MODES OF OPERATION FOR DUAL PRESET LNXNT TIMER (Cont’d)
MODE 11 OUTPUT 1 TURN OFF AT ZERO, TIMED OUTPUT 2 AT
ZERO, MANUAL RESET TO PRESET 2
The unit times down from preset 2, when preset 1
is reached, output 1 turns on. When zero is reached,
output 1 turns off and output 2 turns on for the
amount of time programmed. Time continues to decrement after the
preset levels have been reached. When a manual reset is performed,
the time resets to preset 2, and the cycle starts again.
MODE 12 OUTPUT 1 TURN OFF AT ZERO, TIMED OUTPUT 2 AT
ZERO, AUTOMATIC RESET TO PRESET 2 AT ZERO
The unit times down from preset 2, when preset 1
is reached, output 1 turns on. When zero is reached,
output 2 turns on for the amount of time
programmed, output 1 turns off, and the time
automatically resets to preset 2.
MODE 13 TIMED OUTPUTS AT PRESET 1 AND ZERO,
AUTOMATIC RESET TO PRESET 2 AT ZERO
The unit times down from preset 2, when preset 1
is reached, output 1 turns on. When zero is reached,
output 2 turns on. The outputs turn off at the end of
their respective programmed time values. At zero, the time
automatically resets to preset 2 and the cycle starts again.
MODE 14 OUTPUT 1 TURN OFF AT ZERO, TIMED OUTPUT 2 AT
ZERO, AUTOMATIC RESET TO PRESET 2 AFTER TIMED
OUTPUT 2
The unit times down from preset 2, when preset 1
is reached, output 1 turns on. When zero is reached,
output 1 turns off and output 2 turns on for the
amount of time programmed. At the end of timed output 2, the time
automatically resets to preset 2, and the cycle starts again.
MODE 15 TIMED OUTPUTS AT PRESET 1 AND ZERO,
AUTOMATIC RESET TO PRESET 2 AFTER TIMED
OUTPUT 2
The unit times down from preset 2, when preset 1
is reached, output 1 turns on. When zero is reached,
output 2 turns on. The outputs turn off at the end of
their respective programmed time values. At the end of timed output
2, the time automatically resets to preset 2 and the cycle starts again.