Reer AD SR2 Installation, Use And Maintenance Manual Download Page 9

9

Use of K1 and K2 auxiliary contact elements.

For loads with higher voltage and current characteristics than those
indicated in the table above, use of auxiliary external relays or contactors
suitable for the load to be controlled is recommended.

+

 

If the K1 K2 Feedback is used, The K1 and K2 auxiliary contactors or relays
must be of the guided contact safety type.

  Referring to the table below, pay particular attention to the

configuration of the control contacts on terminal 11 and that
of the contacts of use.

Relay K1

Relay K2

Control contacts

K1-1 normally closed

K2-1 normally closed

Use contacts

K1-2 normally open

K2-2 normally open

  Control contacts K1-1 and K2-1 (terminal 13) must be able to

switch a current of 20mA and a voltage of 24Vdc.

  To increase the electrical life of internal relays A and B, it is

advisable to use anti-disturbance devices which must be
connected across the coils of K1 and K2.

Warnings regarding the connection cables.

  For light curtain/safety interface connections of more than

50m, cables with a cross-section of at least 1mm

2

 must be

used.

  It is good practice to separate the power supply of the safety

interface from that of other electrical appliances (electrical motors,
inverters, frequency variators) or other sources of disturbance.

  The path of the connection cables between the  safety

interface ands the sensors, the connection referring to the test
command and feedback contacts connected to terminal 13
must be different from that of other power cables.

Summary of Contents for AD SR2

Page 1: ...SAFETY INTERFACE AD SR2 INSTALLATION USE AND MAINTENANCE HANDBOOK INDICE INTRODUCTION 3 OPERATING MODES 4 INSTALLATION AND ELECTRICAL CONNECTIONS 7 DIMENSIONS 10 TECHNICAL DATA 10 WARRANTY 11...

Page 2: ...2...

Page 3: ...ut of the K1 K2 feedback to check that these operate in safety The AD SR2 interface when connected to one or two type 4 photoelectric safety barriers certified to IEC 61496 1 2 standard equipped with...

Page 4: ...hrough the opening he she may remain in the danger zone without being detected use as trip device according to IEC 61496 Failure to comply with this rule may result in very serious risks for the perso...

Page 5: ...S K1 and K2 Control of external contactors K1 K2 can be activated in both operating modes If this control is to be used the set of normally closed and normally open ed contacts of the external contact...

Page 6: ...ar waiting for RESTART command ON Malfunction detected output relays open FAIL Red OFF Correct functioning ON K1 K2 malfunction detected output relays open FAIL K1 K2 Red OFF Correct functioning ON Ba...

Page 7: ...ntact blocks connected mechanically Release action to control contact opening There must never be more than a 500msec delay between both contacts in the switch closing if that is not the case the inte...

Page 8: ...ates the RESTART command The Restart command must be located outside the danger zone in a place from which the danger zone and the entire work area concerned are clearly visible The controls must not...

Page 9: ...ol contacts K1 1 and K2 1 terminal 13 must be able to switch a current of 20mA and a voltage of 24Vdc To increase the electrical life of internal relays A and B it is advisable to use anti disturbance...

Page 10: ...1 N C contact 20mA 24VDC Connections To terminal block with protection against reversal of polarity CLEAR output Imax 100mA Status indicators Led Guard Break Fail Fail K1 K2 Light Barr1 Light Barr2 Sa...

Page 11: ...s modifications adaptations not carried out by REER personnel tampering etc Accidents or impacts also due to transportation or causes of force majeure Other causes not to be ascribed to REER Repairs w...

Reviews: