16. ALARMS (Optional):
Solid State: Two, isolated, sinking open collector NPN transistors acting in
parallel with relays.
Imax = 100 mA;
V
SAT
= 1 V @ 100 mA;
V
MAX
= 30 VDC.
Relays:
Type: Form C (2)
Max. Rating: 5 A 120/240 VAC or 28 VDC
(resistive load)
, 1/8 HP
120 VAC
(inductive load)
.
Relay Life Expectancy: 100,000 cycles at Max. Rating.
(As load level
decreases, life expectancy increases.)
17. ANALOG OUTPUT (Optional): Digital scaling and offsetting.
4 to 20 mA:
Accuracy: 0.1% of full scale
Resolution: 12 bits
Compliance Voltage: 10 VDC
(500
W
max. loop impedance)
0 to 10 VDC :
Accuracy:
±
(0.1% of r35 mV)
Resolution: 12 bits
Min. Load Resistance: 10 K
W
(1 mA max.)
18. LINEARIZER/PEAK/VALLEY/TARE (optional):
9-segment multiple slope scaling for non-linear inputs. Peak and Valley
recording. Signal re-zero
(tare)
.
19. CONSTRUCTION: Die-cast metal front bezel that meets NEMA 4/IP65
requirements for indoor use when properly installed. Case body is black, high
impact plastic (panel gasket and mounting clips included). Installation
Category II, Pollution Degree 2.
20. CONNECTION: Removable terminal blocks
21. CERTIFICATIONS AND COMPLIANCES:
SAFETY
IEC 1010-1, EN 61010-1: Safety requirements for electrical equipment
for measurement, control, and laboratory use, Part 1.
IP65 Enclosure rating (Face only), IEC 529
Type 4 Enclosure rating (Face only), UL50
ELECTROMAGNETIC COMPATIBILITY
Immunity to EN 50082-2
Electrostatic discharge
EN 61000-4-2 Level 2; 4 Kv contact
1
Level 3; 8 Kv air
Electromagenetic RF fields
EN 61000-4-3 Level 3; 10 V/m
2
80 MHz - 1 GHz
Fast transients (burst)
EN 61000-4-4 Level 4; 2 Kv I/O
Level 3; 2 Kv power
RF conducted interference
EN 61000-4-6 Level 3; 10 V/rms
150 KHz - 80 MHz
Power frequency magnetic fields
EN 61000-4-8 Level 4; 30 A/m
Emissions to EN 50081-2
RF interference
EN 55011
Enclosure class A
Power mains class A
Notes:
1. Metal bezel of unit connected with ground lead from rear bezel screw to metal
mounting panel.
2. Self-recoverable loss of performance during EMI disturbance at 10 V/m:
process signal deviation less than 2% of full scale.
analog output signal deviation less than 8% of full scale.
For operation without loss of performance:
Unit is mounted in a metal enclosure (Buckeye SM7013-0 or equivalent)
I/O and power cables are routed in metal conduit connected to earth
ground.
Refer to the EMC Installation Guidelines section of the manual for additional
information.
22. WEIGHT: 1.2 lbs (0.5 kg).
-32-