Reer AD SR2 Installation, Use And Maintenance Manual Download Page 8

8

The RESTART command.

  The RESTART command must be sent to the safety interface by

connecting terminal 6 to the +24VDC.

  The contact used for the RESTART command must be

capable of switching 24VDC and 20mA (and guarantee a
closing time of > 300ms). This point is particularly important
when the RESTART command is managed automatically,
using a PLC for example.

  The system restarts within 300ms from sending a RESTART

command (in MANUAL mode). This means that the output circuit
cannot be energized before that time.

  To calculate the SYSTEM RESTART DELAY, add the restart

delay for any external K1/K2 contactors to the AD SR2
interface restart delay (300ms).

  In case of manual operation, an external N/O switch can be

used that, when temporarily closed, generates the RESTART
command.

+

 

The Restart command must be located outside the danger zone, in a place
from which the danger zone and the entire work area concerned are
clearly visible.

+

 

The controls must not be accessible from inside the danger zone.

The CLEAR output.

The interface supplies a voltage (idle) of +24VDC to the 

CLEAR 

output

(terminal  15)

 when the barriers are clear and the relays de-energized.

This output is internally protected to supply a maximum current of
100mA.

Characteristics of the output circuit.

The safety interface uses two safety relays with force guided contacts for
the output circuit.
To ensure correct insulation and avoid damage or premature ageing,
protect each output line with a delayed 4A fuse and check that the load
characteristics comply with the indications shown in the following table.

Minimum switching voltage

18 VDC

Minimum switching current

20 mA

Maximum switching voltage

250Vac

Maximum switching current

2A

Summary of Contents for AD SR2

Page 1: ...SAFETY INTERFACE AD SR2 INSTALLATION USE AND MAINTENANCE HANDBOOK INDICE INTRODUCTION 3 OPERATING MODES 4 INSTALLATION AND ELECTRICAL CONNECTIONS 7 DIMENSIONS 10 TECHNICAL DATA 10 WARRANTY 11...

Page 2: ...2...

Page 3: ...ut of the K1 K2 feedback to check that these operate in safety The AD SR2 interface when connected to one or two type 4 photoelectric safety barriers certified to IEC 61496 1 2 standard equipped with...

Page 4: ...hrough the opening he she may remain in the danger zone without being detected use as trip device according to IEC 61496 Failure to comply with this rule may result in very serious risks for the perso...

Page 5: ...S K1 and K2 Control of external contactors K1 K2 can be activated in both operating modes If this control is to be used the set of normally closed and normally open ed contacts of the external contact...

Page 6: ...ar waiting for RESTART command ON Malfunction detected output relays open FAIL Red OFF Correct functioning ON K1 K2 malfunction detected output relays open FAIL K1 K2 Red OFF Correct functioning ON Ba...

Page 7: ...ntact blocks connected mechanically Release action to control contact opening There must never be more than a 500msec delay between both contacts in the switch closing if that is not the case the inte...

Page 8: ...ates the RESTART command The Restart command must be located outside the danger zone in a place from which the danger zone and the entire work area concerned are clearly visible The controls must not...

Page 9: ...ol contacts K1 1 and K2 1 terminal 13 must be able to switch a current of 20mA and a voltage of 24Vdc To increase the electrical life of internal relays A and B it is advisable to use anti disturbance...

Page 10: ...1 N C contact 20mA 24VDC Connections To terminal block with protection against reversal of polarity CLEAR output Imax 100mA Status indicators Led Guard Break Fail Fail K1 K2 Light Barr1 Light Barr2 Sa...

Page 11: ...s modifications adaptations not carried out by REER personnel tampering etc Accidents or impacts also due to transportation or causes of force majeure Other causes not to be ascribed to REER Repairs w...

Reviews: