background image

 

Inside US: +1 (877) 432-9908

Bulletin No. DA30D-A

Outside US: +1 (717) 767-6511

Drawing No. LP1078

www.redlion.net

Effective  2018-11-02 

-1-

Model

 

DA30D

 ‐ 

High

 

Performance

 

Protocol

 

Converter

 

and

 

Data

 

Acquisition

 

System

CONFIGURED USING CRIMSON

®

 3.1 SOFTWARE

THREE SERIAL COMMUNICATION PORTS, 
(2 RS-232 and 1 RS-422/485)

A 10 BASE T/100 BASE-TX ETHERNET PORT COMMUNICATES 
WITH UP TO TEN PROTOCOLS SIMULTANEOUSLY

ACCEPTS ONE EXPANSION COMMUNICATION MODULE TO ADD 
CANOPEN, J1939, PROFIBUS, DEVICENET AND MORE

ONE USB DEVICE PORT TO LOAD THE UNIT’S CONFIGURATION 
OR TRANSFER DATA TO AND FROM A PC

SD CARD SOCKET FOR DATA LOGGING AND LOADING DATABASE 
IN FIELD

RUGGED IP40-RATED ENCLOSURE

THREE FRONT FACE LED INDICATORS

POWER UNIT FROM 10-30 VDC SUPPLY

SUPPORTS OVER 300 INDUSTRIAL PROTOCOLS

BUILT-IN WEB SERVER FOR REMOTE ACCESS

REAL-TIME DATA LOGGING

ALARM NOTIFICATIONS VIA EMAIL OR SMS MESSAGES

FOR USE IN HAZARDOUS LOCATIONS:

 

Class I, Division 2, Groups A, B, C, and D

 

 

C

US

UL

R

LISTED

IND.CONT. EQ.

E317425

GENERAL

 

DESCRIPTION

The DA30D data station acts as a nexus for industrial data collection

and management. The unit offers multiple protocol conversion, data
logging and remote machine access. With three built in serial ports and a
10 Base-T/100 Base-TX Ethernet port, the unit performs protocol
conversion, allowing disparate devices to communicate seamlessly with
one another including PLCs, motor drives, bar code scanners, etc. The
Ethernet port supports up to ten protocols simultaneously using Crimson
3.1, so even Ethernet to Ethernet protocols can be converted. 

The SD card slot can collect your trending and datalogging information

as well as load the unit's configuration file, allowing configuration
changes to be made and saved to the card for later transfer.

The built-in web server allows log files to be retrieved manually, and

also provides access to the unique “virtual HMI”. The virtual HMI is
programmed just like Red Lion’s CR3000 series of HMIs. Any standard
web browser may be used to monitor or control the DA30D from a PC
anywhere in the world. 

The DAx0D is programmed with Red Lion's Crimson 3.1 software.

Crimson offers easy to use drag and drop communications configuration
and is available as a no charge download from Red Lion's website.

DIMENSIONS

 

In

 

inches

 

(mm)

SAFETY

 

SUMMARY

All safety related regulations, local codes and instructions that appear

in the manual or on equipment must be observed to ensure personal
safety and to prevent damage to either the instrument or equipment
connected to it. If equipment is used in a manner not specified by the
manufacturer, the protection provided by the equipment may be
impaired.

Do not use the unit to directly command motors, valves, or other

actuators not equipped with safeguards. To do so can be potentially
harmful to persons or equipment in the event of a fault to the unit.

CONTENTS

 

OF

 

PACKAGE

- DA30D
- Terminal block for connecting power

ORDERING

 

INFORMATION

1

  Contact your Red Lion distributor or visit our website for selection of expansion

modules, SD  cards, adapters and cables.

5.03

(127.7)

3.99 (101.4)

1.31 (33.3)

MODEL NO.

DESCRIPTION

PART NUMBER

DA30D

Protocol Converter with 3 Serial Ports,
1 Ethernet Port, and USB Device Port

DA30D 0F 000000 000

CRM000

Expansion Modules 

1

CRM0000 xxxxx xxxxx

SD

SD Card 

1

SDxxxxxx

CBL

Communications Cables and Adapter 

1

CBLxxxxx

CRA000

Replacement Battery

CRA000 BT3V0 00000

WARNING - EXPLOSION HAZARD - DO NOT D
EQUIPMENT UNLESS POWER HAS BEEN SW
OR AREA IS KNOWN TO BE NON-HAZARDOU

CAUTION: Risk of Danger.

Read complete instructions prior to installation 
and operation of the unit.

WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT 
EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF 
OR AREA IS KNOWN TO BE NON-HAZARDOUS.

WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT 
EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF 
OR AREA IS KNOWN TO BE NON-HAZARDOUS.

WARNING - EXPLOSION HAZARD - SUBSTITUTION OF 
COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, 
DIVISION 2.

Summary of Contents for DA30D

Page 1: ...tual HMI The virtual HMI is programmed just like Red Lion s CR3000 series of HMIs Any standard web browser may be used to monitor or control the DA30D from a PC anywhere in the world The DAx0D is programmed with Red Lion s Crimson 3 1 software Crimson offers easy to use drag and drop communications configuration and is available as a no charge download from Red Lion s website DIMENSIONS In inches ...

Page 2: ... COMPLIANCES CE Approved EN 61326 1 Immunity to Industrial Locations Emission CISPR 11 Class A IEC EN 61010 1 RoHS Compliant UL Hazardous File E317425 Rugged IP40 enclosure 7 CONNECTIONS High compression cage clamp terminal block Wire Strip Length 0 3 7 5 mm Wire Gage Capacity 12 to 24 AWG 3 31 to 0 20 mm2 copper wire Torque 4 4 5 3 inch lbs 0 5 0 6 N m 8 CONSTRUCTION Polycarbonate enclosure with ...

Page 3: ...ifference between a successful or troublesome installation Listed are some EMI guidelines for a successful installation in an industrial environment 1 A unit should be mounted in a metal enclosure which is properly connected to protective earth 2 Use shielded cables for all Signal and Control inputs The shield connection should be made as short as possible The connection point for the shield depen...

Page 4: ...D CARD Insert the SD card into the slot provided with the card oriented as shown The card is inserted properly when the end of the card is flush with the DA30D case To remove the SD card push in slightly on the card CABLES AND DRIVERS Red Lion has a wide range of cables and drivers for use with many different communication types A list of these drivers and cables along with pin outs is available f...

Page 5: ...B 8 TxA 8 TxA CRIMSON 3 1 SOFTWARE Crimson 3 1 software is available as a no charge download from Red Lion s website The latest version of the software is always available from the website and updating your copy is free STATUS LEDS There are three status LEDs that show system status by default or they may be be user configured via System Functions using Crimson 3 1 Shown below is the default syste...

Page 6: ...ery is correct and as shown in the diagram Re install the battery holder with battery into the DAx0D unit Enter new date and time using Crimson 3 1 software CAUTION Lithium battery Danger of explosion if battery is incorrectly replaced Replace only with the same or equivalent type recommended by the manufacturer Please note that the old battery must be disposed of in a manner that complies with yo...

Page 7: ... 7 Effective 2018 11 02 Bulletin No DA30D A Drawing No LP1078 This page intentionally left blank ...

Page 8: ... BY LAW COURSE OF DEALING COURSE OF PERFORMANCE USAGE OF TRADE OR OTHERWISE Customer shall be responsible for determining that a Product is suitable for Customer s use and that such use complies with any applicable local state or federal law b The Company shall not be liable for a breach of the warranty set forth in paragraph a if i the defect is a result of Customer s failure to store install com...

Reviews: