PROGRAMMING

The CUB7P has programmable prescale values and decimal point positions.

These values are changed using the front panel push buttons. Connect wires
between RST EN (Reset Enable) and COM. (Common); and between HS
(Program Enable) and COM. (Common) to enable front panel push buttons.

Note: Upon entering the PGM mode for the first time, the Prescaler value is

set to 0.0000. Some value between 0.0001 and 1.9999 must be entered in
order for the CUB7P to operate properly. Previously stored values are
retained until changed by the user.

With the front panel push buttons enabled, press the PGM button to enter the

program mode. The CUB7P display will change to the current prescale value,
with the least significant digit flashing at a 2 Hz rate. The prescale value can be
set to any value between 0.0001 and 1.9999. Press the RST button to increment
the flashing digit to the desired value. Pressing the PGM button will lock in the
value of the flashing digit and advance to the next significant digit. The most
significant digit can only be set to 0 or 1. When the entire prescale value has
been programmed, press the PGM button once to enable decimal point
selection. Any new count pulses will be accumulated using the new prescale
value. 

After performing the prescale selection, the display will show 0.0000.

Decimal point positions can be set for:

Press the RST button until the desired decimal point position is displayed.

Press the PGM button to select that position and return to the counter mode.
Remove the wire from the HS (Program Enable) terminal to prevent accidental
changes to the programmed values.

Note: The incrementing edge of the count signal will change when the PGM

button is pressed for the first time. To avoid incorrect display information, it is
recommended that the CUB7P be reset after making programming changes.

COUNT EDGE

Accessing program mode for the first time will complement the

incrementing edge of the count signal. The table below shows the incrementing
edge of the count signal for the different versions of the CUB7P.

2

SPECIFICATIONS

1. 

DISPLAY

: 8-digit LCD, 0.35" (8.90 mm) high digits.

2. 

POWER SOURCE

: Replaceable Internal 3.0 V lithium battery to provide up

to 6 years of continuous operation. (Battery life is dependent upon usage.
Contacts that remain closed for long periods of time reduce battery life.)

3. 

BACKLIGHT POWER REQUIREMENTS

: 9 to 28 VDC; 35 mA. typical,

50 mA max. Above 26 VDC, derate max. operating temperature to 40°C.

4. 

SIGNAL INPUT

: (LS terminal #4) See 

Count Edge

under Programming for

incrementing edge of input signal.

Contact Input

(CUB7P0xx): 30 Hz max. from Switch Contact or solid state

Transistor Switch to Common with a50% duty cycle. Contact burden 7 µA max.

Voltage Input

(CUB7P1xx): 10 V min. to 300 V max. (AC 50/60 Hz. or DC)

to Common, 150 V max. for backlight versions. 30 cps max. Input current
0.5 mA max. ANY off-state leakage current may prevent counter from
activating. 

Logic Input

(CUB7P2xx): 10 KHz max. from a 3.0V bipolar output or 200

Hz max.from a solid state Transistor Switch to Common with a 50% duty
cycle. Contact burden 7 µA max.

5. 

REMOTE RESET

: 15 msec min. pulse width (active low) from 3.0 V

bipolar output, an open collector transistor, or a switch contact to common.

6. 

ENVIRONMENTAL CONDITIONS

:

Operating Temperature Range

: 0 to 50°C Derate max. operating

temperature to 40°C above 26 VDC (Backlight versions).

Storage Temperature

: -30 to 80°C

Operating and Storage Humidity

: 85% max. relative humidity (non-

condensing) from 0°C to 50°C.

Altitude

: Up to 2000 meters

7. 

CERTIFICATIONS AND COMPLIANCES

SAFETY

IEC-1010-1, EN 61010-1: Safety requirements for electrical equipment for

measurement, control, and laboratory use, Part 1.

IP65 Enclosure rating (Face only), IEC 529
Type 4X Enclosure rating (Face only), UL50

ELECTROMAGNETIC COMPATIBILITY

Notes

1. Backlit powered units require a power line filter to be installed, RLC

LFIL0000 or equivalent, so as not to impair the function of the
backlighting.

Refer to EMC Installation Guidelines for additional information.

8. 

CONSTRUCTION

: High impact plastic case with clear viewing window.

The front panel meets NEMA 4X/IP65 requirements for indoor use when
properly installed. Installation Category I, Pollution Degree 2. Panel gasket
and mounting clip included.

9. 

WEIGHT

: 2 oz. (57 grams) [with battery]

900 MHz 

± 5 MHz

Immunity to EN 50082-2

200 Hz, 50% duty cycle

Electrostatic discharge

EN 61000-4-2

Level 2; 4 Kv contact 

Level 3; 8 Kv air

Electromagnetic RF fields

EN 61000-4-3

Level 3; 10 V/m 

80 MHz - 1 GHz

Fast transients (burst)

EN 61000-4-4

Level 4; 2 Kv I/O

Level 3; 2 Kv power 

1

RF conducted interference

EN 61000-4-6

Level 3; 10 V/rms 

150 KHz - 80 MHz

Simulation of cordless telephone

ENV 50204

Level 3; 10 V/m

Emissions to EN 50081-1

RF interference

EN 55022

Enclosure class B

VERSION

AFTER INSTALLING OR

REPLACING BATTERY

AFTER ENTERING

PROGRAM MODE

CUB7P0 (Contact)

Rising Edge

Falling Edge

CUB7P1 (Voltage)

Falling Edge

Rising Edge

CUB7P2 (Logic)

Rising Edge

Falling Edge

0.0000 (Default)

0

0.00000

0.0

0.000000

0.00

00000000

0.000

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

Summary of Contents for CUB7P0

Page 1: ...r viewing window The sealed front panel with the silicone rubber buttons meets NEMA 4X IP65 specifications for wash down and or dusty environments when properly installed SAFETY SUMMARY All instructio...

Page 2: ...AL INPUT LS terminal 4 See Count Edge under Programming for incrementing edge of input signal Contact Input CUB7P0xx 30 Hz max from Switch Contact or solid state Transistor Switch to Common witha50 du...

Page 3: ...ble to the unit to suppress power line interference Install them near the power entry point of the enclosure The following EMI suppression devices or equivalent are recommended Ferrite Suppression Cor...

Page 4: ...d to be mounted into an enclosed panel The viewing window and reset button are factory sealed for a washdown environment A sponge rubber gasket and mounting clip are provided for installing the unit i...

Page 5: ...en the LS input and Common Any off state leakage current may prevent the counter from operating properly WARNING If voltage input is connected to circuits above 30 Vrms any lead may be at hazardous li...

Page 6: ...put voltage the neutral of the single phase AC signal is connected to Terminal 1 COM and line hot is connected to Terminal 4 LS The DC supply for the backlighting is connected as shown in the drawing...

Page 7: ...ctive Counter w Red Backlighting Counter w Yel Grn Backlighting Counter Positive Image Reflective PART NUMBER CUB7P000 CUB7P010 CUB7P020 CUB7P100 CUB7P110 CUB7P120 CUB7P200 CUB7P210 CUB7P220 BNL10000...

Page 8: ...armless from defend and indemnify RLC against damages claims and expenses arising out of subsequent sales of RLC products or products containing components manufactured by RLC and based upon personal...

Reviews: