Reefe 21297 Exploded View & Instruction Manual Download Page 9

www.

reefe

.com.au

Ascento Group Australia

© 

AI.062020

P: 1800 807 604

ALARMS FOR SINGLE ASSEMBLY.

In case of simultaneous alarms, quit the automatic mode and go to manual mode, pressing  the pushbutton 

AUTOMATIC ON/OFF

 (led light PUMP will 

turn off). Using key 



  will be displayed the succesive alarms. Once visualized, for leaving the menu,  press 

ENTER

 returning to 

MANUAL

 mode. 

A1 DRY RUNNING 

(

  Failure verification 

 Final failure)

DESCRIPTION: if the system detects dry running during more than 10 seconds, it will stop the pump and the ART (Automatic ResetTest) will be 

activated. 

SYSTEM REACTION: after 5 minutes ART system will start again the pump during 30 seconds, trying to restore the system. In case of persistent lack of 

water, it will try it again every 30 minutes for 24 hours. If after all these cycles , the system still detects lack of water, pump will remain permanently out 

of order until the damage will be repaired.

SOLUTION: dry running,  it has been activated the safety system: you should verify the feeding of the hydraulic network. The pumps can be primed 

using the push-button START/STOP ( the led light AUTOMATIC should be off, if it is not, press the push-button to disable it).

Special case: 

if the pump cannot provide the programmed pressure (configuration mistake) the unit reacts as it was dry-running.

Special Case 2:

 this device manages the dry running control through the nominal current consumption of the pump. It must be verified  the introduced 

current consumption in the setup menu.

A2 OVER-INTENSITY

(

  Failure verification 

 Final failure)

DESCRIPTION: the  pump is protected against over currents by mean of the intensity values established in the installation menu. These over currents are 

produced generally by dysfunctions in the pump or in the electric supply.

SYSTEM REACTION: when detecting the thermal failure, the pump will be automatically stopped. The  system will try again to restart the  pump when 

the demand of consumption require it. The control system will carry out 4 attempts in this circumstances. If the system remain locked after the 4th 

attempt, the  pump will remain definitively out of order.

SOLUTION: verify the state of the pump, for example the impeller could be blocked. Verify intensity values introduced in the configuration menu. Once 

the problem have been solved the operation will be restored going to the “SET UP” menu ( see the chapter configuration) and configuring the adequate 

intensity values.

A3 DISCONNECTED

 P. (

 Final failure)

DESCRIPTION: the device has an electronic safety system in case of no load detection.

SYSTEM REACTION: the device is disconnected.

SOLUTION: the wound of the motor and the pump consumption should be verified. Once the problem have been solved the operation will be restored 

going to the "SET UP" menu (see the chapter configuration) and introducing the adequate intensity values. Verify the fuses (see fig.3), in case of being 

melt contact with technical service.

A5 TRANSDUCER

 (

 Final failure)

DESCRIPTION: the transducer damages are showed in the LCD screen.

SYSTEM REACTION: the device operation is interrupted.

SOLUTION:  check the external pressure transmitter.

A6 EXCESSIVE TEMP

.  (

 Final failure)

DESCRIPTION: the system has a cooling device to keep the INVERTER in optimum working conditions.  

SYSTEM REACTION: if an excessive temperature is reached the own system leaves the inverter out of service and as consequence the pump too.

SOLUTION: verify the temperature environment should be under 50 ºC.  Contact with technical service.

A7 SHORTCIRCUIT

 (

 Final failure)

DESCRIPTION: the device has an electronic system for protection against short circuits as well as peaks of current.

SYSTEM REACTION: the pump stops and then it starts again -performing 4 successive attempts. If the problem is not solved, the pump will remain 

definitively out of order. 

SOLUTION: check the pump, if the problem persists, contact the technical service.

A8 OVERVOLTAGE - A9 UNDERVOLTAGE

 (

  Failure verification)

DESCRIPTION: the device has an electronic safety system against overvoltage’s and too low supply voltages.

SYSTEM REACTION: in case of overvoltage or undervoltage the system remains stopped until an adequate value of voltage is reached. In this case, the 

system is automatically restored.

SOLUTION: check the electric supply.

ALARM INSTALLATION MASTER-SLAVE 

A10 COMUNICA

 (

  Failure verification)

DESCRIPTION: If you have configured a Master-Slave system and communication cable is disconnected or there is a bad connection, the system stops. 

SYSTEM REACTION: The Master-Slave system stops and starts to operate individually. 

SOLUTION: Check the cable connection and if this is OK, check the connection inside the unit. Check the configuration of the Master-Slave system 

(setup menu). 

DESCRIPTION: blank screen.  

SOLUTION: check the electric supply. In case of being in right conditions, the general fuse, located in the main plate (fig 1) should be verified.

Summary of Contents for 21297

Page 1: ...om au EXPLODED VIEW INSTRUCTION MANUAL P U M P S A U S T R A L I A BETTER FASTER EASIER BETTER FASTER EASIER MODEL VSC1 10W VSC1 12W VSC3 9W VSC3 14W CODE 21297 21910 21934 21941 VARIABLE SPEED DRIVE...

Page 2: ...mm2 1 1 5 OUTPUT FILTER T T Maste Cavo d C ble Cable Maste Maste Kabel Pressu Trasdu Capte Transd Druks Druks Przetw Minim Livello Niveau Senso Extern Minim Minim Power Alimen Alimen Alimen Netza Voe...

Page 3: ...re doing any maintenance inside the device it must be unplugged from the electric supply and wait a minimum of 2 minutes after the disconnection to avoid electrical discharges WARNING SYMBOLS CONTAINE...

Page 4: ...its housing Screw the cover and the PG If the devices are provided with the communication cable it governs the following color code 1 black 2 brown 3 grey and 4 yellow blue They will be connected by...

Page 5: ...robe MAX MIN LEV N O CONTACT General Fuse Power Supply U V 1 240 V M Single Phase Motor Connection Three Phase Motor Connection U V W 3 240 V M Fig 3 CONNECTIONS VSC1 12W 240 VSC1 10W 15 V DC 24 V DC...

Page 6: ...er supply System is activated in AUTOMATIC mode keeping the configuration parameters see CONFIGURATION chapter External pressure transducer 4 20 mA under demand Possibility of communication with anoth...

Page 7: ...nd 4 In case of M S communication it will be connected a pressure transmitter in each unit Min level control optional There is an input for stopping the pump as soon as is disconnected the external sw...

Page 8: ...Press ENTER for validation MINIMUM FREQUENCY Using we can increase the lower frequency value within 15 48 Hz for 3 phase pumps and 30 48 Hz for single phase pumps The minimum frequency value will be...

Page 9: ...ng to the SET UP menu see the chapter configuration and configuring the adequate intensity values A3 DISCONNECTED P Final failure DESCRIPTION the device has an electronic safety system in case of no l...

Page 10: ...arms in both devices the system performs 4 restore attempts if it fails the system is disabled To restore manually a device disabled by an alarm push AUTOMATIC ON OFF in MASTER device and then ENTER i...

Reviews: