enter the value in the controller. Consult the 
manufacturer information for third-party products. 

Cap. soft water 
05000 l 

This value is only displayed if "YES" has been set in the 
"With softening" menu option. 
The attainable soft water capacity is calculated from the 
type of softening used and the specified hardness 
reduction. 
• 

Fillsoft I, soft water capacity ≤ 6000/hardness red. l

 

• 

Fillsoft II, soft water capacity ≤ 12000/hardness 

red. l 

Enter the value in the controller. Consult the 
manufacturer information for the values of third-party 
products. 

Remaining cap. soft 
w. 
000020 l 

This value is only displayed if "YES" has been set in the 
"With softening" menu option. 
• 

Available soft water capacity. 

Indication on the 
display 

Meaning 

Replacement 
18 months 

This value is only displayed if "YES" has been set in the 
"With softening" menu option. 
• 

Manufacturer specification for the replacement 
interval of the softening cartridges, regardless of 
the calculated soft water capacity. The system 
displays the "Softening" message. 

Next maintenance 
012 months 

Recommended maintenance messages. 
• 

Off: Without maintenance recommendation. 

• 

001 – 060: Maintenance recommendation in 
months. 

Floating fault 
contact 
YES 

For the output of messages to the floating contact, see 
chapter 9.2.2 "Messages" on page 14 . 
• 

YES: Output of all messages. 

• 

NO: Output of all messages identified with 

"xxx"

 

("01", for example). 

Fault memory

˃

 

Switch to the "Fault memory" sub-menu. 
• 

Press "OK" to open the menu. 

• 

Use the "

▼▲

" buttons to open the sub-menu. 

ER 01…xx 

The last 20 alarms are stored with fault type, date, time, 
and fault code. 
See the chapter "Messages" for more information about 
the ER... messages. 

Parameter 
memory

˃

 

Switch to the "Parameter memory" sub-menu. 
• 

Press "OK" to open the menu. 

• 

Use the "

▼▲

" buttons to open the sub-menu. 

P0 = xx.x bar 
Date | Time 

The last 10 entries of the minimum working pressure are 
stored with date and time. 

Vessel info 
00600 l 

The system displays the values for the volume and the 
diameter of the "RG" primary vessel. 
• 

If you identify differences to the information 
provided on the primary vessel's nameplate, please 
contact the Reflex Customer Service. 

Reflexomat 
V1.00 

Information about the software version 

 

9.2.1

 

Default settings 

The device controller is shipped with the following default settings. Use the 
Customer menu to adjust these values to local conditions. In specific cases, it is 
possible to further adjust the values in the Service menu. 
 
Customer menu 

Parameter 

Setting 

Comment 

Language 

DE  

Display language. 

Minimum operating 
pressure "P

0

1.8 bar 

see chapter 7.2 "Reflexomat 
switching points"
 on page 10 . 

Next maintenance 

12 months 

Time left to the next due 
maintenance. 

Volt-free contact 

YES 

see chapter 9.2.2 "Messages" on 
page 14 . 

Make-up 

 

 

Make-up "ON" 

8 % 

 

Make-up "OFF" 

12 % 

 

Maximum make-up 
volume 

0 Litres 

Only if make-up has been 
selected in the customer menu 
with "With water meter Yes". 

Maximum make-up time   30 minutes 

 

Maximum make-up cycles  6 cycles within 

2 hours  

 

Softening (Only if "With 
softening Yes") 

 

 

Shut off make-up 

No 

In the case of soft water residual 
capacity = 0 

Hardness reduction  

8°dH  

= Target – Actual 

Summary of Contents for Reflexomat Basic RS 90 / 1

Page 1: ...20 09 2020 Rev A Reflexomat Basic GB Operating manual Original operating manual Reflexomat RS 90 1 mounted Reflexomat external air...

Page 2: ...5 Fitting the level sensor 8 6 4 Make up and degassing variants 8 6 4 1 Function 8 6 5 Electrical connection 9 6 5 1 Terminal diagram 9 6 5 2 RS 485 interface 9 6 6 Installation and commissioning cert...

Page 3: ...observe the safety information can result in death or severe irreversible injuries CAUTION Damage to health The sign in combination with the signal word Caution indicates danger failure to observe th...

Page 4: ...or SV Safety valve PV Solenoid valve LIS Pressure load cell EC Expansion pipe Expansion vessels One primary vessel and multiple optional secondary vessels may be connected A membrane separates the ves...

Page 5: ...otection IP 54 Noise level 72 dB Electric output 750 W Power supply 230 V 50 Hz Fusing 3 A Electrical voltage control unit 230 V 2 A Number of RS 485 interfaces 1 Weight 21 kg Permissible operating te...

Page 6: ...eing stressed or strained If necessary provide support structures for the pipes or equipment For installation proceed as follows Position the device Complete the primary tank and the optional secondar...

Page 7: ...cables are factory installed on the primary vessel The cables between the primary vessel and the control unit are pre installed Subsequently install the level sensor at the primary vessel see chapter...

Page 8: ...ontroller s customer menu the external make up is activated 6 4 1 1 Make up without pump Reflexomat Basic with solenoid valve and ball valve 1 Reflexomat Basic WC Make up pipe 2 Solenoid valve Fillval...

Page 9: ...ke up request Not used with the Reflexomat 17 Make up 230 V 18 Make up 230 V 19 PE shield Level analogue input Display at the controller Activation of the make up Factory prepared sensor plug must be...

Page 10: ...n in extreme cases Note Avoid dropping below the P0 minimum operating pressure Vacuum vaporisation and cavitation are thus excluded 7 3 Modifying the controller s start routine Note During commissioni...

Page 11: ...e up pressure at least 1 3 bar above the set minimum pressure P0 Without automatic make up Use the discharge ports or the facility system to manually fill the individual tank to approximately 30 of th...

Page 12: ...ey marked menu items must be reviewed during commissioning Press Manual to switch to manual operation Press Menu to display the first main menu option Customer menu Indication on the display Meaning C...

Page 13: ...oftening used and the specified hardness reduction Fillsoft I soft water capacity 6000 hardness red l Fillsoft II soft water capacity 12000 hardness red l Enter the value in the controller Consult the...

Page 14: ...ed Note Floating contacts setting in the Customer menu see chapter 9 2 Configuring settings in the controller on page 12 ER Code Alarm Floating contact Causes Remedy Alarm reset 01 Minimum pressure YE...

Page 15: ...een option card and controller faulty Option card defective Inform Reflex Customer Service 31 EEPROM defective YES EEPROM defective Internal calculation error Inform Reflex Customer Service Quit 32 Un...

Page 16: ...ended closing Checking Insufficient water Off 14 Check the displayed value for the Insufficient water OFF filling level message Insufficient water Off is displayed at the controller at a minimum filli...

Page 17: ...ified by the operating company based on a safety evaluation taking into consideration the actual operating conditions experience with the mode of operation and charging material and the applicable nat...

Page 18: ...Installation and commissioning certificate This device has been installed and commissioned in accordance with the instructions provided in the operating manual The settings in the controller match th...

Page 19: ...SI2041enA 11 20 Reflex Winkelmann GmbH Gersteinstra e 19 59227 Ahlen Germany 49 0 2382 7069 0 49 0 2382 7069 9546 www reflex winkelmann com...