background image

P/N 26404 Manual Issue A 

Instruction Manual

 26404 (Pg 1 / 2)

Time switch (weekly program)

Connection diagram 

Directory 

1. Safety instructions 

70mm  (4 channels) 

Weekly time switch 

1. Safety instructions

2. Initial operation 

3. DCF (Installation DCF-receiver) 

4. Menu overview 

5. Symbol legend 

6. Key function 

7. Handling advice 

8. Channel 

ON  OFF 

/ Permanent 

P

9. Programming menu 

10. Standard weekly program 

11. Example of a standard weekly  

      switching time 

12. Cycle 

13. Cycle options

14.  Pulse

15. Priority of the switching programs 

16. Permanentprogram 

17. External Input   

18. Channel keys 

19. Additional adjustments 

20. Program modify 

21. Data-key 

!

The installation and assembly of electrical equipment must be only carried out only 

by a skilled Person! Otherwise fire danger or danger of an electric shock exists! 

!

Connect the supply voltage/frequency as stated on the product label! 

!

Warranty void if housing opened by unauthorised person!

!

The electronic circuit is protected against a wide range of external influences. 

Incorrect operating may occur if external influences exceed certain limits! 

2.  Initial operation 

3. DCF (Installation of the DCF-antenna FU 20) 

The time switch is delivered in sleep-mode, the display is switched off.

Press  -button for 1 second. 

The current date and time is already programmed and European 

daylight savings time is activated. 

Select the desired language by pressing 

-buttons and confirm it by 

pressing  .

(Remark: By pressing   you move one step backwards 

from the current position)

If required, date, time and daylight savings time mode can be adjusted 

also by pressing 

-buttons and a subsequent confirmation with  .

The time switch can process the DCF signal.

The antenna FU 20 is not included in delivery of the time switch. 

Disconnect power supply voltage 

Connect the antenna as indicated by the connection diagram 

Connect supply voltage 

Antenna symbol (LCD) flashes for approx. 3 minutes 

Reception is not possible if severe interference is present 

(Permanent flashing of the symbol / The oscillating crystal is used as time base) 

Defective wire between antenna and time switch 

(No antenna symbol visible / The oscillating crystal is used as time base)

4.  Menu overview 

5.  Symbol legend 

Channel is switched ON 
Channel is switched OFF 
For the current date the “holiday program” / “permanent by date” is activated 
Standard programming step 
Current state is based on a manual over-ride. The state will be cancelled with the next 

programming step 

Current state is based on a manual over-ride. The state is permanent until terminated manually 

Days of the week Monday, Tuesday, ... Sunday; 

The underscores indicate if the program is active for the days above 
Current state is based on a switching time with pulse function  

Current state is based on a switching time with cycle function 

Is displayed if the corresponding channel is activated by the external input. 

Element within sub-menu “program delete” 

6.  Key function 

DCF: The time switch receives the signal for the DCF -77 time standard 

1. To access the Enter-mode (program, adjustments, options) from the automatic-mode. 

2. To revert to the beginning of the current (sub-) menu.   

The time switch is locked; to unlock the device the PIN has to be entered

1. To adjust the flashing digit. 

2. To scroll through a choice 
1. Automatic-mode: To switch the channel ON or OFF until the next programming step occurs. 

2. Automatic-mode: A push longer than 3 sec. = Permanent switching status (7). 
1. To activate the time switch when operated without power supply. 

2. To confirm the selection or the entered data. 

7. Handling advice 

8. Channel 

ON OFF

/ Permanent 

P

9. Programming menu 

The time switch is programmable without external power supply 

after pressing the   -button. 

To revert one step or one level back while in the Enter-Mode press

.

After completion of a (sub-) menu confirming 

end

 will return the 

device into the automatic-mode. 

With 

 the choice changes from 

end

 to 

continue

. By 

confirming 

continue

 the time switch returns to the beginning of 

the current (sub-) menu. 

When confirming 

end

 before completion, the time switch returns 

to the automatic-mode without saving the entered data. 

Channel 

ON OFF

By pushing 

-buttons a manual switch of the channels 

take place. The resulting switching status is marked with 

the hand-symbol and remains until the next programming 

step occurs. (temporary over-ride) 

Permanent switching status 

P

By pressing the corresponding channel button 

for 

more than 3 sec. the channel is permanently switched ON 

or OFF. The status remains until the next manual switching 

occurs (> 3 sec.). (permanent over-ride) 

*within yearly time switches 

10. Standard weekly program 

11. Example for the programming of 

STANDARD

 switching times (

ON

 and 

OFF

)

**The cycle function will only be available if it is activated (point 13) 

A.

If you want to program a standard weekly switching time (

on

,

) confirm 

Standard

 with  .

B.

For regular switching times choose 

on

 or 

 with 

-buttons and confirm with  .

C.

Within this level you activate the days of the week (1…7) on which the switching time should happen. 
With 

 you activate “yes” or deactivate “no” the corresponding date. Confirm each day with  .

D.

Adjustment of the time: Hours 

 and . Minutes 

 and .

E.

Verify the entered switching time: If the flashing summary of the programming step is correct, verify 

on

or 

 with  . After verification you have the choice between 

edit/delete

 and 

end

 with 

.

F.

If you want to proceed with programming, confirm 

next switching

with 

.

To leave the programming menu confirm 

end

.

Information: You can easily transfer switching times from one channel to the other if you use the 

copy function. 

12. Cycle 

13. Cycle options 

Standard weekly program:

 

Program

 ->

new program

 ->

channel A/B/C/D

 ->

Standard

 -> 

For the cycle function it is possibile to enter a periodic switching time. The time switch acts as a recycling timer and 

switches between pulse (ON) and pause (OFF). The max. value for pulse and pause is 9:59:59 h:mm:ss.  

If you haven’t defined and activated a cycle, the cycle function will not be available as switching time. Therefore you 

have to activate and define at least one of the four cycles within menu 

Options

 and sub-menu 

Cycle

 (point 13). 

The cycle switching time will be terminated by another switching time (

on

,

,

pulse

) or by another cycle switching 

time. 

Options

 ->

Cycle

 ->

Cycle 1 - 4

 ->

You have the possibility to define 4 different Cycles. For these purposes choose menu 

Options

 and sub-menu 

Cycle

. The different 

cycles can be activated, defined or deactivated (the max. value for pulse or pause is 9:59:59 h:mm:ss): 

Choose menu 

Options

 and sub-menu 

Cycle

 and confirm with   .

Select with 

 -buttons one out of the 4 cycles (

Cycle 1 – Cycle 4

) and confirm with  .

Activate the cycle by changing 

No

 to 

Yes

 with 

  -buttons and subsequent confirming with  .

Define duration of the pulse 

„on-time“

 (

 ->  …). 

Define duration of the pause 

 (

 ->  …). 

Confirm 

End

 with  .

The cycle is now offered within the programming menu.  

Further applications of the cycle function in combination with: External Input function and/or Channel keys function. 

14. Pulse 

15. Priorities of the switching programs 

Standard weekly program:

 

Program

 ->

new program

  ->

channel A/B/C/D

 ->

Standard

 -> 

The pulse function provides you the opportunity of programming a switching time with a defined duration. 

As soon as the pulse-duration has expired the time switch switches OFF automatically (the duration of the pulse is up to 

59:59 mm:ss). 

Standard switching times and Permanent by date are executed according to their 

corresponding priority (by channel and date)  

All switching programs 

except

 Extra switching times, suspend all other switching programs with lower priority: 

  highest priority   

 

 

manual over-ride Permanent (3 sec. push)  

                     

 

 

Permanent by date

  lowest priority   

 

Standard weekly program

16