English                                                    Instruction Manual DIGIMON-SE / DIGIMON4 

18 

Calibrating the K-Type sensors (using room temperature)

 

1.  Switch off the DIGIMON 

2.  Plug in the thermocouples (K-type).  

Room and measurement temperatures must remain constant at 25 +/-3°C and 

be stable for at least 20 minutes. The thermocouple cables must be straight 

(unwound). 

During calibration, you should neither touch the cables nor the plugs. 

3.  While holding down the  

 button continuously, switch on the device by 

pressing the 

 button once. Continue holding down the Light button until the 

display shows,  "Password"  

000

 

4.  Press the  

 / 

 

 buttons to scroll to code

 018

5.  Press the  

 button once. 

  Display shows  

“T-call”

 

6.  Press the  

 button once and then the 

 button once to enter 

temperature sensor/clamp calibration mode. 

7.  During calibration, ensure that both thermocouples are well connected to the 

DIGIMON.  

  The display shows   

  (low pressure side) 

 

 

 

 

 

 

 

The current temperature displayed on the DIGIMON should not deviate by 

more than +/-0.5°C  from the room temperature. 

8.  Press the  

 button to confirm. 

  The display shows: 

 

 

 

 

 

 

SET 

SET 

R

 -

 

SET 

R

 -

 

R

 +

 

ON/OFF 

LIGHT 

LP 
00xxx 
27.0°C 

Temperature code 

Current temperature 

LP 
End 
00xxx 
27.0°C 

Summary of Contents for DIGIMON-SE

Page 1: ...DIGIMON SE DIGIMON4 Installation and operating guide Digital Manifold...

Page 2: ...anchor SAE 2 High pressure anchor SAE 3 Vacuum anchor SAE or 3 8 4 Refrigerants anchor SAE 5 Low pressure valve blue 6 High pressure valve red 7 Vacuum valve yellow 8 Refrigerants valve black 9 2 ext...

Page 3: ...icator 6 Application 7 Connecting the manifold 12 Evacuating the system 12 Filling the system 13 Measuring using the Superheat Subcool modes 14 Maintenance work on the manifold 14 Guarantee 14 Environ...

Page 4: ...6MPa Under no circumstances should the manifold be used as a pressure regulator especially not when using nitrogen N2 The manifold must not be used with the refrigerant ammonia NH3 R717 The manifold s...

Page 5: ...o the central T piece when not in use This serves to protect the thread from contamination and damage Technical description The DIGIMON can be used with the following refrigerants R11 R113 R114 R12 R1...

Page 6: ...olution 0 1 C 0 1 F Optional clamp thermocouple K type Temperature range 40 C to 125 C 40 F to 257 F For pipe diameters of 6mm to 38mm to 1 Plug K type Accuracy of measurement 1 K Resolution 0 1 C 0 1...

Page 7: ...pressure display function Switch vacuum display function Switch LCD light on off switches off automatically after 1 minute Select refrigerant search forwards select pressure unit Select refrigerant s...

Page 8: ...cator Illuminating the display Press the button to switch the display light on or off The light switches off automatically after 1 minute Automatic shut off The DIGIMON switches off automatically appr...

Page 9: ...to select the desired refrigerant from the list During selection you will see a flashing R on the display Press the button to confirm selection of the desired refrigerant The R no longer flashes on th...

Page 10: ...ice will save the last pressure and temperature units selected Memory function of the analogue pressure display Save value current measurement value press the and buttons at the same time Retrieve mem...

Page 11: ...e vacuum display Vacuum display values When evacuating the device a maximum of 10 bars will be displayed When the display remains stable the ultimate vacuum has been reached and the evacuation time be...

Page 12: ...lect pressure unit Hold down the button Use the button to select the desired unit Release both buttons Save value current measurement value press the and buttons at the same time Retrieve memory value...

Page 13: ...red hose 2 to high pressure side of system Connect yellow hose 3 8 3 to vacuum pump Connect yellow hose 1 4 4 to refrigerant cylinder Close both valves 5 6 Evacuating the system Switch on the manifol...

Page 14: ...ure and temperature Remove the hoses from the system Open valves 5 6 b with DIGIMON4 manifold Disconnect the yellow hose 3 8 from the vacuum pump and the DIGIMON4 3 and screw the caps onto the 3 8 SAE...

Page 15: ...sehold cleaners and soapy water should be used instead Manifold seals are subject to mechanical and age related wear Therefore the manifold should be regularly tested by the user for leaks In case of...

Page 16: ...evice users should observe the disposal regulations applicable in their country Replacement parts and accessories Description Identifier P N Control knob set M4 7 SET B N R Y 4687094 Complete valve se...

Page 17: ...er a vacuum Factory settings Set the DIGIMON to the Digital display screen Press the and buttons at the same time for 5 seconds Display shows Press the button to exit Resetting the external vacuum sen...

Page 18: ...y For a correct calibration there should be no pressure or vacuum in the DIGIMON 6 Press the button to select the low pressure side s calibration pressure 400psi 7 Press the button to exit 8 Wait 3 5...

Page 19: ...he button once Continue holding down the Light button until the display shows Password 000 4 Press the buttons to scroll to code 018 5 Press the button once Display shows T call 6 Press the button onc...

Page 20: ...cables must be straight unwound 3 While holding down the button continuously switch on the device by pressing the button once Continue holding down the Light button until the display shows Password 0...

Page 21: ...cool button Read T1 and T2 temperature readings with sensors in the same ice bath They should be within 1 0 C of 0 0 C ON OFF R SET LP End 011xx 24 4 C Take your time use lots of ice and stir water of...

Page 22: ...REFCO Manufacturing Ltd Industriestrasse 11 6285 Hitzkirch Switzerland Telefon 41 41 919 72 82 Telefax 41 41 919 72 83 info refco ch www refco ch 4686731 0916...

Reviews: