Instruction Manual DIGIMON-SE / DIGIMON4
English
13
Filling the system
a) with DIGIMON-SE manifold
Disconnect the yellow hose from the vacuum pump and screw it onto the
refrigerant bottle or cylinder.
Open the valve on the refrigerant bottle or cylinder.
Open the blue valve (5) (low pressure side) and let the required amount of
refrigerant to flow in. If the required amount of refrigerant does not flow into the
system, the compressor must be switched on.
After the system has been filled with the desired amount, close the valve on the
refrigerant bottle or cylinder.
Close the blue valve (5).
Check the system's pressure and temperature!
Remove the hoses from the system.
Open valves (5+6).
b) with DIGIMON4 manifold
Disconnect the yellow hose (3/8“) from the vacuum pump and the DIGIMON4
(3) and screw the caps onto the 3/8“ SAE thread.
Open the black valve (8).
Open the valve on the refrigerant bottle or cylinder. Then open the blue valve (5)
and allow the required amount of refrigerant to flow in. If the required amount of
refrigerant does not flow into the system, the compressor must be switched on.
After the system has been filled with the desired amount, close the black valve
(8).
Close the valve on the refrigerant bottle or cylinder.
Open the red valve (6). Check the pressure and temperature on the high and
low pressure sides of the system! If all pressures are in order, close all valves.
Remove the hoses from the system.
Open all valves.