Reefe 21297 Exploded View & Instruction Manual Download Page 10

www.

reefe

.com.au

Ascento Group Australia

© 

AI.062020

P: 1800 807 604

              ALARMS FOR GROUP ASSEMBLY:

The alarms for assembled devices, are like those of the individual one with the specific particularities of operation with 2 communicated devices. De-

pending on the system´s reaction there are 3 types of alarm:

1

 .- 

COMMUNICATION FAILURE:

 not any alarm is activated. Both devices continue operating independently. There will not be flashing led-light in any 

unit.

2 .- DRY RUNNING OPERATION:

 if there is a lack of water alarm in a single pump, the other one assumes the role of “main device”, if there is an 

over-demand during next operating cycles, the system will try to restore the device in failure. If the device is restored in these conditions, then it will 

be also restored the alternated operating mode. If there is lack of water on both devices, the system will activate the ART system in the MASTER unit. 

3 .- REST OF ALARMS:

 If the alarm has occurred in a single device, the other will act as “main device”. The system will try to restore the disabled 

device only in case of over demand, after 4 successive attempts without success the device is turned off, it should be restored manually. In case of 

alarms in both devices the system performs 4 restore attempts, if it fails the system is disabled.

To restore manually a device disabled by an alarm push 

AUTOMATIC ON / OFF 

in MASTER device and then 

ENTER

 in the device with the alarm.

REGISTER OF OPERATION DATA AND ALARMS.

By using simultaneously MENU + 

during 3” is acceded to 

REGISTER OF OPERATION DATA AND ALARMS

, by mean of 

ENTER

 we can advance through 

the sequence, once finished the sequence it returns to the main display. This is all the sequence:

• 

REGISTER HOURS. Counter of total time that the pump has been operating.

• 

REGISTER STARTS. Number of cycles of operation, a cycle is a start and a stop.

• 

REGISTER SWITCH. Number of connections to the electric supply.

• 

MAX PRESSURE. Maximum pressure reached by the installation. It allows the detection of water hammer.

• 

ALARM COUNT. SHORTCIRC. Number of short circuit alarms.

• 

ALARM COUNT I MAX. Number of overcurrent alarms.

• 

ALARM COUNT. TEMP. Number of alarms by excessive temperature.

• 

ALARM COUNT DRY RUN. Number of dry-running alarms.

All the records are saved even if the device has been disconnected from the electric supply.

C Y C L E S

X X

D R Y

R U N

X X

S H O R T C I R

X X

R E G I S T E R

S W I T C H

O N

X X

T E M P E R A T

X X

H I G H
V O L T

X X

U N D E R V O L

X X

H O U R S

X X

I N T E N S I .

X X

 

MENU+

ENTER

ENTER

ENTER

ENTER

ENTER

ENTER

ENTER

P s e t

4 , 0

P b a r

3 , 9

P s e t

4 , 0

P b a r

3 , 9

Summary of Contents for 21297

Page 1: ...om au EXPLODED VIEW INSTRUCTION MANUAL P U M P S A U S T R A L I A BETTER FASTER EASIER BETTER FASTER EASIER MODEL VSC1 10W VSC1 12W VSC3 9W VSC3 14W CODE 21297 21910 21934 21941 VARIABLE SPEED DRIVE...

Page 2: ...mm2 1 1 5 OUTPUT FILTER T T Maste Cavo d C ble Cable Maste Maste Kabel Pressu Trasdu Capte Transd Druks Druks Przetw Minim Livello Niveau Senso Extern Minim Minim Power Alimen Alimen Alimen Netza Voe...

Page 3: ...re doing any maintenance inside the device it must be unplugged from the electric supply and wait a minimum of 2 minutes after the disconnection to avoid electrical discharges WARNING SYMBOLS CONTAINE...

Page 4: ...its housing Screw the cover and the PG If the devices are provided with the communication cable it governs the following color code 1 black 2 brown 3 grey and 4 yellow blue They will be connected by...

Page 5: ...robe MAX MIN LEV N O CONTACT General Fuse Power Supply U V 1 240 V M Single Phase Motor Connection Three Phase Motor Connection U V W 3 240 V M Fig 3 CONNECTIONS VSC1 12W 240 VSC1 10W 15 V DC 24 V DC...

Page 6: ...er supply System is activated in AUTOMATIC mode keeping the configuration parameters see CONFIGURATION chapter External pressure transducer 4 20 mA under demand Possibility of communication with anoth...

Page 7: ...nd 4 In case of M S communication it will be connected a pressure transmitter in each unit Min level control optional There is an input for stopping the pump as soon as is disconnected the external sw...

Page 8: ...Press ENTER for validation MINIMUM FREQUENCY Using we can increase the lower frequency value within 15 48 Hz for 3 phase pumps and 30 48 Hz for single phase pumps The minimum frequency value will be...

Page 9: ...ng to the SET UP menu see the chapter configuration and configuring the adequate intensity values A3 DISCONNECTED P Final failure DESCRIPTION the device has an electronic safety system in case of no l...

Page 10: ...arms in both devices the system performs 4 restore attempts if it fails the system is disabled To restore manually a device disabled by an alarm push AUTOMATIC ON OFF in MASTER device and then ENTER i...

Reviews: