Once the protected area has been occupied, the relay outputs are de-
activated. The sequence described above must be repeated in order to
re-activate these.
The RESTART command is active with a voltage of 24 Vdc.
The minimum duration of the command is 300 ms.

Figure 2

CONNECTION OF EXTERNAL CONTACTORS K1 and K2

Control of external contactors K1/K2 can be activated in both operating
modes. If this control is to be used, the set of normally closed and
normally open ed contacts of the external contactors must be connected
to terminal 13 of the interface (figures 3 and 4).

Figure 3

Automatic functioning with K1/K2 relays

**

 CONNECT INPUTS 8-9-11 TO +24Vdc AND INPUT 12 TO 0Vdc

 IF NOT USED

 USE SUITABLE ANTI-DISTURBANCE DEVICE

**

 CONNECT INPUTS 8-9-11 TO +24Vdc AND INPUT 12 TO 0Vdc

 IF NOT USED

USE CONTACTS

Summary of Contents for AD SR2

Page 1: ...SAFETY INTERFACE AD SR2 INSTALLATION USE AND MAINTENANCE HANDBOOK INDICE INTRODUCTION 3 OPERATING MODES 4 INSTALLATION AND ELECTRICAL CONNECTIONS 7 DIMENSIONS 10 TECHNICAL DATA 10 WARRANTY 11...

Page 2: ...2...

Page 3: ...ut of the K1 K2 feedback to check that these operate in safety The AD SR2 interface when connected to one or two type 4 photoelectric safety barriers certified to IEC 61496 1 2 standard equipped with...

Page 4: ...hrough the opening he she may remain in the danger zone without being detected use as trip device according to IEC 61496 Failure to comply with this rule may result in very serious risks for the perso...

Page 5: ...S K1 and K2 Control of external contactors K1 K2 can be activated in both operating modes If this control is to be used the set of normally closed and normally open ed contacts of the external contact...

Page 6: ...ar waiting for RESTART command ON Malfunction detected output relays open FAIL Red OFF Correct functioning ON K1 K2 malfunction detected output relays open FAIL K1 K2 Red OFF Correct functioning ON Ba...

Page 7: ...ntact blocks connected mechanically Release action to control contact opening There must never be more than a 500msec delay between both contacts in the switch closing if that is not the case the inte...

Page 8: ...ates the RESTART command The Restart command must be located outside the danger zone in a place from which the danger zone and the entire work area concerned are clearly visible The controls must not...

Page 9: ...ol contacts K1 1 and K2 1 terminal 13 must be able to switch a current of 20mA and a voltage of 24Vdc To increase the electrical life of internal relays A and B it is advisable to use anti disturbance...

Page 10: ...1 N C contact 20mA 24VDC Connections To terminal block with protection against reversal of polarity CLEAR output Imax 100mA Status indicators Led Guard Break Fail Fail K1 K2 Light Barr1 Light Barr2 Sa...

Page 11: ...s modifications adaptations not carried out by REER personnel tampering etc Accidents or impacts also due to transportation or causes of force majeure Other causes not to be ascribed to REER Repairs w...

Reviews: