background image

For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com

3

EMC INSTALLATION GUIDELINES

Although this unit is designed with a high degree of immunity to

ElectroMagnetic Interference (EMI), proper installation and wiring methods
must be followed to ensure compatibility in each application. The type of the
electrical noise, source or coupling method into the unit may be different for
various installations. In extremely high EMI environments, additional measures
may be needed. The unit becomes more immune to EMI with fewer I/O
connections. Cable length, routing and shield termination are very important
and can mean the difference between a successful or a troublesome installation.
Listed below are some EMC guidelines for successful installation in an
industrial environment.

1. Use shielded (screened) cables for all Signal and Control inputs. The shield

(screen) pigtail connection should be made as short as possible. The
connection point for the shield depends somewhat upon the application.
Listed below are the recommended methods of connecting the shield, in
order of their effectiveness.
a. Connect the shield only at the panel where the unit is mounted to earth

ground (protective earth).

b. Connect the shield to earth ground at both ends of the cable, usually when

the noise source frequency is above 1 MHz.

c. Connect the shield to common of the unit and leave the other end of the

shield unconnected and insulated from earth ground.

2. Never run Signal or Control cables in the same conduit or raceway with AC

power lines, conductors feeding motors, solenoids, SCR controls, and
heaters, etc. The cables should be run in metal conduit that is properly
grounded. This is especially useful in applications where cable runs are long
and portable two-way radios are used in close proximity or if the installation
is near a commercial radio transmitter.

3. Signal or Control cables within an enclosure should be routed as far away as

possible from contactors, control relays, transformers, and other noisy
components.

4. In extremely high EMI environments, the use of external EMI suppression

devices, such as ferrite suppression cores, is effective. Install them on Signal
and Control cables as close to the unit as possible. Loop the cable through the
core several times or use multiple cores on each cable for additional
protection. Install line filters on the power input cable to the unit to suppress
power line interference. Install them near the power entry point of the
enclosure. The following EMI suppression devices (or equivalent) are
recommended:

Ferrite Suppression Cores for signal and control cables:

Fair-Rite # 0443167251 (RLC #FCOR0000)
TDK # ZCAT3035-1330A
Steward #28B2029-0A0

Line Filters for input power cables:

Schaffner # FN610-1/07 (RLC #LFIL0000)
Schaffner # FN670-1.8/07
Corcom #1VR3

Note: Reference manufacturer’s instructions when installing a line filter.

5. Long cable runs are more susceptible to EMI pickup than short cable runs.

Therefore, keep cable runs as short as possible.

WIRING CONNECTIONS

The electrical connections are made via screw-clamp terminals located on

the back of the unit. All conductors should meet voltage and current ratings for
each terminal. Also, cabling should conform to appropriate standards of good
installation, local codes and regulations. It is recommended that power supplied
to the unit be protected by a fuse or circuit breaker. When wiring the unit, use
the battery cover to identify the wire position with the proper function. Strip the
wire, leaving approximately 1/4" bare wire exposed (stranded wires should be
tinned with solder). Insert the wire under the screw-clamp and tighten down the
screw until the wire is clamped in tightly. Each terminal can accept up to two
#14 AWG wires.

WARNING

: Lithium battery may explode if incinerated.

BATTERY INSTALLATION

1. Remove all power to the unit before removing battery cover.
2. To remove the battery cover, push upward in the direction of the arrow on

the rear cover (See drawing below), until the cover unlatches. Pull the
cover straight out from unit to fully remove.

3. Remove old battery* and replace it with an RLC battery (BNL10000).

Observe proper polarity when replacing the battery as shown in the
drawing.

4. Replace the cover. The battery cover is keyed so that it cannot be placed

upside down. The arrow on the rear of the cover should point toward the
top of the CUB7P when properly installed.

* - Dispose of properly.

WARNING

: Lithium battery may explode if incinerated.

Summary of Contents for CUB7P

Page 1: ...s that appear in the manual or on equipment must be observed to ensure personal safety and to prevent damage to either the instrument or equipment connected to it If equipment is used in a manner not...

Page 2: ...erature to 40 C Must use NEC Class 2 or SELV rated power supply 4 SIGNAL INPUT LS terminal 4 See Count Edge under Programming for incrementing edge of input signal Contact Input CUB7P0xx 30 Hz max fro...

Page 3: ...uch as ferrite suppression cores is effective Install them on Signal and Control cables as close to the unit as possible Loop the cable through the core several times or use multiple cores on each cab...

Page 4: ...when properly installed The units are intended to be mounted into an enclosed panel The viewing window and reset button are factory sealed for a washdown environment A sponge rubber gasket and mounti...

Page 5: ...max voltage drop 0 5 V when ON The OFF state leakage current must be less than 2 A Note The RC protection circuit on the RST Input causes a delay of approximately 15 msec in Reset response L S INPUT C...

Page 6: ...t versions of the CUB7P require an external 9 to 26 VDC power supply The external supply is connected between the V and common terminals as shown in the drawing APPLICATION TOTAL YARDS OF MATERIAL A f...

Page 7: ...For Sales and Support Contact Walker EMD Toll free 800 876 4444 Tel 203 426 7700 Fax 203 426 7800 www walkeremd com 7 This page intentionally left blank...

Page 8: ...or products containing components manufactured by RLC and based upon personal injuries deaths property damage lost profits and other matters which Buyer its employees or sub contractors are or may be...

Reviews: